50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 600 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 100 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Ics 35 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 65 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 70 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Category A
1
[Ics] rated service breaking capacity
Suitability for isolation
Utilisation category
May 24, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Trip unit name
Trip unit technology
Trip unit protection functions
Trip unit rating
Protection type
Micrologic 2.2
Electronic
LSoI
100 A ( 40 °C )
Overload protection (long time) L
Short time short-circuit protection with fixed delay So
Instantaneous short-circuit protection I
3 conforming to IEC 60664-1
Pollution degree
Complementary
Control type
Mounting mode
Mounting support
Upside connection
Downside connection
Auxiliary contact composition
Mechanical durability
Electrical durability
Toggle
Fixed
Backplate
Front
Front
Without
40000 cycles
10000 cycles 440 V In/2 conforming to IEC 60947-2
15000 cycles 690 V In/2 conforming to IEC 60947-2
20000 cycles 440 V In conforming to IEC 60947-2
7500 cycles 690 V In conforming to IEC 60947-2
35 mm
LED 90 % Ir
LED ready
LED 105 % Ir
Adjustable 9 settings
0.9...1 x Io
Fixed
11 s 7.2 x Ir
16 s 6 x Ir
400 s 1.5 x Ir
20 minutes before and after tripping
Adjustable 9 settings
1.5...10 x Ir
Fixed
Fixed
1500 A
161 mm
105 mm
86 mm
2.2 kg
Connection pitch
Local signalling
Long time pick-up adjustment type Ir
Long time pick-up adjustment range
Long time delay adjustment type
[Tr] long-time delay adjustment range
Thermal memory
Short-time pick-up adjustment type Isd
[Isd] short-time pick-up adjustment
range
Short-time delay adjustment type
Instantaneous pick-up adjustment type
Ii
Instantaneous pick-up adjustment
range
Height
Width
Depth
Product weight
Environment
Overvoltage category
Electrical shock protection class
Standards
Product certifications
Class II
Class II
EN/IEC 60947
UL 508
Marine
EAC
CCC
IP40 conforming to IEC 60529
IK07 conforming to IEC 62262
-35...70 °C
-55...85 °C
IP degree of protection
IK degree of protection
Ambient air temperature for operation
Ambient air temperature for storage
2
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
REACh
Product environmental profile
Product end of life instructions
Green Premium product
Compliant - since 0819 - Schneider Electric declaration of conformity