EMC filters
3-line filters
for converters and power electronics
Series/Type:
Date:
B84143B/K*S080/S081
May 2014
© EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
3-line filters
for converters and power electronics
B84143B/K*S080/S081
Power line filters for 3-phase systems
Rated voltage V
R
: 520/300 V AC and 760/440 V AC
Rated current I
R
: 180 A to 1600 A
Construction
3-line filters
Metal case
Versions
B84143B*S080 type for standard applications
B84143B*S081 type for applications with higher
voltages
B84143K*S081 type without Y capacitors, very low
leakage current
Features
Optimized leakage current
Easy to install
Very compact design
Optimized for operation under full load
Low weight
Design complies with IEC 60939
UL and cUL approval
Typical applications
Frequency converters for motor drives
Photovoltaics
Wind farms
Power supplies
Terminals
Busbars
Marking
Marking on component:
Manufacturer's logo, ordering code, rated voltage, rated
current, rated temperature, climatic category, date code,
approvals
Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code
Accessories
For busbar filter series B84143B/K*S080/S081
protective covers can be supplied as accessories.
See chapter "Accessories" B84143Q*S080.
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 2 of 16
3-line filters
for converters and power electronics
B84143B/K*S080/S081
Typical circuit diagrams
B84143B*S08*
B84143K*S081
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 3 of 16
3-line filters
for converters and power electronics
B84143B/K*S080/S081
Technical data and measuring conditions
Rated voltage V
R
Rated voltage for IT mains supply
Type S080:
520/300 V AC (50/60 Hz)
Type S081:
760/440 V AC (50/60 Hz)
Type S081:
560/320 V AC (50/60 Hz)
See also chapter "General technical information",
section 7.
Referred to 40
°C
rated temperature (250 A ... 1600 A)
Referred to 60
°C
rated temperature (180 A)
According IEC 60439-1:2011, chapter 3.8.10.2;
limited by I
2
t characteristics of fuse
Type S080:
2240 V DC, 2 s (line/line)
2720 V DC, 2 s (lines/case)
Type S081:
3270 V DC, 2 s (line/line)
2890 V DC, 2 s (lines/case)
1.5 I
R
for 3 min per hour or
2.5 I
R
for 30 s per hour
At V
R
and 50 Hz
25/100/21 ( 25
°C/+100 °C/21
days damp heat test)
UL 1283; CSA C22.2 No.8
(Type *S080: 500/290 V; Type *S081: 600/350 V)
Rated current I
R
Rated peak withstand current I
pk
Test voltage V
test
Overload capability (thermal)
Leakage current l
LK
Climatic category (IEC 60068-1)
Approvals
Characteristics and ordering codes
I
R
A
I
pk
kA
I
LK
mA
14
14
14
14
14
14
14
14
R
typ
mΩ
Approx. weight Ordering code
kg
B84143B0180S080
B84143B0250S080
B84143B0320S080
B84143B0400S080
B84143B0600S080
B84143B1000S080
B84143B1250S080
B84143B1600S080
Approvals
V
R
= 520/300 V AC
180
25
250
25
320
50
400
50
600
50
1000
75
1250
75
1600
75
0.110 5.0
0.110 5.0
0.051 7.2
0.048 7.5
0.043 7.8
0.029 18.5
0.022 24.5
0.022 24.5
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
= Approval granted:
Type *S080 for 500/290 V
Type *S081 for 600/350 V
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 4 of 16
3-line filters
for converters and power electronics
B84143B/K*S080/S081
I
R
A
I
pk
kA
I
LK
mA
20
20
20
20
20
20
20
20
R
typ
mΩ
0.110
0.110
0.110
0.110
0.051
0.051
0.048
0.048
0.043
0.043
0.029
0.029
0.022
0.022
0.022
0.022
Approx. weight Ordering code
kg
5.0
5.0
5.0
5.0
7.2
7.2
7.5
7.5
7.8
7.8
18.5
18.5
24.5
24.5
24.5
24.5
B84143B0180S081
B84143K0180S081
B84143B0250S081
B84143K0250S081
B84143B0320S081
B84143K0320S081
B84143B0400S081
B84143K0400S081
B84143B0600S081
B84143K0600S081
B84143B1000S081
B84143K1000S081
B84143B1250S081
B84143K1250S081
B84143B1600S081
B84143K1600S081
Approvals
V
R
= 760/440 V AC
180
25
180
25
250
25
250
25
320
50
320
50
400
50
400
50
600
50
600
50
1000
75
1000
75
1250
75
1250
75
1600
75
1600
75
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
= Approval granted:
Type *S080 for 500/290 V
Type *S081 for 600/350 V
Please read
Cautions and warnings
and
Important notes
at the end of this document.
Page 5 of 16