RSMN Series
3A to 60A, 250VAC EMI Filters
Features
High Voltage Pulse Attenuation
Two Stage Filter for Better Performance
DIN Rail Mount Option (Up 30A)
Low Earth Leakage Current Option (Up to 30A)
Conforms to UL, CSA and EN Safety Agency Certifications
Specifications
Model
Rated Voltage (AC, DC)
Rated Current
Withstand Voltage
Isolation Resistance
Leakage Current (max)
DC Resistance (total)
RSMN-2003
RSMN-2003D
RSMN-2003L
V
A
V
MΩ
A
mΩ
3A
RSMN-2010
RSMN-2016
RSMN-2010D
RSMN-2016D
RSMN-2010L
RSMN-2016L
250V
6A
10A
16A
Terminals to Case: 2500VAC (1 Minute)
100MΩ minimum (500VDC, 1 Minute)
RSMN-20xx 1mA; RSMN20xxL 10uA (250VAC, 60Hz)
140
60
35
RSMN-2040
RSMN-2050
RSMN-2060
RSMN-2006
RSMN-2006D
RSMN-2006L
RSMN-2020
RSMN-2020D
RSMN-2020L
20A
350
RSMN-2030
RSMN-2030D
RSMN-2030L
22
Model
Rated Voltage (AC, DC)
Rated Current
Withstand Voltage
Isolation Resistance
Leakage Current (max)
DC Resistance (total)
Operating Temperature
Storage Temperature
Safety Agency Certifications
Weight
Warranty
V
A
V
MΩ
A
mΩ
°C
°C
-
g
yr
30A
12
250V
40A
50A
60A
Terminals to Case: 2500VAC (1 Minute)
100MΩ minimum (500VDC, 1 Minute)
RSMN-20xx 1mA; RSMN20xxL 10uA (250VAC, 60Hz)
10
8
6
-25 to +85°C (Derate above 55°C, see derating curve)
-25 to +85°C
Up to 30A Models - UL1283, CSA C22.2 No.8, EN60939
190g to 960g model dependant (See weights chart on website)
5 Year
Derating
Circuit
Options
Chassis Mount & Standard Leakage Current
DIN Rail Mount & Standard Leakage Current
Chassis Mount & Low Leakage Current
RSMN-20xx
RSMN-20xxD
RSMN-20xxL
1-800-526-2324 • www.us.tdk-lambda.com/lp/
284
Disclaimer: us.tdk-lambda.com/lp/legal.htm
RSMN Series
Outline Drawing
For Additional Information, please visit
us.tdk-lambda.com/lp/products/r-series.htm
1-800-526-2324 • www.us.tdk-lambda.com/lp/
285
Revision A4: Jan 2018