https://www.phoenixcontact.com/us/products/2814472
Signal conditioner - MCR-C-U-I- 0-DC - 2814472
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way isolating amplifier, for electrical isolation of analog signals, input signal: 0 V ... 10 V, output signal: 0
mA ... 20 mA
The illustration shows version MCR-
C-I-I-00-DC
Product Features
■
■
■
Processing of standard signals
3-way isolation
Fixed setting of input and output signals
Key Commercial Data
Packing unit
GTIN
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
88.79 g
85437090
Germany
1 pc
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
12.5 mm
99 mm
114.5 mm
04/21/2016 Page 1 / 4
https://www.phoenixcontact.com/us/products/2814472
Signal conditioner - MCR-C-U-I- 0-DC - 2814472
Technical data
Ambient conditions
Ambient temperature (operation)
-25 °C ... 60 °C
Input data
Description of the input
Configurable/programmable
Voltage input signal
Max. input voltage
Input resistance of voltage input
Voltage input
no
0 V ... 10 V
30 V
200 kΩ
Output data
Output name
Configurable/programmable
Current output signal
Max. output current
Load/output load current output
Linear transmission range (in reference to the output range end value)
Current output
no
0 mA ... 20 mA
30 mA
≤ 500 Ω
-5 % ... 105 %
Power supply
Supply voltage range
Typical current consumption
20 V DC ... 30 V DC
< 15 mA (without load)
Connection data
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Stripping length
Screw thread
Pluggable screw connection
0.2 mm²
2.5 mm²
24
14
0.2 mm²
2.5 mm²
8 mm
M3
General
No. of channels
Maximum transmission error
Transmission error, typical
Max. scale factor error
Maximum temperature coefficient
Limit frequency (3 dB)
Step response (10-90%)
1
≤ 0.2 % (of final value)
< 0.1 %
< 0.2 %
< 0.015 %/K
30 Hz
11 ms
04/21/2016 Page 2 / 4
https://www.phoenixcontact.com/us/products/2814472
Signal conditioner - MCR-C-U-I- 0-DC - 2814472
Technical data
General
Protective circuit
Test voltage, input/output/supply
Color
Housing material
Mounting position
Conformance
Transient protection
1.5 kV (50 Hz, 1 min.)
green
Polyamide PA non-reinforced
any
CE-compliant
Standards and Regulations
Conformance
CE-compliant
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
27210120
27210120
27210120
27210120
27210120
27210120
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001485
EC001485
EC001485
EC001485
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211506
39121008
39121008
39121008
39121008
Accessories
Accessories
Bridge
04/21/2016 Page 3 / 4
https://www.phoenixcontact.com/us/products/2814472
Signal conditioner - MCR-C-U-I- 0-DC - 2814472
Accessories
Wire bridge - DB 50- 90 GY - 2820929
Wire bridge, Color: gray
Wire bridge - DB 50- 90 BK - 2820916
Wire bridge, Color: black
Wire bridge - DB 50- 90 BU - 2821180
Wire bridge, Color: blue
Drawings
Dimensional drawing
99
12,5
IN
IN I/U 1
GND 1 2
U,
Circuit diagram
OUT
5 OUT I/U
6 GND 2
U
114,5
7 +20...30V
8 GND 3
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
04/21/2016 Page 4 / 4