https://www.phoenixcontact.com/us/products/2819707
Inline function terminal - IB IL TEMP 4 UTH HEI 1 DO4-PAC - 2819707
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline temperature measurement terminal, complete with accessories (connection plug and labeling field) with
process data multiplex with 4 thermocouple inputs, 8 binary outputs (24 V, 70 mA), 1 input for recording the total
current of heating elements.
Product Features
■
■
■
■
I/Os for 4 closed-loop control circuits
Connection of thermocouples according to DIN EN 60584-1 and DIN 43710
Output for solid-state relay
Input for heating current acquisition
Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
260.0 g
85389091
Germany
Technical data
Dimensions
Width
Height
Depth
48.8 mm
119.8 mm
71.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Degree of protection
0 °C ... 55 °C
-25 °C ... 85 °C
75% average, 85% seldom
75% average, 85% seldom
IP20
General
Mounting type
Net weight
DIN rail
122 g
04/24/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2819707
Inline function terminal - IB IL TEMP 4 UTH HEI 1 DO4-PAC - 2819707
Technical data
Interfaces
Designation
Connection method
Transmission speed
Transmission physics
Inline local bus
Inline data jumper
500 kBit/s
Copper
Inline potentials
Communications power U
L
Current consumption from U
L
Segment circuit supply U
S
Current consumption from U
S
I/O supply voltage U
ANA
Current consumption from U
ANA
7.5 V DC (via voltage jumper)
max. 150 mA
typ. 90 mA
24 V DC (via voltage jumper)
max. 600 mA
24 V DC (via voltage jumper)
max. 30 mA
typ. 20 mA
Analog inputs
Number of inputs
Input name
Connection method
Sensor types that can be used (TC)
Measured value representation
A/D conversion time
4
Analog UTH inputs
Spring-cage connection
2-wire (floating)
B, C, D, E, J, K, L, N, R, S, T
Depends on thermocouple
max. 225 ms
Digital outputs
Output name
Number of outputs
Output voltage
Output current
Digital outputs
4
24 V DC
70 mA (short-circuit resistant)
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
27250304
27250304
27250304
27242605
27242605
04/24/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2819707
Inline function terminal - IB IL TEMP 4 UTH HEI 1 DO4-PAC - 2819707
Classifications
eCl@ss
eCl@ss 7.0
27242605
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001433
EC001601
EC001601
EC001596
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
43172015
43201404
43172015
43201404
43201404
Accessories
Accessories
Labeling panel
Labeling field - IB IL FIELD 8 - 2727515
Labeling field, width: 48.8 mm
Plug
Inline connector - IB IL SCN-8 - 2726337
Connector, for digital 1, 2 or 8-channel Inline terminals
Terminal marking
04/24/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2819707
Inline function terminal - IB IL TEMP 4 UTH HEI 1 DO4-PAC - 2819707
Accessories
Insert strip - ESL 62X46 - 0809502
Insert strip, Sheet, white, unlabeled, can be labeled with: Office printing systems, Plotter: Laser printer, Mounting type:
Insert, Lettering field: 62 x 46 mm
Drawings
Connection diagram
1.1
2.1
1.1
2.1
Dimensional drawing
OUT 1
1.2
2.2
1.2
2.2
1.2
2.2
1.2
2.2
119,8
1.3
2.3
1.3
2.3
1.3
2.3
1.3
2.3
1.4
2.4
1.4
2.4
1.4
2.4
1.4
2.4
OUT 8
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
71,5