OmniSmart 120V 330VA 225W UL 60601-1
Medical Grade Line-Interactive UPS, Tower, DB9
Serial
MODEL NUMBER:
OMNISMART350HG
Highlights
q
330VA line interactive tower
UPS
q
Maintains sine-wave 120V
nominal output over an input
range of 83 to 132V
q
Professional features include
serial port, hospital grade plug &
outlets, built-in isolation
transformer and UL60601-1
listing
q
Input: Hospital-grade NEMA 5-
15P (120V 15A) / Output: 4
Hospital-grade NEMA 5-15R
(120V)
q
2 line phone suppression for
TEL/DSL line protection
Description
Tripp Lite's OMNISMART350HG offers medical-grade UPS protection with built-in line interactive voltage
regulation, intelligent monitoring and unattended shutdown capability. Hospital-grade plug & outlets, plus
built-in isolation transformer with Faraday shield offers full isolation and removes common mode noise
equal to 100 microamps. UL 60601-1 listed as medical electrical equipment. 330VA power handling
capacity supports computers, inter-networking equipment and other critical loads during commercial
power failures. Line interactive voltage regulation corrects brownouts as low as 83V back to normal 120V
levels, saving battery reserves for use only during complete power failures. Includes, 2 line phone surge
suppression and built-in DB-9 communications port that works with PowerAlert Software and cabling to
provide automatic unattended shutdown of connected network and PC applications.
Application Usage
This UPS contains a lead acid battery designed to be connected continuously to an AC power source,
except during brief power outages. It is not intended for frequent charge/discharge cycles, such as mobile
cart applications where the UPS is often disconnected from the power source. Using the
OMNISMART350HG in this type of application will void the battery warranty.
q
Leakage current less than 100
microamps
Package Includes
q
OMNI SMART 350HG Hospital
Grade UPS System
q
Serial cable for remote
monitoring
q
Warranty information
Instruction manual
q
Features
q
Ideal UPS protection for applications in medical patient-care areas where UL 60601-1 listed electrical
medical equipment is required
q
Line-interactive voltage regulation corrects brownouts as low as 83V without using battery power
Hospital-grade plug and outlets offer added degree of safety and reliability to input/output connections
Full line isolation prevents shock potential and operational problems in sensitive electronic equipment
Resistant to electrostatic discharge
Supports loads up to 330VA/225 watts
46 minutes half load runtime (with 165VA load), 18 minutes full load runtime (with 330VA load)
4 protected hospital-grade outlets; 6-ft. cord
q
q
q
q
q
q
1/5
q
1-DB9 serial port for network interface
Complete surge protection, line isolation and EMI/RFI noise filtering
2 phone line surge suppression for modems, fax machines and other phone accessories
Complete remote monitoring cabling included, PowerAlert UPS management software available via free
download
q
q
q
q
4 diagnostic LEDs indicate AC present, on battery, voltage correction & battery low/replace
Battery replacement door and back panel grounding lug
q
Specifications
OVERVIEW
UPC Code
037332098542
OUTPUT
Output Volt Amp Capacity (VA)
Output Watt Capacity (Watts)
Nominal Output Voltage(s)
Supported
Frequency Compatibility
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles
Output Receptacle Details
Output AC Waveform (AC Mode)
Output AC Waveform (Battery
Mode)
Individually Controllable Load Banks
330
225
120V
60 Hz
-18%, +8%
+/- 5%
(4) 5-15R
Hospital grade output receptacles
Sine wave
PWM sine wave
No
INPUT
Rated input current (Maximum Load)
Nominal Input Voltage(s) Supported
UPS Input Connection Type
Input Circuit Breakers
UPS Input Cord Length (ft.)
UPS Input Cord Length (m)
Recommended Electrical Service
2.3A
120V AC
5-15P-HG
3.5A
6
1.8
15A 120V
2/5
Input Phase
Single-Phase
BATTERY
Full Load Runtime (min.)
Half Load Runtime (min.)
DC System Voltage (VDC)
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery Access
Battery Replacement Description
Expandable Runtime
18 min. (225w)
46 min. (115w)
12
Less than 4.5 hours from 10% to 90%
<a class="productLink" href="//www.tripplite.com/UPS-Replacement-Battery-Cartridge-select-Tripp-Lite-Best-
Liebert-Minuteman-other-UPS~RBC52">RBC52</a> (quantity 2)
Battery access door
Hot-swappable, user replaceable batteries
No
VOLTAGE REGULATION
Voltage Regulation Description
Undervoltage Correction
Automatic voltage regulation (AVR) maintains line power operation with input voltage as low as 89
Input voltages between 89 and 107 are boosted by 14%
USER INTERFACE, ALERTS & CONTROLS
Switches
Alarm Cancel Operation
Audible Alarm
LED Indicators
2 Switches control off/on power status and alarm-cancel/self-test operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-
battery status
Audible alarm indicates power-failure and low-battery conditions
4 LEDs indicate line power, battery power, overload and battery low/replace status
SURGE / NOISE SUPPRESSION
UPS AC Suppression Response
Time
UPS Dataline Suppression
EMI / RFI AC Noise Suppression
Instantaneous
2 line TEL/DSL
Yes
ISOLATION
Output Isolation Transformer
Hospital grade load isolation transformer
PHYSICAL
Installation Form Factors Supported
with Included Accessories
Installation Form Factors Supported
with Optional Accessories
Primary Form Factor
Tower
Wallmount (UPSWM - tower mounting kit)
Tower
3/5
UPS Power Module Dimensions
(hwd, in.)
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Weight (lbs.)
UPS Power Module Weight (kg)
Shipping Dimensions (hwd / in.)
Shipping Dimensions (hwd / cm)
Shipping Weight (lbs.)
Shipping Weight (kg)
UPS Housing Material
Primary UPS Height (mm)
Primary UPS Width (mm)
Primary UPS Depth (mm)
10.8 x 5.2 x 7.2
27.43 x 13.21 x 18.29
25
11.34
14.000 x 8.000 x 10.100
35.56 x 20.32 x 25.65
27.8000
12.61
PVC
274
132
183
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
Battery Mode BTU / Hr. (Full Load)
AC Mode Efficiency Rating (100%
Load)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
48.8
215.8
94%
COMMUNICATIONS
Communications Interface
PowerAlert Software
Communications Cable
DB9 Serial
For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at
http://www.tripplite.com/poweralert
DB9 serial cable included
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
2-4 milliseconds
89
139
SPECIAL FEATURES
Grounding Lug
Grounding lug
4/5
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Cold-start operation supported
Hot swappable batteries
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category B (EMI); Tested to UL60601-1
(medical grade)
WARRANTY
Product Warranty Period
(Worldwide)
2-year limited warranty
© 2018 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
https://www.tripplite.com/products/product-certification-agencies
5/5