https://www.phoenixcontact.com/pi/products/2811569
Signal conditioner - MACX MCR-UI-UI-UP-SP-NC - 2811569
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Isolating amplifier with safe electrical isolation and wide-range power supply (24 V ... 230 V AC/DC). DIP
switches on the front, over 1600 signal conversions can be set. Standard configuration (IN 0 ... 10 V/OUT 0 ...
20 mA), spring-cage connection, SIL.
Your advantages
Over 1600 signal conversions can be set via DIP switches on the front
Installation in zone 2 permitted
Up to SIL 2 according to EN 61508
Analog signal conditioner for isolating, filtering, amplifying, and converting standard analog signals
Plug-in screw or spring-cage connection technology (Push-in technology)
Active or passive output
Configurable input and output signals including bipolar current and voltage signals
Status indicator for supply voltage
Wide-range power supply of 19.2 ... 253 V AC/DC
3-way electrical isolation
Key Commercial Data
Packing unit
GTIN
GTIN
4046356466998
1 pc
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
12.5 mm
99 mm
10/25/2018 Page 1 / 9
https://www.phoenixcontact.com/pi/products/2811569
Signal conditioner - MACX MCR-UI-UI-UP-SP-NC - 2811569
Technical data
Dimensions
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Maximum altitude
-20 °C ... 70 °C
-40 °C ... 85 °C
≤ 2000 m
Input data
Number of inputs
Voltage input signal
1
0 mV ... 50 mV
0 mV ... 60 mV
0 mV ... 75 mV
0 mV ... 100 mV
0 mV ... 120 mV
0 mV ... 150 mV
0 mV ... 200 mV
0 mV ... 300 mV
0 mV ... 500 mV
0 V ... 1 V
0 V ... 1.5 V
0 V ... 2 V
0 V ... 3 V
0 V ... 5 V
0 V ... 10 V (Configurable via DIP switches)
0 V ... 15 V
0 V ... 20 V
0 V ... 30 V
0 V ... 50 V
0 V ... 100 V
-50 mV ... 50 mV
-60 mV ... 60 mV
-75 mV ... 75 mV
-100 mV ... 100 mV
-120 mV ... 120 mV
-150 mV ... 150 mV
-200 mV ... 200 mV
-300 mV ... 300 mV
-500 mV ... 500 mV
-1 V ... 1 V
-1.5 V ... 1.5 V
-2 V ... 2 V
-3 V ... 3 V
10/25/2018 Page 2 / 9
https://www.phoenixcontact.com/pi/products/2811569
Signal conditioner - MACX MCR-UI-UI-UP-SP-NC - 2811569
Technical data
Input data
-5 V ... 5 V
-10 V ... 10 V
-15 V ... 15 V
-20 V ... 20 V
-30 V ... 30 V
-50 V ... 50 V
-100 V ... 100 V
1 V ... 5 V
2 V ... 10 V
Current input signal
0 mA ... 1 mA (Configurable via DIP switches)
0 mA ... 1.5 mA
0 mA ... 2 mA
0 mA ... 3 mA
0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 15 mA
0 mA ... 20 mA
0 mA ... 30 mA
0 mA ... 50 mA
0 mA ... 100 mA
-1 mA ... 1 mA
-1.5 mA ... 1.5 mA
-2 mA ... 2 mA
-3 mA ... 3 mA
-5 mA ... 5 mA
-10 mA ... 10 mA
-15 mA ... 15 mA
-20 mA ... 20 mA
-30 mA ... 30 mA
-50 mA ... 50 mA
-100 mA ... 100 mA
1 mA ... 5 mA
2 mA ... 10 mA
4 mA ... 20 mA
max. input voltage
Max. input current
Input resistance of voltage input
Input resistance current input
± 100 V
± 100 mA
approx. 1 MΩ (± 1 V DC ... ± 100 V DC)
approx. 10 Ω (± 10 mA DC ... ± 100 mA DC)
Output data
Number of outputs
1
10/25/2018 Page 3 / 9
https://www.phoenixcontact.com/pi/products/2811569
Signal conditioner - MACX MCR-UI-UI-UP-SP-NC - 2811569
Technical data
Output data
Configurable/programmable
Voltage output signal
Yes, can be switched
0 V ... 10 V (Configurable via DIP switches)
0 V ... 5 V
2 V ... 10 V
1 V ... 5 V
-10 V ... 10 V
-5 V ... 5 V
0 V ... 2.5 V
0.5 V ... 2.5 V
-2.5 V ... 2.5 V
Current output signal
0 mA ... 5 mA
0 mA ... 10 mA
0 mA ... 20 mA (Configurable via DIP switches)
1 mA ... 5 mA
2 mA ... 10 mA
4 mA ... 20 mA
-5 mA ... 5 mA
-10 mA ... 10 mA
-20 mA ... 20 mA
Max. output voltage
Max. output current
Load/output load voltage output
Load/output load current output
Ripple
15 V
35 mA
≥ 1 kΩ (10 V)
≤ 600 Ω (20 mA; active)
passive: ≤ (UB-2 V) / I
outmax
< 10 mV
rms
Power supply
Supply voltage range
24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Connection data
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Stripping length
Connection technology
Push-in connection
0.2 mm²
1.5 mm²
24
16
0.2 mm²
1.5 mm²
8 mm
COMBICON
General
No. of channels
1
10/25/2018 Page 4 / 9
https://www.phoenixcontact.com/pi/products/2811569
Signal conditioner - MACX MCR-UI-UI-UP-SP-NC - 2811569
Technical data
General
Maximum transmission error
Maximum temperature coefficient
Limit frequency (3 dB)
Alignment zero
Alignment span
Step response (10-90%)
Protective circuit
Overvoltage category
Degree of pollution
Rated insulation voltage
Electromagnetic compatibility
Noise immunity
Color
Housing material
Mounting position
Conformance
ATEX
IECEx
UL, USA/Canada
≤ 0.1 % (Compared to the final value)
0.0075 %/K
10 kHz (Can be switched to 30 Hz)
±4%
±4%
35 µs (at 10 kHz)
11 ms (At 30 Hz)
Transient protection
II
2
300 V AC
Conformance with EMC directive
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
green
PA 6.6-FR
any
CE-compliant
II 3 G Ex nA IIC T4 Gc
Ex nA IIC T4 Gc
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC
Safety characteristic data
Integrity requirement
Designation
Architecture
Equipment type
Safety Integrity Level (SIL)
Safe Failure Fraction (SFF)
MTBF
λ
SU
λ
SD
λ
DU
λ
DD
Probability of a hazardous failure on demand (PFD
AVG
)
Diagnostic coverage (DC)
Integrity requirement
Designation
Architecture
IEC 61508 - Low demand
Input isolator (live zero signals)
Single-channel, 1oo1
Type A
2
85.9 %
231 Years
3.7 x 10 (370 FIT)
0
6 x 10 (60 FIT)
0
2.7 x 10 (1 year)
0%
IEC 61508 - Low demand
Output isolator (live zero signals)
Single-channel, 1oo1
10/25/2018 Page 5 / 9
-4
-8
-7