American
Electrical, Inc.
Industrial Electrical Accessories
425 southlake blvd. • Suite 9-B • Richmond, VA 23236 • (804) 379-2899 • Fax: (804) 379-8935
DIN Rail Mounted Circuit Breakers
UL 1077 Rated
Features:
• UL 1077 Approved (UL 489
also Available)
• DIN Rail Mounted
• Compact 13 mm width
• One, Two & Three Pole
• Current Rating up to 50 A
• 100% Rating Capability
• Hydraulic-Magnetic
Technology
Technical Data:
Numbers of Poles
maximum Voltage
Minimum Amp Rating
maximum Amp Rating
Interrupting Cap.
1, 2 & 3
277/480 50/60 Hz
1 Amp
50 Amp
5000A @ 120V
1000A @ 277V
1000A @ 480V
1960V 50/60 Hz
100 Megaohm
-40˚C to +60˚C
Dielectric Strength
insulation resistance
Operating Temp. Range
Part Numbering System:
C____A___P
No. of Poles: 1, 2 or 3
Amperage:
e.g., 1 for 1 Amp, 15 for 15 Amp, etc.
Example: C10A1P = 10A single Pole Circuit Breaker
American
Electrical, Inc.
Industrial Electrical Accessories
425 southlake blvd. • Suite 9-B • Richmond, VA 23236 • (804) 379-2899 • Fax: (804) 379-8935
DIN Rail Mounted Circuit Breakers
UL 489 Rated
Features:
• UL 489 Approved (UL 1077
also Available)
• DIN Rail Mounted
• Compact 13 mm width
• One & Two Pole only
• Current Rating up to 25 A
• 100% Rating Capability
• Hydraulic-Magnetic
Technology
Part Numbering System:
Technical Data:
Numbers of Poles
maximum Voltage
Minimum Amp Rating
maximum Amp Rating
Interrupting Cap.
Dielectric Strength
insulation resistance
Operating Temp. Range
1and 2 pole only
120/240V 50/60 Hz
1 Amp
25 Amp
10,000 A
1500V 50/60 Hz
100 Megaohm
-40˚C to +60˚C
C____A___P-489
No. of Poles: 1or 2
Amperage:
e.g., 1 for 1 Amp, 15 for 15 Amp, etc.
Example: C10A1P-489 = 10A single Pole Circuit Breaker UL 489 Rated