LSA-PLUS coarse protection magazine for 10 double conductors, equipped with 10 three-electrode gas-filled
surge arresters.
Why buy this product
For use in CT-TERMIBLOCK or in LSA-PLUS and LSA-PROFIL disconnect and terminal strips
Fitted with up to 10 three-electrode arresters filled with inert gas
When the gas-filled arrester is triggered, the potentials of the three connections a-b-... are equalized
Coarse protection both in the normal mode voltage branch and the common mode voltage branch for 10 double wires
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4046356181822
85363010
Made to Order (non-returnable)
10 STK
Technical data
Dimensions
Height
Width
Depth
22.5 mm
113.3 mm
41.35 mm
Ambient conditions
Ambient temperature (operation)
Degree of protection
-25 °C ... 75 °C
IP20
General
Housing material
Flammability rating according to UL 94
PBT
V-0
11/15/2016 Page 1 / 3
https://www.phoenixcontact.com/hq/products/2920829
Magazine - CT 10-2/2-GS/3E-110AC - 2920829
Technical data
General
Color
Standards for cearances and creepage distances
Mounting type
Design
Number of positions
Direction of action
gray
VDE 0110-1
IEC 60664-1
On CT-TERMIBLOCK and LSA-PLUS disconnect strip
LSA-PLUS module
20
Line-Line & Line-Earth Ground
Protective circuit
IEC test classification
C2
C3
D1
Nominal voltage U
N
Maximum continuous voltage U
C
Rated current
Operating effective current I
C
at U
C
Residual current I
PE
Nominal discharge current I
n
(8/20) µs (Core-Earth)
Pulse discharge current I
imp
(10/350) µs (core-ground)
Nominal pulse current Ian (10/1000) µs (Core-Earth)
Output voltage limitation at 1 kV/µs (Core-Earth) spike
Response time tA (Core-Earth)
Capacity (Core-Earth)
Resistance in series
Impulse durability (conductor-ground)
110 V AC
60 V DC
130 V AC
1.5 A AC (per path)
150 mA DC (per path)
≤ 1 µA (per path)
≤ 20 µA
5 kA
2.5 kA
100 A
≤ 500 V
≤ 100 ns
typ. 5 pF
≤ 10 mΩ
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 2.5 kA
Alternating current carrying capacity (conductor-ground)
10 A - 1 s
Connection data
Connection method
Connection type IN
Connection type OUT
Connection method
can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS
disconnect and switching strips
COMTRAB plug-in system
COMTRAB plug-in system
LSA-PLUS
Connection, equipotential bonding
Connection method
Spring contact
Standards and Regulations
Standards/specifications
IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
11/15/2016 Page 2 / 3
https://www.phoenixcontact.com/hq/products/2920829
Magazine - CT 10-2/2-GS/3E-110AC - 2920829
Technical data
Standards and Regulations
EN 61643-21 2001 + A1:2009 + A2:2013
Drawings
Dimensional drawing
22
41
b1
b2
b3
b4
b5
b8/b10
Circuit diagram
113
a1
a2
a3
a4
a5
a8/a10
Approvals
Approvals
Approvals
EAC
Ex Approvals
Approval details
EAC 7500651.22.01.00243
Phoenix Contact 2016 © - all rights reserved