Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
9462 Multi-Conductor - Audio, Control and Instrumentation Cable
For more Information
please call
1-800-Belden1
General Description:
22 AWG stranded (7x30) tinned copper conductors, PVC insulation, twisted pair, overall Beldfoil® shield
(100% coverage), 22 AWG stranded TC drain wire, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
1
22
7x30
TC - Tinned Copper
2
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material
Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.014
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material
Beldfoil® (Z-Fold®)
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
22
7x30
TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride .035
Overall Cable
Overall Nominal Diameter:
0.186 in.
Pair
Pair Color Code Chart:
Number Color
1
Black & Red
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-30°C To +80°C
80°C (UL AWM Style 2464)
19 lbs/1000 ft.
27 lbs.
2 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
AWM Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
CMG
CMG
UL Style 2464 (300 V 80°C)
Yes
Yes
Yes
Yes
04/01/2005
Page 1 of 2
08-12-2014
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
9462 Multi-Conductor - Audio, Control and Instrumentation Cable
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
CSA Flame Test:
UL1685 FT4 Loading
FT4
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
36
Nom. Inductance:
Inductance (µH/ft)
0.19
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
50
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
90
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
16
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
9462 060U1000
9462 060U500
9462 060100
9462 0601000
9462 060500
9462 0605000
Putup
1,000 FT
500 FT
100 FT
1,000 FT
500 FT
5,000 FT
Ship Weight
21.000 LB
11.000 LB
2.700 LB
21.000 LB
10.500 LB
105.000 LB
Color
CHROME
CHROME
CHROME
CHROME
CHROME
CHROME
CZ
C
Notes
Item Desc
2 #22 PVC FS PVC
2 #22 PVC FS PVC
2 #22 PVC FS PVC
2 #22 PVC FS PVC
2 #22 PVC FS PVC
2 #22 PVC FS PVC
Notes:
C = CRATE REEL PUT-UP.
Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
Revision Number: 2
© 2014 Belden, Inc
All Rights Reserved.
Revision Date: 08-15-2012
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 2 of 2
08-12-2014