Extract from the online
catalog
TRIO-PS/ 1AC/48DC/10
Order No.: 2866501
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866501
DIN rail power supply unit, primary-switched mode, 1-phase, output:
48 V DC / 10 A
Product notes
Commercial data
GTIN (EAN)
sales group
Pack
Customs tariff
Weight/Piece
Catalog page information
4046356287364
H009
1 pcs.
85044081
2.09 KG
Page 575 (IF-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
WEEE/RoHS-compliant since:
07/24/2008
Product description
TRIO POWER is the DIN-rail-mountable power supply unit with basic functions. With an output voltage of 12 V DC,
24 V DC and 48 V DC and 1- and 3-phase versions with 60 W or 960 W, it is particularly suited for use in series
production in mechanical engineering. The wide-range input and international certification package allows worldwide
implementation.
The high MTBF of 500,000 h stands for high supply reliability. The devices can be connected in parallel to increase the
capacity and redundancy.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 6
Oct 8, 2010
TRIO-PS/ 1AC/48DC/10
Order No.: 2866501
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866501
The clear LED signaling and the device connection with double terminal block for plus and minus for fast potential
distribution are further advantages of this device series. A third terminal block simplifies the grounding on the secondary
side. All power supply units are idle proof and short-circuit proof and provide a regulated and adjustable output voltage.
Technical data
Input data
Nominal input voltage
AC input voltage range
Short-term input voltage
AC frequency range
Current consumption
Nominal power consumption
Inrush surge current
Power failure bypass
Permissible backup fuse
Type of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Derating
Connection in parallel
Connection in series
Max. capacitive load
Current limitation
Control deviation
48 V DC ±1%
30 V DC ... 56 V DC (> 48 V constant capacity)
10 A (-25°C ... 55°C)
+55°C to +70°C: 2.5% per Kelvin
55 °C ... 70 °C (2.5%/K)
Yes, for redundancy and increased capacity
Yes
Unlimited
Approx 11.4 A (in the event of a short-circuit)
< 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple
Peak switching voltages nominal load
Maximum power dissipation idling
Power loss nominal load max.
< 50 mV
PP
< 50 mV
PP
8W
49 W
100 V AC ... 240 V AC
85 V AC ... 264 V AC (derating < 90 V AC: 2.5% per Kelvin)
300 V AC
45 Hz ... 65 Hz
Approx. 4.6 A (120 V AC)
Approx. 2.4 A (230 V AC)
(> 48 V constant capacity)
< 15 A
> 13 ms (120 V AC)
> 18 ms (230 V AC)
B16
Transient surge protection
Varistor
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 6
Oct 8, 2010
TRIO-PS/ 1AC/48DC/10
Order No.: 2866501
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866501
General data
Width
Height
Depth
Net weight
Operating voltage display
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Mounting position
Assembly instructions
Electromagnetic compatibility
Noise immunity
Low Voltage Directive
Standard – Electrical equipment of machines
Standard - Safety of transformers
Standard - Electrical safety
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
Standard – Safety extra-low voltage
Standard - Safe isolation
Standard – Protection against electric shock
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
Standard – Limitation of mains harmonic currents
115 mm
130 mm
152.5 mm
1.9 kg
LED green
> 91 % (At 230 V AC and nominal values)
4 kV AC (type test)
2 kV AC (routine test)
IP20
I, with PE connection
> 500 000 h in acc. with IEC 61709 (SN 29500)
-25 °C ... 70 °C (> 55° C derating)
-40 °C ... 85 °C
95 % (at 25 °C, no condensation)
Horizontal DIN rail NS 35, EN 60715
Can be aligned: Horizontal 0 cm, vertical 5 cm
Conformance with EMC directive 2004/108/EC
EN 61000-6-2:2005
Conformance with LV directive 2006/95/EC
EN 60204
EN 61558-2-17
EN 60950/VDE 0805 (SELV)
EN 61558-2-17
EN 50178/VDE 0160 (PELV)
EN 60950 (SELV)
EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN 57100-410
DIN VDE 0106-101
EN 61000-3-2
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 6
Oct 8, 2010
TRIO-PS/ 1AC/48DC/10
Order No.: 2866501
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866501
UL approvals
Surge voltage category
Connection data, input
Type of connection
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
Screw thread
Connection data, output
Type of connection
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
Signaling
Status display
Note on status display
Certificates / Approvals
UL Listed UL 508
UL/C-UL Recognized UL 60950
III
Screw connection
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
14
9 mm
M2,5
Screw connection
0.5 mm²
0.6 mm²
0.5 mm²
4 mm²
20
10
14 mm
"DC OK" LED green
U
OUT
< 0.9 x U
N
: LED flashing
Certification
CUL, CUL Listed, UL, UL Listed
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 6
Oct 8, 2010
TRIO-PS/ 1AC/48DC/10
Order No.: 2866501
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866501
Diagrams/Drawings
Block diagram
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 6