https://www.phoenixcontact.com/us/products/2316064
Device coupler - FB-ISO - 2316064
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Device coupler for Foundation Fieldbus and PROFIBUS PA. Provides intrinsically safe FISCO connection to a
single end device.
Product Features
■
Field barrier
Key Commercial Data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
134.2 g
85389099
United States
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
17.5 mm
89.7 mm
70.4 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Degree of protection
-40 °C ... 60 °C
-40 °C ... 85 °C
10 % ... 95 % (non-condensing)
IP20
04/25/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2316064
Device coupler - FB-ISO - 2316064
Technical data
General
Electrical isolation
Standards/regulations
500 V AC (between input and output, routine test)
IEC 60529, IEC 61158-2
NE21
EN 61326, EN 60068-2-27, EN 60068-2-6
VI-7-2 category C, EMC1
Mounting position
Net weight
Color
Conformance
On horizontal DIN rail NS 35 in acc. with EN 60715
129.7 g
green
CE-compliant, additionally EN 61326
Power supply
Supply voltage range
Typical current consumption
17 V DC ... 32 V DC (input on trunk line side)
10 mA
Serial interface
Interface 1
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Output nominal voltage
Output current
Maximum output current
Foundation Fieldbus and PROFIBUS PA Segment
Pluggable COMBICON screw connection for each spur
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
≥ 10 V (each spur)
15 mA (each spur, adjustable via selector switch)
22 mA (each spur, adjustable via selector switch)
Safety data
Input voltage U
i
Group
Max. external capacity C
o
Group
Max. external capacity C
o
Group
Max. external inductivity L
o
Group
Max. external inductivity L
o
ATEX
32 V
IIC
0.36 µF
IIB
2.11 µF
IIB
660 µH
IIC
220 µH
II 3(3) G Ex nA [nL Gc] IIC T4 Gc, FNICO power supply (spur)
II 3(1) GD Ex nA [ia Ga Da] IIC T4 Gc, FISCO power supply (spur)
04/25/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2316064
Device coupler - FB-ISO - 2316064
Technical data
Safety data
IECEx
Ex nA [nL Gc] IIC T4 Gc, FNICO power supply (spur)
Ex nA [ia Ga Da] IIC T4 Gc, FISCO power supply (spur)
Standards and Regulations
Shock
Standards/regulations
15g, 11 ms
IEC 60529, IEC 61158-2
NE21
EN 61326, EN 60068-2-27, EN 60068-2-6
VI-7-2 category C, EMC1
Electrical isolation
Vibration (operation)
Conformance
Group
500 V AC (between input and output, routine test)
1g, 10 Hz - 150 Hz
CE-compliant, additionally EN 61326
IIC
IIB
IIB
IIC
ATEX
IECEx
II 3(3) G Ex nA [nL Gc] IIC T4 Gc, FNICO power supply (spur)
II 3(1) GD Ex nA [ia Ga Da] IIC T4 Gc, FISCO power supply (spur)
Ex nA [nL Gc] IIC T4 Gc, FNICO power supply (spur)
Ex nA [ia Ga Da] IIC T4 Gc, FISCO power supply (spur)
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27250203
27250203
27250203
27259205
27259090
27259090
27242610
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001423
EC001600
EC001600
EC001600
04/25/2016 Page 3 / 5
https://www.phoenixcontact.com/us/products/2316064
Device coupler - FB-ISO - 2316064
Classifications
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211506
39121008
39121008
39121008
43201553
Accessories
Accessories
Base element
Surge protection base element - PT 1X2+F-BE - 2856126
Base element for protective plug PT with protective circuit for a 2-core floating signal circuit. Integrated gas arrester as
coarse protection between GND and PE. Mounting on NS 35/7.5 und NS 35/15, housing width: 17.5 mm.
Power supply
Power supply - FB-PS-25/0.36A - 2316035
Isolated Foundation Fieldbus Power Supply with integrated Terminator. Multiple single channel modules can be installed
using Phoenix Contacts TBUS connector system reducing wiring and installation costs.
Surge protection for measurement and control technology
Surge protection plug - PT 1X2-24AC-ST - 2856058
PT protective connector with protective circuit for a 2-wire floating signal circuit. HART-compatible.
04/25/2016 Page 4 / 5
https://www.phoenixcontact.com/us/products/2316064
Device coupler - FB-ISO - 2316064
Accessories
Control cabinet - FB- 8-ENCL - 2316093
Enclosure for Foundation Fieldbus and PROFIBUS PA. 8 ports with glands.
Control cabinet - FB-13-ENCL - 2316103
Enclosure for Foundation Fieldbus and PROFIBUS PA. 11 ports with glands and 2 pluged ports.
Drawings
Dimensional drawing
DC
Circuit diagram
SPUR 1
I
S1+
S1-
S1S
89,7
7 17,5
85
DC
70,4
F+ F-
S
TBUS
Connection diagram: FB-ISO
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
04/25/2016 Page 5 / 5