3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
FMAD
1-stage filter for 3-phase systems with neutral conductor
Approvals and Compliances
Description
- Terminals for three phases, neutral conductor and ground
Applications
-
-
-
-
Voltage rating 480 VAC for world wide acceptance
Protection against interference voltage from the mains
For standard and industrial applications
Suitable for use in equipment according to IEC/UL 60950
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Microsite
Technical Data
Rated Current
Rated voltage
Approval for
Overload Current
Leakage Current
Dielectric Strength
6 - 550 A
277/480 VAC, 50/60 Hz
6 - 550 A @ 40 (75) °C / 277/480 VAC
1.5 x Ir
industrial < 5 mA (440 V / 50 Hz)
277/480 VAC:
2.25 kVDC between L-L
1.7 kVDC between L-N
3 kVDC between L-PE
2.7 kVDC between N-PE
Test voltage (2 sec)
1-stage
0.95 - 24.5 kg
Metal
UL 94V-0
Mounting
Terminal
Operating Temperature
Climatic Category
Degree of Protection
Protection Class
MTBF
Screw-on mounting on chassis, from
top
Screw clamps
-25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
IP 20 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
> 200'000 h acc. to MIL-HB-217 F
Number of Filter Stages
Weight
Material: Housing
Sealing Compound
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in
Details about
Approvals
Approvals
The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products.
Approval Reference Type: FMAD
Approval Logo
Certificates
UL Approvals
Certification Body
UL
Description
UL File Number: E72928
Product standards
Product standards that are referenced
Organization
Design
Designed according to
Designed according to
Standard
IEC 60939
UL 1283
Description
Passive filters for suppressing electromagnetic interference
Electromagnetic interference filters
EMC Products
1
FMAD
Application standards
Application standards where the product can be used
Organization
Design
Designed for applications acc.
Standard
IEC/UL 60950
Description
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification
Details
CE declaration of conformity
Initiator
SCHURTER AG
Description
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
EU Directive RoHS 2011/65/EU
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
RoHS
China RoHS
REACH
SCHURTER AG
SCHURTER AG
SCHURTER AG
Dimension [mm]
Case 24-4
Case 31-4
max. 137
max. 100
max. 58
(7)
max. 217
max. 181
(7)
max. 61
max. 106
max. 116
(29.5)
100
-1
1)
2)
(30)
M6
5.3
±0.3
51
±0.3
1) Line
2) Load
3) Nut torque 3...4 Nm
6.5
±0.3
M6
115
±0.3
3)
(17)
3)
(17)
Case 32-4
Case 32-8
237 max.
201 max.
(7)
66 max.
237 max.
201 max.
(2)
66 max.
151 max.
121 max.
151 max.
135
1)
2)
(41)
1)
2)
(41)
M6
6.5
±0.3
115
±0.3
3)
(17)
M6
6.5
±0.3
115
±0.3
3)
(17)
2
EMC Products
121 max.
+0
135
-1
+0
-1
max. 86
95
-1
+0
1)
2)
max. 86
+0
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
FMAD
Case 34-4
Case 37-4
250 max.
201 max.
(10)
66 max.
378 max.
301 max.
6.5x15
81 max.
(15)
151 max.
121 max.
1)
2)
(41)
150 max.
110
±0.3
135
-1
+0
1)
3)
325
±1
3)
2)
(42)
M10
4)
6.5
±0.3
M6
115
±0.3
5)
(17)
(58)
Case 53-4
Case 54-4
308 max.
231 max.
(13)
66 max.
387 max.
301 max.
6.5x15
150 max.
110
±0.3
81 max.
(14)
151 max.
121 max.
135
+0
-1
1)
2)
(45)
1)
5)
2)
5)
M10
4)
(45)
M6
6.5
±0.3
115
±0.3
3)
(34)
325
±1
(58)
1) Line
2) Load
3) Tightening torque 3...4 Nm
4) Tightening torque 10...17 Nm
5) Do not unscrew lock-nut
Case 55-4
Case 56-4
591 max.
400 max.
169 max.
615 max.
400 max.
169 max.
232 max.
171 max.
232 max.
1)
4)
(30)
2)
1)
4)
(30)
9
±0.5
280
±0.5
2)
9
±0.5
280
±0.5
M12
3)
(50)
M12
3)
(50)
1) Line
2) Load
3) Nut torque 14...30 Nm
4) Do not unscrew lock-nut
EMC Products
3
171 max.
+0
200
-2
+0
200
-2
FMAD
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
Case KQ
max. 340
303
±1
6.4
±0.3
(4x)
max. 258
33
max. 150
92
1)
25
(4x)
max. 25 Nm
2)
278
–2
max. 300
+0
130
±0.3
79
8
(4x)
1) Line
2) Load
3) Torsional stress at flat copper max. 25 Nm
Technical data to the filter components
Rated Current
@ Ta 40°C (75°C) [A]
6 (4.8)
8 (5)
16 (9.5)
25 (13)
36 (19)
50 (32)
64 (34)
80 (43)
110 (66)
180 (95)
250 (120)
550 (320)
L [mH]
9
8
5
2.6
1.8
0.8
0.6
0.9
0.5
0.25
0.2
0.2
C1 [μF]
1.0
1.0
1.0
4.4
4.4
4.4
4.4
6.6
6.6
6.6
11
10
C2 [μF]
-
-
-
1
1
1
1
1
1
1
1
1
C3 [nF]
100
100
100
10
10
10
10
47
47
47
100
100
C4 [nF]
10
10
10
47
47
100
100
100
100
100
100
100
C5 [μF]
2.2
2.2
2.2
4.4
4.4
4.4
4.4
6.6
6.6
6.6
11
10
C6 [μF]
-
-
-
1
1
1
1
1
1
1
1
1
R1 [MΩ] R2 [MΩ] R3 [MΩ] R4 [MΩ]
-
-
-
-
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
-
-
-
1
1
1
1
1
1
1
0.5
0.5
1
1
1
1
1
1
1
1
1
1
0.5
0.5
2.2
2.2
2.2
2.2
-
-
-
-
-
2.2
2.2
2.2
Diagrams
1)
1) Line
4
EMC Products
max. 158
92
.5
10 )
(4x
.3
±0
3-Phase AC Filters / DC Filters
https://www.schurter.com /PG80
FMAD
Derating Curves
Permissible Working Current as a Function of Ambient Temperature
Admissible operating current in % of In
100
80
60
UL Listed
40
20
0
0
20
Ambient air temperature T
a
°C
40
60
75
100
Attenuation Loss
Industrial version
- - - - 50Ω differential mode _____ 50Ω common mode
6A (FMAD-0924-0610)
8A (FMAD-0931-0810)
16A (FMAD-0931-1610)
16A (FMAD-0932-1610)
25A (FMAD-0932-2510)
36A (FMAD-0934-3610)
50A (FMAD-0934-5010)
64A (FMAD-0953-6410)
80A (FMAD-0937-8010)
110A (FMAD-0954-H110)
180A (FMAD-0955-H210)
250A FMAD-0956-H310
550A FMAD-09KQ-H650
All Variants
Rated Current
@ Ta 40°C (75°C) [A]
6 (4.8)
8 (5)
16 (9.5)
16 (9.5)
25 (13)
36 (19)
50 (32)
64 (34)
80 (43)
110 (66)
180 (95)
Leakage Current [mA]
@ 440V, 60Hz
1)
1.3
1.3
1.3
1.3
8.4
8.4
9.0
9.0
9.7
9.7
9.7
Tripped Power Dissi-
pation [W]
3.9
9
15.4
15.4
11.5
21
20
27
39
58
51
Contact Resi-
stance [mΩ]
27
35
15
15
4.6
4
2
1.6
1.5
1.2
0.39
Weight
[kg]
0.95 kg
1.9 kg
2.1 kg
3.1 kg
3.35 kg
3.4 kg
3.4 kg
4.3 kg
7.35 kg
7.25 kg
22 kg
Clamps [mm
2
]
4
4
4
4
6
10
10
25
25
50
95
Housings
24-4
31-4
31-4
32-4
32-8
34-4
34-4
53-4
37-4
54-4
55-4
Order Number
FMAD-0924-0610
FMAD-0931-0810
FMAD-0931-1610
FMAD-0932-1610
FMAD-0932-2510
FMAD-0934-3610
FMAD-0934-5010
FMAD-0953-6410
FMAD-0937-8010
FMAD-0954-H110
FMAD-0955-H210
█
█
█
█
█
█
█
█
EMC Products
5