SmartPro 120V 1.5kVA 900W Line-Interactive
Sine Wave UPS, Tower, Network Card Options,
USB, DB9, 8 Outlets
MODEL NUMBER:
SMART1500SLT
Highlights
q
Corrects under- and
overvoltages from 95V to 145V
q
8 NEMA 5-15R outlets
Front-panel LEDs indicate load,
power and battery statuses
q
q
Monitoring of power conditions
via PowerAlert®
q
20 min. runtime at half load; 8
min. at full load
Package Includes
q
SMART1500SLT SmartPro
120V 1.5kVA 900W Line-
Interactive Sine Wave UPS
q
USB cable
DB9 cable
Owner’s manual
q
Protects connected mission-critical equipment against damage, downtime and data loss due to blackouts,
brownouts, power surges and line noise. Ideal solution for VoIP systems, point-of-sale applications and
network closets.
q
Description
The SMART1500SLT SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS provides battery
backup and AC power protection against blackouts, brownouts, power surges and line noise that can
damage electronics or destroy data. Ideal for backing up VoIP systems, point-of-sale applications and
network closets, the SMART1500SLT switches to battery mode in milliseconds to keep your connected
equipment running long enough to save files and shut down safely with no data loss.
Featuring eight NEMA 5-15R outlets and a six-foot power cord with NEMA 5-15P input, the
SMART1500SLT has an internal battery that provides 20 minutes of support at half load and eight minutes
at full load. Front-panel LEDs indicate line power, battery power, overload, voltage regulation and battery
status. An alarm sounds to indicate power failure and overload conditions.
Automatic voltage regulation (AVR) maintains selectable 100V, 110V or 120V nominal output over an
input range of 95V to 145V without using battery power. EMI/RFI noise filtering improves your equipment’s
performance and prevents damage. A 690-joule surge suppression rating protects your equipment from
harmful power surges. With Tripp Lite’s PowerAlert software (available via free download),
SMART1500SLT enables safe unattended system shutdown and file saves in case of a prolonged power
failure.
Features
Protects Mission-Critical Equipment
q
Provides fully regulated AC output for VoIP systems, point-of-sale applications and network closets
1/6
q
Audible alarm signals loss of utility power or overload
8 NEMA 5-15R outlets
6 ft. power cord with NEMA 5-15P input
690-joule surge suppression rating
q
q
q
Reliable Battery Backup
q
Supports half load up to 20 min. and full load up to 8 min.
Internal batteries designed for hot-swap field replacement
95% line-power efficiency rating saves money in energy costs
Cold-start capability enables turn-on in battery mode during blackouts
q
q
q
Automatic Voltage Regulation (AVR)
q
Maintains selected 100V, 110V or 120V nominal output over input range of 95V–145V without using
battery power
EMI/RFI Line Noise Filtering
q
Removes electromagnetic and radio frequency interference that can disrupt or damage equipment’s
performance
LED Indicators
q
Front-panel LEDs signal indicate line power, battery power, overload, voltage regulation and battery
status
Network Management Cards
q
Compatible with Tripp Lite UPS management card options WEBCARDLX, SNMPWEBCARD and
RELAYIOCARD
Communications Ports
q
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from www.tripplite.com/poweralert
RJ45 Telephone/Ethernet Protection Jacks
q
Protect phone/DSL/fax/modem/Ethernet network against power surges
Specifications
OVERVIEW
UPC Code
037332119896
OUTPUT
2/6
Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA)
Output Watt Capacity (Watts)
Nominal Output Voltage(s)
Supported
Nominal Voltage Details
Frequency Compatibility
Frequency Compatibility Details
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles
Output AC Waveform (AC Mode)
Output AC Waveform (Battery
Mode)
Individually Controllable Load Banks
1500
1.5
900
100V; 110V; 120V
120V default (voltage selection via back panel switches)
50 / 60 Hz
Automatic frequency selection
-13%, + 15%
+/- 5%
(8) 5-15R
Sine wave
Pure Sine wave
No
INPUT
Rated input current (Maximum Load)
Nominal Input Voltage(s) Supported
UPS Input Connection Type
UPS Input Cord Length (ft.)
UPS Input Cord Length (m)
Recommended Electrical Service
Input Phase
10.1A (100V), 9.3A (110V), 8.6A (120V)
100V AC; 110V AC; 120V AC
5-15P
6
1.8
15A 120V
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
Expandable Runtime
8 min. (900w)
20 min. (450w)
36
Less than 8 hours from 10% to 90% (typical, full load discharge)
<a class="productLink" href="//www.tripplite.com/UPS-Replacement-36VDC-Battery-Cartridge-for-select-
Tripp-Lite-SLT-UPS~RBC36-SLT">RBC36-SLT</a>
Battery access door
Hot-swappable, user replaceable batteries
No
3/6
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 95 to 145 (120v),
87 to 133 (110v), 83 to 121 (100v)
Voltage reduction of 12% applies when input is 127 to 145 (120v), 116 to 133 (110v), 111 to 121 (100v)
Voltage boost of 14% applies when input is 95 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v)
USER INTERFACE, ALERTS & CONTROLS
Switches
Alarm Cancel Operation
Audible Alarm
LED Indicators
Site Wiring Fault Indication
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support
nominal voltage selection
Power-fail alarm can be silenced using alarm-cancel switch
Audible alarm indicates power failure and overload conditions
Status LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter
for load and battery charge level
Rear panel site wiring fault LED
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
UPS AC Suppression Response
Time
UPS Dataline Suppression
EMI / RFI AC Noise Suppression
690
Instantaneous
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
Yes
PHYSICAL
Primary Form Factor
UPS Power Module Dimensions
(hwd, in.)
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Weight (lbs.)
UPS Power Module Weight (kg)
Shipping Dimensions (hwd / in.)
Shipping Dimensions (hwd / cm)
Shipping Weight (lbs.)
Shipping Weight (kg)
Cooling Method
UPS Housing Material
Primary UPS Height (mm)
Primary UPS Width (mm)
Primary UPS Depth (mm)
Tower
10.2 x 6.8 x 13.2
25.91 x 17.27 x 33.53
45
20.41
13.90 x 9.70 x 17.60
35.31 x 24.64 x 44.70
49.50
22.45
Fan
Steel
259
173
335
4/6
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
Battery Mode BTU / Hr. (Full Load)
AC Mode Efficiency Rating (100%
Load)
Audible Noise
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
148
500
95%
Audible Noise < 50 dBA at Front Side 1 Meter
COMMUNICATIONS
Communications Interface
Network Management Cards
Network Monitoring Port Description
PowerAlert Software
Communications Cable
WatchDog Compatibility
USB; DB9 Serial; Slot for SNMP/Web interface
SNMPWEBCARD; WEBCARDLX; <a class="productLink" href="//www.tripplite.com/Programmable-Relay-I-O-
Card~RELAYIOCARD">RELAYIOCARD</a>
Supports detailed monitoring of UPS and site power conditions
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at
http://www.tripplite.com/poweralert
USB and DB9 cabling included
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
4-6 milliseconds
95V (120V), 87V (110V), 83V (100V)
145V (120V), 133V (110V), 121V (100V)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Hot swappable batteries
Greater than 95% efficiency - GREEN UPS
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
WARRANTY
Product Warranty Period
(Worldwide)
2-year warranty, 3 year with registration. Note: <a class="insuranceLink"
href="//www.tripplite.com/support/product-warranty-registration">Registration is required</a> for 3-year
warranty.
5/6