https://www.phoenixcontact.com/hq/products/2908667
Type 1/2 surge protection plug - VAL-MS-T1/T2 1000DC-PV-
ST/36 - 2908667
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for PV arrester combinations from the VAL-MS-T1/T2 1000DC-PV-... product range
Product Description
Large-scale packaging
Key Commercial Data
Packing unit
Minimum order quantity
GTIN
GTIN
Custom tariff number
Note
4055626320991
85363030
Made to Order (non-returnable)
36 STK
36 STK
Technical data
Dimensions
Height
Width
Depth
Horizontal pitch
52.4 mm
17.5 mm
55.3 mm
1 Div.
Ambient conditions
Degree of protection
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
Permissible humidity (operation)
Shock (operation)
IP20
-40 °C ... 80 °C
-40 °C ... 80 °C
≤ 2000 m (amsl (above mean sea level))
5 % ... 95 %
60g (Half sine/11 ms/3x XYZ)
11/15/2016 Page 1 / 3
https://www.phoenixcontact.com/hq/products/2908667
Type 1/2 surge protection plug - VAL-MS-T1/T2 1000DC-PV-
ST/36 - 2908667
Technical data
Ambient conditions
Vibration (operation)
7.5g (5-500 Hz/2.5 h/XYZ)
General
IEC test classification
SPD failure behavior
SPD design
Installation location
Accessibility
Installation location of the disconnect device
Mounting type
Color
Housing material
Degree of pollution
Flammability rating according to UL 94
Surge protection fault message
PV T1
PV T2
OCM (Open-circuit mode)
Voltage-limiting type
Inside
Accessible
Internal
On base element
jet black RAL 9005
PA 6.6-FR
2
V-0
optical
Protective circuit DC voltage side (DC)
Maximum continuous operating voltage U
CPV
Open circuit voltage U
OCSTC
Short-circuit current rating I
SCPV
Continuous operating current I
CPV
Standby power consumption P
C
Nominal discharge current (8/20) µs
Maximum discharge current I
max
(8/20) µs
Impulse discharge current (10/350)µs, charge
Impulse discharge current (10/350)µs, specific energy
Impulse discharge current (10/350) µs, peak value l
imp
Voltage protection level U
p
Residual voltage U
res
525 V DC
≤ 435 V DC
1000 A
< 20 µA
≤ 25 mVA
15 kA
40 kA
2.5 As
6.25 kJ/Ω
5 kA
≤ 1.8 kV
≤ 1.8 kV (at I
n
)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 1.9 kV (at 20 kA)
≤ 2.2 kV (at 30 kA)
≤ 2.4 kV (at 40 kA)
Response time t
A
Insulation resistance R
iso
≤ 25 ns
> 5 GΩ (at 500 V DC)
UL specifications
SPD Type
4CA
11/15/2016 Page 2 / 3
https://www.phoenixcontact.com/hq/products/2908667
Type 1/2 surge protection plug - VAL-MS-T1/T2 1000DC-PV-
ST/36 - 2908667
Technical data
UL specifications
Maximum continuous operating voltage MCOV (L+) - G
Nominal voltage
Mode of protection
Power distribution system
Measured limiting voltage MLV (L+) - G
Nominal discharge current I
n
(L+) - G
1050 V DC
875 V DC
(L+) - G
1
1900 V
20 kA
Standards and Regulations
Standards/regulations
EN 50539-11 2013
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
11/15/2016 Page 3 / 3