Type 2 arrester replacement plug (surge arrester) with leakage current free connection in series, consisting of a
varistor and gas-filled surge arrester.
Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
46.0 g
85363030
Germany
Technical data
Ambient conditions
Degree of protection
Ambient temperature (operation)
IP20
-40 °C ... 80 °C
General
Housing material
Flammability rating according to UL 94
Color
Standards for cearances and creepage distances
PBT
V0
gray
DIN VDE 0110-1
IEC 60664-1
IEC 61643-1
Overvoltage category
Degree of pollution
Mounting type
Type
III
2
On base element
DIN rail module, two-section, divisible
04/18/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2859615
Type 2 surge protection plug - VAL-CP-350 VF-ST - 2859615
Technical data
General
Number of positions
Surge protection fault message
Direction of action
1
optical
L-N / L-PEN
Protective circuit
IEC test classification
EN type
Maximum continuous operating voltage U
C
U
T
(TOV-proof)
Nominal frequency f
N
Residual current I
PE
Standby power consumption P
C
Power consumption without load Pc
Max. discharge current I
max
(8/20) µs
Nominal discharge current I
n
(8/20) µs
Front of wave sparkover voltage at 6 kV (1.2/50) µs
Voltage protection level U
p
Residual voltage
II
T2
T2
350 V AC
350 V AC (5 sec.)
50 Hz
60 Hz
≤ 1 µA (Residual current I
PE
)
≤ 0.35 mW
≤ 0.35 mW
20 kA
10 kA
≤ 1.5 kV
≤ 1.5 kV
≤ 1.1 kV (at I
n
)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Clamping voltage ringwave
≤ 1.3 kV (category C3 20 kV/10 kA)
≤ 1.2 kV (category C2 10 kV/5 kA)
≤ 1.1 kV (category B3/C1 6 kV/3 kA)
Response time t
A
Max. backup fuse with branch wiring
Short-circuit resistance I
P
with max. backup fuse (effective)
≤ 100 ns
125 A (gL/gG)
25 kA
Connection, protective circuit
Connection method
Connection type IN
Connection type OUT
Plug connection
FLASHTRAB/VALVETRAB plug-in system
FLASHTRAB/VALVETRAB plug-in system
Standards and Regulations
Standards/regulations
IEC 61643-1 1998
DIN EN 61643-11 2002
UL 1449
04/18/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2859615
Type 2 surge protection plug - VAL-CP-350 VF-ST - 2859615
Technical data
Standards and Regulations
IEEE C62.1 / C62.34 / C62.45
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
27140201
27130801
27130801
27130801
27130805
27130805
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000941
EC000941
EC000941
EC000941
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Accessories
Accessories
Device marking
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: Plotter, Mounting type: Snap into tall marker groove, for
terminal block width: 18 mm, Lettering field: 18 x 5 mm
Labeled device marker
04/18/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2859615
Type 2 surge protection plug - VAL-CP-350 VF-ST - 2859615
Accessories
Marker for terminal blocks - ZBN 18,LGS:ERDE - 2749589
Marker for terminal blocks, Strip, white, labeled, Horizontal: Grounding symbol, Mounting type: Snap into tall marker
groove, for terminal block width: 18 mm, Lettering field: 18 x 5 mm
Marker pen
Marker pen - B-STIFT - 1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
04/18/2016 Page 4 / 4