https://www.phoenixcontact.com/hq/products/3045907
Plug - UPBV 4/11 - 3045907
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Plug, Connection method: Screw connection, Number of positions: 11, Cross section: 0.14 mm² - 6 mm²,
AWG: 26 - 10, Width: 68.2 mm, Height: 48.5 mm, Color: gray
The illustration shows the 6-position
version
Why buy this product
Can be bridged with FBS ... standard bridges
Connector with lateral conductor connection direction
The connected conductors can be led directly into the cable duct to save space
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4046356083416
85366990
Made to Order (non-returnable)
10 STK
Technical data
General
Number of positions
Number of levels
Number of connections
Potentials
Nominal cross section
Color
Insulating material
Flammability rating according to UL 94
Maximum load current
Rated surge voltage
11
1
11
1
4 mm²
gray
PA
V0
32 A (with 6 mm² conductor cross section)
8 kV
11/15/2016 Page 1 / 5
https://www.phoenixcontact.com/hq/products/3045907
Plug - UPBV 4/11 - 3045907
Technical data
General
Degree of pollution
Overvoltage category
Insulating material group
Maximum load current
Nominal current I
N
Nominal voltage U
N
Relative insulation material temperature index (Elec., UL 746 B)
Temperature index of insulation material (DIN EN 60216-1 (VDE
0304-21))
Static insulating material application in cold
Behavior in fire for rail vehicles (DIN 5510-2)
Flame test method (DIN EN 60695-11-10)
Oxygen index (DIN EN ISO 4589-2)
NF F16-101, NF F10-102 Class I
NF F16-101, NF F10-102 Class F
Surface flammability NFPA 130 (ASTM E 162)
Specific optical density of smoke NFPA 130 (ASTM E 662)
Smoke gas toxicity NFPA 130 (SMP 800C)
Calorimetric heat release NFPA 130 (ASTM E 1354)
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23
Fire protection for rail vehicles (DIN EN 45545-2) R24
Fire protection for rail vehicles (DIN EN 45545-2) R26
3
III
I
32 A (with 6 mm² conductor cross section)
32 A
800 V
130 °C
130 °C
-60 °C
Test passed
V0
>32 %
2
2
passed
passed
passed
28 MJ/kg
HL 1 - HL 3
HL 1 - HL 3
HL 1 - HL 3
HL 1 - HL 3
Dimensions
Width
Length
Height
Pitch
68.2 mm
22 mm
48.5 mm
32.2 mm
6.2 mm
Connection data
Connection method
Connection in acc. with standard
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Min. AWG conductor cross section, flexible
Max. AWG conductor cross section, flexible
Screw connection
IEC 61984
0.14 mm²
6 mm²
26
10
0.14 mm²
6 mm²
26
10
11/15/2016 Page 2 / 5
https://www.phoenixcontact.com/hq/products/3045907
Plug - UPBV 4/11 - 3045907
Technical data
Connection data
Conductor cross section flexible, with ferrule without plastic sleeve min.
Conductor cross section flexible, with ferrule with plastic sleeve min.
Conductor cross section flexible, with ferrule with plastic sleeve max.
2 conductors with same cross section, solid min.
2 conductors with same cross section, solid max.
2 conductors with same cross section, stranded min.
2 conductors with same cross section, stranded max.
2 conductors with same cross section, stranded, TWIN ferrules with
plastic sleeve, min.
2 conductors with same cross section, stranded, TWIN ferrules with
plastic sleeve, max.
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, min.
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, max.
Stripping length
Internal cylindrical gage
Screw thread
Tightening torque, min
Tightening torque max
0.14 mm²
0.14 mm²
4 mm²
0.14 mm²
1.5 mm²
0.14 mm²
1.5 mm²
0.5 mm²
1 mm²
0.14 mm²
1.5 mm²
9 mm
A4
M3
0.6 Nm
0.8 Nm
Conductor cross section flexible, with ferrule without plastic sleeve max. 4 mm²
Standards and Regulations
Connection in acc. with standard
Flammability rating according to UL 94
CUL
IEC 61984
V0
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
11/15/2016 Page 3 / 5
https://www.phoenixcontact.com/hq/products/3045907
Plug - UPBV 4/11 - 3045907
Circuit diagram
Current carrying capacity [A]
35
30
25
20
15
10
5
0
0
1
= 2-pos.
2
= 5-pos.
3
= 10-pos.
4
= 15-pos.
20
40
60
80
100
120
Diagram
1
3
4
2
Ambient temperature [°C]
The figure shows the derating curve of the UT 4/1P... terminal block in connection with the UPVB 4 plug
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / CSA / cULus Recognized
Ex Approvals
Approval details
UL Recognized
mm²/AWG/kcmil
Nominal current IN
Nominal voltage UN
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B
26-10
30 A
600 V
C
26-10
30 A
600 V
cUL Recognized
mm²/AWG/kcmil
Nominal current IN
Nominal voltage UN
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B
26-10
30 A
600 V
C
26-10
30 A
600 V
EAC 7500651.22.01.00246
11/15/2016 Page 4 / 5
https://www.phoenixcontact.com/hq/products/3045907
Plug - UPBV 4/11 - 3045907
Approvals
CSA
http://www.csagroup.org/services/testing-and-certification/certified-product-listing/ 13631
B
26-10
30 A
600 V
C
26-10
30 A
600 V
mm²/AWG/kcmil
Nominal current IN
Nominal voltage UN
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com