Product data sheet
Characteristics
9001KA3
control button contact block - 9001-K Ø 30 - 1
NC protected terminals
Main
Range of product
Product or component
type
Component name
Contacts type and
composition
Contacts operation
Connections - terminals
Harmony 9001K
Contact block with protected terminals
9001K
1 NC
Standard
Screw clamp terminals , 1 x 0.22...2 x 1.5 mm²
conforming to IEC 60947-1
Complementary
Tightening torque
[Ie] rated operational current
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contacts material
Positive opening
Short circuit protection
[Ith] conventional free air thermal current
[Icm] rated short-circuit making capacity
0.8 N.m cross slotted screw head conforming to IEC 60947-1
0.55 A at 125 V DC-13 , A600-Q600
3 A at 240 V AC-15 , A600-Q600
250 V pollution degree 3 conforming to IEC 60947-1
2.5 kV conforming to IEC 60947-1
Silver alloy contacts
With conforming to IEC 60947-5-2
10 A cartridge fuse protection conforming to IEC 60947-5-1
10 A
≤ 0.1 kA at 600 V DC-13
≤ 0.27 kA at 250 V DC-13
≤ 0.55 kA at 125 V DC-13
≤ 12 kA at 600 V AC-15 , 7200 VA
≤ 15 kA at 480 V AC-15 , 7200 VA
≤ 30 kA at 240 V AC-15 , 7200 VA
≤ 60 kA at 120 V AC-15 , 7200 VA
≤ 0.1 kA at 600 V DC-13
≤ 0.27 kA at 250 V DC-13
≤ 0.55 kA at 125 V DC-13
≤ 1.2 kA at 600 V AC-15 , 720 VA
≤ 1.5 kA at 480 V AC-15 , 720 VA
≤ 3 kA at 240 V AC-15 , 720 VA
≤ 6 kA at 120 V AC-15 , 720 VA
0.023 kg
Rated breaking capacity
Product weight
Environment
Standards
CSA C22-2 No 14
EN/IEC 60947-5-1
IEC 60947-1
IEC 60947-5-4
JIS C 4520
JIS C 852
UL 508
TC
-40...70 °C
-25...70 °C
7 gn (f = 2...500 Hz) conforming to IEC 60068-2-6
50 gn conforming to IEC 60068-2-27
Class II conforming to IEC 60536
IP20 conforming to NF C 20-010
IP20 conforming to IEC 60529
1
Protective treatment
Ambient air temperature for storage
Ambient air temperature for operation
Vibration resistance
Shock resistance
Class of protection against electric shock
IP degree of protection
15/2/2012
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.