Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
8412 Multi-Conductor - Two-Conductor, Low-Impedance Cable
For more Information
please call
1-800-Belden1
Description:
20 AWG stranded (26x34) high-conductivity TC conductors, EPDM rubber insulation, rayon braid, TC braid
shield (85% coverage), cotton wrap, EPDM jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
2
20
26x34
Dia. (mm)
High Conductivity TC - Tinned Copper 0.9398
Insulation
Insulation Material:
Insulation Material
Wall Thickness (mm) Dia. (mm)
2.1082
EPDM - Ethylene Propylene Diene Monomer Rubber 0.5842
Outer Shield
Outer Shield Material:
Layer # Type Outer Shield Material Coverage (%)
1
2
Braid Cotton
Braid TC - Tinned Copper
85
Outer Shield Separator Material:
Cotton Wrap
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (mm)
EPDM - Ethylene Propylene Diene Monomer Rubber 0.889
Overall Cabling
Overall Cabling Color Code Chart:
Number Color
1
2
White
Black
Overall Cabling Separator Material:
Overall Nominal Diameter:
Rayon Braid
6.655 mm
Mechanical Characteristics (Overall)
Operating Temperature Range:
Non-UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-50°C To +90°C
90°C
65.481 Kg/Km
444.820 N
69.850 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
EU CE Mark:
EU Directive 2000/53/EC (ELV):
Yes
Yes
Page 1 of 3
05-10-2011
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
8412 Multi-Conductor - Two-Conductor, Low-Impedance Cable
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Yes
01/01/2004
Yes
Yes
Yes
Yes
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
67.000
Nom. Inductance:
Inductance (µH/m)
0.59058
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
108.273
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
190.298
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
34.779
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
14.765
Max. Operating Voltage - Non-UL:
Voltage
600 V RMS
Max. Recommended Current:
Current
4 Amps per conductor @ 25°C
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Item #
8412 0021000
8412 0041000
8412 0061000
8412 010U1000
8412 010U500
8412 010100
8412 0101000
8412 010250
8412 010500
Notes:
C = CRATE REEL PUT-UP.
Putup
305 MT
305 MT
305 MT
305 MT
152 MT
30 MT
305 MT
76 MT
152 MT
Ship Weight
21.319 KG
21.319 KG
21.319 KG
20.865 KG
10.659 KG
2.359 KG
21.319 KG
5.443 KG
9.979 KG
Color
RED
YELLOW
BLUE, LIGHT
BLACK
BLACK
BLACK
BLACK
BLACK
BLACK
C
C
Notes
C
C
C
Item Desc
2 #20 EPDM BRD EPDM
2 #20 EPDM BRD EPDM
2 #20 EPDM BRD EPDM
2 #20 EPDM SHLD EPDM
2 #20 EPDM SHLD EPDM
2 #20 EPDM BRD EPDM
2 #20 EPDM BRD EPDM
2 #20 EPDM BRD EPDM
2 #20 EPDM BRD EPDM
Page 2 of 3
05-10-2011
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
8412 Multi-Conductor - Two-Conductor, Low-Impedance Cable
Revision Number: 3
© 2011 Belden, Inc
All Rights Reserved.
Revision Date: 09-01-2009
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
05-10-2011