Industrial Control Transformers
SMT Series - Open Style, Aluminum Wound
The SolaHD SMT Series is economical and compact with
traditional open wound varnished coils. Ratings are from 1
kVA through 5 kVA with Class I80°C insulation system and
115°C rise under full load. SMT transformers provide excel-
lent cost benefits with NEMA regulation characteristics and
electrical performance specifications.
Features
• Available from 1000–5000 VA, 60 Hz unless noted
• Meets or exceeds electrical requirements of NEMA,
ANSI, NMTBA and JIC
Certifications and Compliances
•
•
Listed: E77014 - Type SMT
- UL 5085-1, UL 5085-2
Design Style
E77014
LR14328-4
Certified LR14328-4
-
CSA C22.2 No. 66.1, No. 66.2
•
RoHS Compliant
Related Products
• Linear Power Supplies
• DIN Rail DC Power Supplies
• Constant Voltage Transformers
Selection Table
Group 1 – 240 X 480 Volt Primary, 120 Volt Secondary 60 Hz
230 X 460 Volt Primary, 115 Volt Secondary 50/60 Hz
220 X 440 Volt Primary, 110 Volt Secondary 50/60 Hz
VA
1000
1500
2000
3000
5000
Catalog
Number
T1000
T1500
T2000
T3000
T5000
Height
in (mm)
5.63
(143.0)
6.25
(158.8)
6.25
(158.8)
8.00
(203.2)
8.00
(203.2)
Width
in (mm)
6.38
(162.1)
6.75
(171.5)
6.75
(171.5)
9.00
(228.6)
9.00
(228.6)
Depth
(in (mm)
6.38
(162.1)
8.25
(209.6)
9.13
(231.9)
9.30
(236.2)
11.3
(287.0)
Mtg
Width
in (mm)
5.31
(134.9)
5.75
(146.1)
5.75
(146.1)
8.00
(203.2)
8.00
(203.2)
Mtg
Depth
in (mm)
4.25
(108.0)
6.38
(162.1)
6.63
(168.4)
5.81
(147.6)
7.50
(190.5)
Slot Size
in (mm)
.31 x .69
(7.9 x 17.5)
.44 x .69
(11.2 x 17.5)
.44 x .69
(11.2 x 17.5)
.44 x .69
(11.2 x 17.5)
.44 x .69
(11.2 x 17.5)
Approx. Ship
Weight
lbs (kg)
22 (10.00)
28.3 (12.86)
38.5 (17.5)
55 (25.00)
91 (41.36)
Note: Fuse holders are not available for this voltage configuration.