Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5326UL Multi-Conductor - Commercial Applications
For more Information
please call
1-800-Belden1
General Description:
Fire Alarm Cable, Riser-FPLR, 8-18 AWG solid bare copper conductors with Polypropylene insulation,
PVC jacket with ripcord
Usage (Overall)
Suitable Applications:
Fire Protections, Alarm, Signal, Monitor/Detection, Audio Circuits, Control Circuits, Initiating Circuits,
Notification Circuits
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
8
18
Solid
BC - Bare Copper
8
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
Polypropylene
0.007
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.018
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Length (in.) Twists (twist/ft)
3.500
3.430
Overall Cabling Color Code Chart:
Number Color
1
2
3
4
5
6
7
8
Black
Red
Brown
Blue
Orange
Yellow
Purple
Green
0.216 in.
Overall Nominal Diameter:
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +75°C
75°C
53.800 lbs/1000 ft.
156.800 lbs.
2.200 in.
Page 1 of 2
09-11-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5326UL Multi-Conductor - Commercial Applications
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
NEC Articles:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Other Specification:
FPLR
760
Yes
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
California State Fire Marshall
Flame Test
UL Flame Test:
CSA Flame Test:
UL1666 Vertical Riser
FT4
Plenum/Non-Plenum
Plenum (Y/N):
Plenum Number:
No
6326UL
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
30.000
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
6.4
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
3.5 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
5326UL 0021000
Putup
1,000 FT
Ship Weight
51.000 LB
Color
RED
Notes
Item Desc
8 #18 PP FRPVC
Revision Number: 2
© 2017 Belden, Inc
All Rights Reserved.
Revision Date: 04-05-2013
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 2 of 2
09-11-2017