https://www.phoenixcontact.com/us/products/2688080
I/O module - AXL AO 8 - 2688080
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Axioline analog output module, 8 outputs: 0 - 10 V, ±10 V, 0 - 5 V, ±5 V, 0 - 20 mA, 4 - 20 mA, ±20 mA, 2-wire
connection method (including bus base module and connectors)
Product description
The module is designed for use within an Axioline F station.
It is used to output analog voltage and current signals.
Product Features
8 analog, bipolar output channels for the connection of either voltage or current signals
Connection of actuators in 2-wire technology
Voltage ranges: 0 V ... 10 V, ±10 V, 0 V ... 5 V, ±5 V
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Short-circuit-proof outputs
Device rating plate stored
Diagnostic and status indicators
Key commercial data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
260.0 GRM
85389091
Germany
Technical data
Dimensions
Width
Height
Depth
Note on dimensions
53.6 mm
126.1 mm
54 mm
The depth is valid when a TH 35-7.5 DIN rail is used (according to
EN 60715).
09/03/2014 Page 1 / 6
https://www.phoenixcontact.com/us/products/2688080
I/O module - AXL AO 8 - 2688080
Technical data
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
Permissible humidity (storage/transport)
Air pressure (operation)
Air pressure (storage/transport)
Degree of protection
-25 °C ... 60 °C
-40 °C ... 85 °C
5 % ... 95 % (according to DIN EN 61131-2)
5 % ... 95 % (according to DIN EN 61131-2)
70 kPa ... 106 kPa (up to 3000 m above sea level)
70 kPa ... 106 kPa (up to 3000 m above sea level)
IP20
Connection data
Designation
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
Axioline F connector
Push-in technology
0.2 mm²
1.5 mm²
0.2 mm²
1.5 mm²
24
16
8 mm
General
Weight
Note on weight specifications
Mounting type
Protection class
Test section
260 g
with connectors and bus base module
DIN rail
III, IEC 61140, EN 61140, VDE 0140-1
5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min
5 V supply (logic)/analog outputs 500 V AC 50 Hz 1 min
5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min
24 V supply (I/O)/analog outputs 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Analog outputs/functional earth ground 500 V AC 50 Hz 1 min
Conformance with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000‑4‑2/IEC 61000‑4‑2 Criterion B; 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN 61000‑4‑3/IEC 61000‑4‑3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN 61000‑4‑4/IEC 61000‑4‑4 Criterion B, 2 kV
Noise immunity test in accordance with EN 61000-6-2 Transient surge
voltage (surge) EN 61000‑4‑5/IEC 61000‑4‑5 Criterion B; supply lines DC:
±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV to shielded I/O cables
09/03/2014 Page 2 / 6
https://www.phoenixcontact.com/us/products/2688080
I/O module - AXL AO 8 - 2688080
Technical data
General
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000‑4‑6/IEC 61000‑4‑6 Criterion A; Test voltage 10 V
Noise emission test according to EN 61000-6-3 Radio interference
properties EN 55022 Class B
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25g, 11 ms period, half-
sine shock pulse
Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g
Interfaces
Designation
Connection method
Transmission speed
Axioline F local bus
Bus base module
100 MBit/s
Axioline potentials
Communications power U
Bus
Current consumption from U
Bus
Supply of analog modules U
A
Current consumption from U
A
5 V DC (via bus base module)
typ. 105 mA
max. 130 mA
24 V DC
typ. 50 mA (induced current consumption; no load, 0 V output)
typ. 110 mA (8 voltage channels, 10 V output)
max. 235 mA (8 current channels, 20 mA output)
Analog outputs
Number of outputs
Connection method
Output name
D/A conversion time
D/A resolution
Type of protection
Protective circuit/component
Data formats
Representation of output values
Process data update
Current output signal
8
Push-in technology
2-wire (shielded, twisted pair)
Analog outputs
5 µs
16 bit
Short-circuit and overload protection
Transient protection
Electronic
Suppressor diode
IB IL, S7-compatible
16 bits (15 bits + sign)
300 µs
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
09/03/2014 Page 3 / 6
https://www.phoenixcontact.com/us/products/2688080
I/O module - AXL AO 8 - 2688080
Technical data
Analog outputs
Load/output load current output
Voltage output signal
to 500 Ω
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output
Precision
Permissible cable length
> 2 kΩ
typ. 0.1 % (of output range final value)
typ. 0.1 % (of output range final value)
max. 250 m
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27240405
27240405
27242201
27242601
27242601
27242601
27242601
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001599
EC001599
EC001596
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
43172015
43201404
39121311
39121311
39121311
Approvals
Approvals
09/03/2014 Page 4 / 6
https://www.phoenixcontact.com/us/products/2688080
I/O module - AXL AO 8 - 2688080
Approvals
Approvals
UL Listed / cUL Listed / BSH / RINA / DNV / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
BSH
RINA
DNV
cULus Listed
Drawings