https://www.phoenixcontact.com/us/products/2800603
Type 1/2 surge protection device - SYS-SET/LTE-RRU BOX - 2800603
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Key commercial data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
4615.6 GRM
85369010
Germany
Technical data
Dimensions
Height
Width
Depth
361 mm
254 mm
165 mm
Ambient conditions
Degree of protection
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
IP66
IP66
A, B
-25 °C ... 55 °C (Above 38 °C, derating of 1.96 A/K)
-40 °C ... 70 °C
General
Housing material
Cover material
Inflammability class according to UL 94
Color
Standards for air and creepage distances
Polycarbonate, glass-fiber-reinforced
Polycarbonate, glass-fiber-reinforced
V2 (Gehäuse / Deckel)
light grey RAL 7035
DIN VDE 0110-1
IEC 60664-1
IEC 61643-1
09/10/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2800603
Type 1/2 surge protection device - SYS-SET/LTE-RRU BOX - 2800603
Technical data
General
Surge voltage category
Pollution degree
Mounting type
Type
Arrester can be tested with CHECKMASTER from software version:
Surge protection fault message
Direction of action
III
2
Wall mounting/optional mounting on round masts
Installation housing
From SW rev. 3.00
Optical, remote indicator contact
1L-N & N-PE
Protective circuit
IEC test classification
EN type
Nominal voltage U
N
Maximum continuous operating voltage U
C
(L-N)
Maximum continuous operating voltage U
C
(N-PE)
U
T
(TOV-proof)
U
T
(TOV-safe)
TOV behavior at U
T
Rated load current I
L
Residual current I
PE
Nominal discharge current I
n
(8/20) µs (L-N)
Nominal discharge current I
n
(8/20) µs (L-PE)
Nominal discharge current I
n
(8/20) µs (N-PE)
Impulse discharge current (10/350) µs charge
Impulse discharge current (10/350)½µs, specific energy
Impulse discharge current (10/350)½µs, peak value l
imp
Impulse discharge current (10/350) µs charge
Impulse discharge current (10/350)½µs, specific energy
Impulse discharge current (10/350)½µs, peak value l
imp
Impulse discharge current (10/350) µs charge
Impulse discharge current (10/350)½µs, specific energy
Impulse discharge current (10/350)½µs, peak value l
imp
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-N)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PE)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)
Voltage protection level U
p
(L-N)
Voltage protection level U
p
(L-PE)
Voltage protection level U
p
(N-PE)
T1 + T2
T1 + T2
-48 V DC
350 V AC
350 V AC
≤ 415 V AC (5 s / L-N)
≤ 1200 V AC (200 ms / N-PE)
<p></p>
125 A (≤ 55°C)
≤ 0.01 mA
25 kA
25 kA
100 kA
12.5 As
160 kJ/Ω
25 kA
50 As
2500 kJ/Ω
100 kA
12.5 As
160 kJ/Ω
25 kA
≤ 1.5 kV
≤ 2.2 kV
≤ 1.5 kV
≤ 1.5 kV
≤ 2.2 kV
≤ 1.5 kV
09/10/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2800603
Type 1/2 surge protection device - SYS-SET/LTE-RRU BOX - 2800603
Technical data
Protective circuit
Residual voltage (L-N)
≤ 1.3 kV (at I
n
)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 1 kV (at 3 kA)
Residual voltage (L-PE)
≤ 2.2 kV (at I
n
)
≤ 2 kV (at 10 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.6 kV (at 3 kA)
Residual voltage (N-PE)
≤ 1.5 kV (at I
n
)
≤ 1 kV (at 10 kA)
≤ 0.9 kV (at 5 kA)
≤ 0.8 kV (at 3 kA)
Response time (L-N)
Response time (N-PE)
Max. backup fuse with branch wiring
Max. backup fuse with V-type through wiring
Short-circuit resistance I
P
with max. backup fuse (effective)
Short-circuit current self-quenching
Follow current quenching capacity If (L-N)
Follow current quenching capacity If (N-PE)
≤ 25 ns
≤ 100 ns
315 A AC (gG)
125 A AC (gG)
25 kA
100 A (effective (N-PE))
25 kA (264 V AC)
3 kA (350 V AC)
100 A (350 V AC)
Remote indicator contact
Connection name
Switching function
Connection method
Screw thread
Tightening torque
Stripping length
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section solid min.
Conductor cross section solid max.
AWG conductor cross section
Maximum operating voltage U
max.
AC
Remote fault indicator contact
PDT contact
Plug-in/screw connection via COMBICON
M2
0.25 Nm
4 lb
f
-in.
7 mm
0.14 mm²
1.5 mm²
0.14 mm²
1.5 mm²
28 ... 16
30 ... 14 (UL)
250 V AC
09/10/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2800603
Type 1/2 surge protection device - SYS-SET/LTE-RRU BOX - 2800603
Technical data
Remote indicator contact
Maximum operating voltage U
max
DC
Max. operating current I
max
125 V DC
1 A AC (inductive)
1 A AC (ohmic)
30 mA DC (inductive)
200 mA DC (ohmic)
Standards and Regulations
Standards/regulations
EN 61439-2 2011
IEC 61439-2 2011
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27140201
27140201
27140201
27140201
27140201
27140201
27140201
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001473
EC002498
EC001457
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
09/10/2014 Page 4 / 4