Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for
critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS)
with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels
while maintaining a full battery charge in case of power failure. Tripp Lite's unique configuration excels in
exceptionally poor-power environments with two separate levels of voltage boost to correct both slight
undervoltages and severe brownout conditions. Interactive LCD interface reports UPS operating mode, detailed
UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover
from line to battery power occurs within milliseconds to maintain operation of connected equipment without
interruption or reboot. 98% line-mode efficiency offers reduced heat emissions and operating costs. Network
management interfaces support communications via USB, RS-232 and installed Network Management Card
option. HID-compliant USB port enables integration with built-in power management and auto shutdown features
of Windows and Mac OS X. Network communications ports enable detailed monitoring of equipment load levels,
NEMA 5-15/20R & 1 L5-30R
outlets
This product is ENERGY STAR
qualified for its ability to save
customers money while
helping to protect the
environment
Package Includes
SMART3000RM2U UPS System
USB, Serial & EPO cabling
4-post rackmount installation kit
Instruction manual
self-test data and utility power conditions. PowerAlert UPS monitoring software is available via free download. Switched output load banks enable scheduled
and real-time remote reboot and load shedding of select outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in
rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test.
Field-replaceable, hot-swappable battery modules.
Features
Tripp Lite SMART3000RM2U line interactive 2U rack/tower UPS with 3000VA / 3kVA capacity (1600W maximum load with external battery packs)
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages from 83 to 145V
NEMA L5-30P input plug; 8 NEMA 5-15/20R and 1 L5-30R output receptacles, Two independently switchable output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges, brownouts and overvoltages
High 98% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
Internal batteries offer 10 minutes at 50% load (1125W) and 3.5 minutes at 100% load (2250W)
1/6
Extended runtime is available with optional
BP48V24-2U
(limit 1),
BP48V60RT-3U
(multi-pack compatible) and
BP48V27-2US
(multi-pack compatible)
external battery packs (max output de-rates to 1600 watts with external batteries)
External battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Intelligent battery management system extends battery life
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no disruption to connected equipment
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar battery charge graphic, plus 7 selectable screens
of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional
2POSTRMKITWM
enables 2 post rackmount/wallmount installation; Optional
2-9USTAND
enables tower placement
Built-in USB, RS-232 and slot for Network Management Card options; Compatible with Tripp Lite UPS management card options
TLNETCARD,
WEBCARDLX, SNMPWEBCARD
and
RELAYIOCARD
HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from
www.tripplite.com/poweralert
Built-in Emergency Power Off (EPO) interface with cable
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA)
Output Watt Capacity (Watts)
Output kW Capacity (kW)
Output Capacity Details
Nominal Output Voltage(s)
Supported
Nominal Voltage Details
Frequency Compatibility
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles
Load Management Receptacles
Output Circuit Breakers
Output AC Waveform (AC Mode)
Output AC Waveform (Battery Mode)
3000
3
2250
2.25
Output is reduced to 1600 watts maximum when used with external battery packs
110V; 115V; 120V
120v nominal output in battery mode
60 Hz
-14%, +6%
+/- 5%
(8) 5-15/20R; (1) L5-30R
Two switchable single-outlet load banks
Two 20A output breakers protect 4 5-15/20R outlets each
Pure Sine wave
Pure Sine wave
INPUT
2/6
Rated input current (Maximum Load)
Nominal Input Voltage(s) Supported
UPS Input Connection Type
UPS Input Cord Length (ft.)
UPS Input Cord Length (m)
Recommended Electrical Service
Input Phase
24A
120V AC
L5-30P
10
3.0
30A 120V
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
Expandable Battery Runtime
External Battery Pack Compatibility
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
Expandable Runtime
3.5 min. (2250w)
10 min. (1125w)
Extended runtime supported via optional external battery packs
BP48V24-2U
(limit 1);
BP48V60RT-3U(multi-pack
compatible);
BP48V27-2US(multi-pack
compatible)
48
Less than 4.5 hours from 10% to 90%
RBC94-2U
Front panel battery access door
Hot-swappable, user replaceable batteries
Yes
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Severe Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Input voltages between 127 and 145 are reduced by 12%
Input voltages between 108 and 96 are boosted by 12%
Input voltages between 83 and 95 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
Switches
Alarm Cancel Operation
Audible Alarm
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating
data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual
for detailed LCD configuration and monitoring options)
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option