https://www.phoenixcontact.com/us/products/2855347
Bus coupler - IBS IL 24 BK RB LK-2MBD - 2855347
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
INTERBUS bus coupler, with fiber optic connection and fiber optic remote bus branch, 24 V DC, transmission
speed 2 Mbaud, without accessories
The illustration shows the version
IBS IL 24 BK RB-LK
Product Features
Remote bus connections using fiber optic technology
Optical path diagnostics
Packing unit
1 pc
320.5 GRM
85389091
Germany
Key commercial data
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
Technical data
Dimensions
Width
Height
Depth
85 mm
119.8 mm
71.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
-25 °C ... 55 °C
-25 °C ... 85 °C
75 % ... 85 %
75 % ... 85 %
80 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
10/20/2014 Page 1 / 4
https://www.phoenixcontact.com/us/products/2855347
Bus coupler - IBS IL 24 BK RB LK-2MBD - 2855347
Technical data
Ambient conditions
Degree of protection
IP20
Interfaces
Fieldbus system
Designation
Connection method
Transmission speed
Transmission physics
Fieldbus system
Designation
Connection method
Transmission speed
Transmission physics
Designation
Connection method
Lokalbus
Inline local bus
Inline data jumper
2 MBit/s
FO
INTERBUS
INTERBUS
6x F-SMA connector
2 MBit/s
FO
Supply
8-pos. Inline connector
Power supply for module electronics
Connection method
Supply voltage
Supply voltage range
Current consumption
Inline connector
24 V DC (via Inline connector)
19.2 V DC ... 30 V DC (including ripple)
max. 1.3 A (with max. number of connected I/O terminal blocks)
General
Weight
Mounting type
Test section
235 g
DIN rail
7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply/
functional earth ground 500 V AC 50 Hz 1 min
Inline potentials
Communications power U
L
Power supply at U
L
I/O supply voltage U
ANA
Power supply at U
ANA
7.5 V DC ±5 %
max. 2 A DC (observe derating)
24 V DC -15 % / +20 %
max. 0.5 A DC (observe derating)
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
27250203
27250203
27250203
10/20/2014 Page 2 / 4
https://www.phoenixcontact.com/us/products/2855347
Bus coupler - IBS IL 24 BK RB LK-2MBD - 2855347
Classifications
eCl@ss
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
27242608
27242608
27242608
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001434
EC001604
EC001604
EC001604
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
43172015
43201404
43172015
43201404
43201404
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
10/20/2014 Page 3 / 4
https://www.phoenixcontact.com/us/products/2855347
Bus coupler - IBS IL 24 BK RB LK-2MBD - 2855347
Approvals
cUL Listed
cULus Listed
Drawings
Dimensioned drawing
119,8
Phoenix Contact 2014 © - all rights reserved
http://www.phoenixcontact.com
71,5