NOW PART OF
D-Series
P RO DU C T WE BPAGE
request sample, configure part, watch video
Hydraulic-Magnetic Circuit Breaker
DIN Rail Mounted Circuit Breaker
The D-Series hydraulic-magnetic circuit breakers
feature simple snap on back panel DIN rail mounting
for easy assembly and removal. Added safety features
round out this thoughtful breaker design with recessed
wire ready terminals that are both touch proof and
shock resistant. D-Series breakers are available as a one
to four pole breaker, rated up to 50 amps, 480Y/277VAC
or 80VD and with a max IC of 5,000 amps.
1-4 0.02-50 80
Poles
Amps
VDC Max
VAC Max
480Y
Typical Applications
∙
Industrial Controls
∙
Renewable Energy
www.carlingtech.com
860.793.9281
sales
@
carlingtech.com
Tech Specs
Electrical
Maximum Voltage
Standard Current Coils
AC, 480Y VAC
(See Table A), 50/60 Hz, 80VDC
0.100, 0.250, 0.500, 0.750, 1.00,
2.50, 5.00, 7.50, 10.0, 15.0, 20.0,
25.0, 30.0, 35.0, 40.0 & 50.0.
Other ratings available - consult
factory.
DC - 6V, 12V; AC - 120V, other
ratings available, see ordering
scheme.
Minimum of 100 Megohms at 500
VDC.
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. D-Series
circuit breakers comply with the
8mm spacing and 3750V 50/60
Hz dielectric requirements from
hazardous voltage to operator
accessible surfaces and between
adjacent poles per Publications
EN 60950 and VDE 0805.
Values from Line to Load Terminal
based on Series Trip Circuit
Breaker
Mechanical
Endurance
10,000 ON-OFF operations @ 6
per minute; with rated current &
voltage.
All D-Series circuit breakers will
trip on overload, even when
actuator is forcibly held in the ON
position.
The operating actuator moves
positively to the OFF position
when an overload causes the
breaker to trip.
Trip Free
Standard Voltage Coils
Trip Indication
Insulation Resistance
Dielectric Strength
Physical
Number of Poles
Internal Circuit Config.
Weight
Standard Colors
Mounting
Rocker Type: 1-3; Handle Type:
1-4
Switch Only and Series Trip with
current or voltage trip coils.
Approximately 128 grams/pole
(Approximately 4.57 ounces/pole)
Housing - Black; Actuator - See
Ordering Scheme.
Mounts on a standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
35 x 15mm per DIN EN5002).
Resistance, Impedance
RESISTANCE, IMPEDANCE VALUES
RESISTANCE PER POLE VALUES
from Line to
to Load Terminals
from Line
Load Terminals
(Values Based on Series Trip Circuit Breaker
(Values Based on Series Trip Circuit Breaker)
1000
CURRENT
(AMPS)
TOLERANCE
(%)
100
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short
curves tested @ 90% of rated
current.
Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C,
Test Condition A. Instantaneous
and ultra-short curves tested at
90% of rated current.
Method 106D, i.e., ten 24-hour
cycles @ + 25°C to +65°C, 80-
98% RH.
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
-40° C to +85° C
0.10 - 5.0
5.1 - 20.0
20.1 - 50.0
15
25
35
10
O
H
M
S
1
0.1
0.01
0.001
0.01
Vibration
0.1
AMPERE RATING
1
10
100
Pulse Tolerance Curves
Ir
60 Hz 1/2 Cycle
Inrush Pulse Tolerance
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24, 26 (70 Amps Max.)
Ir
Moisture Resistance
50 Hz 1/2 Cycle
Inrush Pulse Tolerance
Multiple of
Rated Current
25x
Multiple of
Rated Current
22x
Time Delay Curves
42, 44 & 46
(50 Amps Max.)
Time Delay Curves
22, 24 (100 Amps Max.)
26 (70 Amps Max.)
t
Salt Spray
Thermal Shock
12x
10x
t
4.165
8.33
16.67
5.0
10.0
20.0
Time in
Milliseconds
Time in
Milliseconds
Operating Temperature
2.
*Manufacturer reserves the right to change product specification without prior notice.
Tech Specs
Table A:
Lists UL Recognized, CSA Accepted and VDE Certified configurations and performance capabilities as a Component
Supplementary Protector.
Tables
Component Supplementary Protectors
Voltage
Circuit
Configuration
Max
Rating
65
80
Series
125 / 250
250
277
480 Y
3
65
Switch Only
250
277
480 Y
3
50 / 60
DC
50 / 60
Current
Rating
Short Circuit Capacity (Amps)
UL/CSA
VDE
Application Codes
UL
CSA
Frequency Phase
1
Full Load
with
without
(Inc) with (Icn) without
Amps Backup Fuse Backup Fuse Backup Fuse Backup Fuse
DC
---
1
1&3
1
1&3
---
3
1
1&3
0.02 - 30
0.02 - 50
0.02 - 50
5,000
2
---
5,000
3,000
---
5,000
---
1,500
---
TC1, 2, OL1, U1
TC1, 2, OL1, U1
---
---
TC1, 2, OL1, C1
TC1, 2, OL1, C1
Notes:
1
DC and 1 Phase 277 V ratings are 1 or 2 poles breaking. Three phase ratings are 3 poles breaking.
2 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full
load amps not to exceed 150 A for 250V rating and 125 A for 277 and 480 V ratings.
3 UL recognition and CSA Acceptance at 480 volts refers to 3 and 4 pole versions, used only in a 3 phase WYE connected
circuit or 2 pole versions connected with 2 poles breaking 1 phase and backed up with series fusing per note 2
Agency Approvals
UL 1077
Component Recognition Program
as Protectors, Supplementary
(Guide QVNU2, File E75596)
Switches, Industrial Control
(Guide NRNT2, File E148683)
Component Supplementary
Protector under Class 3215 30,
File 047848 0 000
CSA Standard C22.2 No. 235
EN60934, VDE 0642
under File No. 10537
UL 508
CSA Accepted
VDE Certified
3.
Ordering Scheme
Sample
Part Number
Selection
Handle & Rocker
D
1
A 3 - B0 - 10 -450 - 1 2 1 - C
2
3
4
5
6
7
8
9
10
1. SERIES
D
D-Series
1
6. CURRENT RATING
(
AMPERES
)
CODE AMPERES
9
2. ACTUATOR
Handle
2
A
Handle, one per pole
B
Handle, one per multipole unit
Visi-Rocker
3
C
Indicate ON, vertical legend
D
Indicate ON, horizontal legend
E
Indicate ON, no legend
(VDE approval not available with no legend)
F
Indicate OFF, vertical legend
G
Indicate OFF, horizontal legend
H
Indicate OFF, no legend
(VDE approval not available with no legend)
Single Color Rocker
3
J
Vertical legend
K
Horizontal legend
L
No legend
(VDE approval not available with no legend)
INDICATE “ON”
VERTICAL
STYLE
LINE
020
025
030
050
075
080
085
210
215
220
225
230
235
240
245
250
255
260
265
270
ROCKER STYLE DESCRIPTIONS
INDICATE “OFF”
CODE “F”, ”N”
OR VOLTAGE COIL (NORMAL RATED VOLTAGE)
A06
A12
A18
A24
A32
CODE AMPERES
0.020
0.025
0.030
0.050
0.075
0.080
0.085
0.100
0.150
0.200
0.250
0.300
0.350
0.400
0.450
0.500
0.550
0.600
0.650
0.700
275
280
285
410
512
413
414
415
517
420
522
425
527
430
532
435
436
440
445
547
0.750
0.800
0.850
1.000
1.250
1.300
1.400
1.500
1.750
2.000
2.250
2.500
2.750
3.000
3.250
3.500
3.600
4.000
4.500
4.750
A48
A65
J06
J12
J18
450
455
460
465
470
572
475
480
485
490
495
610
710
611
711
612
712
613
614
615
5.000
5.500
6.000
6.500
7.000
7.250
7.500
8.000
8.500
9.000
9.500
10.000
10.500
11.000
11.500
12.000
12.500
13.000
14.000
15.000
J24
J48
K20
L40
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
632
635
640
645
650
16.000
17.000
18.000
19.000
20.000
21.000
22.000
23.000
24.000
25.000
26.000
27.000
28.000
29.000
30.000
32.000
35.000
40.000
45.000
50.000
SINGLE COLOR
CODE “J”, ”R”
CODE “C”
6 DC, 5 DC
12 DC, 10 DC
18 DC, 15 DC
24 DC, 20 DC
32 DC, 25 DC
48 DC, 40 DC
65 DC, 55 DC
6 AC, 5 AC
12 AC, 10 AC
18 AC, 15 AC
24 AC, 20 AC
48 AC, 40 AC
120 AC, 65 AC
240 AC, 130 AC
INDICATE
COLOR
LOCATION
LINE
LINE
HORIZONTAL
STYLE
CODE “D”
CODE “G”, ”O”
CODE “K”, ”U”
7. TERMINAL
1
2
#10 Screw & Pressure Plate for Direct Wire Connection
#10 Screw without Pressure Plate
LINE
LINE
FIG.B
LINE
8. ACTUATOR COLOR & LEGEND
Actuator or
Visi-Color Marking:
Color:
White
Black
Red
Green
Blue
Yellow
Gray
Orange
I-O
A
C
F
H
K
M
P
R
ON-OFF
B
D
G
J
L
N
Q
S
Marking Color:
Single Color
Dual/None Rocker/Handle
1
Black
2
White
3
White
4
White
5
White
6
Black
7
Black
8
Black
Visi-Rocker
7
White
n/a
Red
Green
Blue
Yellow
Gray
Orange
3. POLES
1
2
One
Two
2
3
4
Three
Four
4. CIRCUIT
A0
B0
C0
Switch Only (No Coil)
4
Series Trip (Current)
Series Trip (Voltage)
5. FREQUENCY & DELAY
03
10
5
11
12
14
16
20
5
21
22
24
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
DC Long
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
50/60Hz Medium
9. MOUNTING / VOLTAGE
26
32
34
36
42
6
44
6
46
6
52
6
54
6
56
6
50/60Hz Long
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, High-inrush
50/60Hz Medium, High-inrush
50/60Hz Long, High-inrush
DC, Short, High-inrush
DC, Medium, High-inrush
DC, Long, High-inrush
1
C
8
2
D
8
MOUNTING STYLE
Threaded Insert
6-32 x 0.195 inches
6-32 X 0.195 inches
ISO M3 x 5mm
ISO M3 x 5mm
VOLTAGE
< 300
≥ 300
< 300
≥ 300
10. AGENCY APPROVAL
C
D
9
UL Recognized & CSA Accepted
VDE Certified, UL Recognized & CSA Accepted
Notes:
1
Handle breakers available up to four poles. Rocker breakers available up to
three poles.
2
Actuator Code:
A: Multi-pole units factory assembled with common handle tie.
B: Handle location as viewed from front of breaker:
2 pole - left pole
3 pole - center pole
4 pole - two handles at center poles
3
Multipole rocker breakers have one rocker per breaker, as viewed from the
front of the panel. Two pole - left pole. Three pole - center pole
4
≤ 30A, select Current Rating code 630. 31-50A, select Current Rating code 650.
5
Voltage coil only available with delay codes 10 & 20.
6
Available to 50A max with circuit code BO only.
7
Color shown is visi and legend with remainder of rocker black.
8
≥ 300V: Three pole breaker 3Ø or 2 pole breaker 1Ø, UL/CSA limited to 30 FLA max.
9
VDE Approval requires Dual (I-O, ON-OFF) or I-O markings
4.
Configure Complete Part Number >
Browse Standard Parts >
Circuit & Terminal Diagram
inches [millimeters]
HANDLE ACTUATOR
ROCKER ACTUATOR
INDICATE “ON”
SERIES TRIP
(2 TERM’S.)
LINE
SWITCH ONLY
(2 TERM’S.)
LINE
MULTI-POLE INDENTIFICATION SCHEME
POLE
1
POLE
2
POLE
3
LINE
LOAD
LOAD
ROCKER ACTUATOR
INDICATE “OFF”
&
SINGLE COLOR
SERIES TRIP
(2 TERM’S.)
LOAD
LOAD
SWITCH ONLY
(2 TERM’S.)
LOAD
MULTI-POLE INDENTIFICATION SCHEME
POLE
1
POLE
2
POLE
3
LOAD
LINE
LINE
(HANDLE ACTUATOR SHOWN)
.346
[8.79] TYP
LINE
LINE
ON
TIGHTENING TORQUE SPEIFICATIONS
3.612
[91.75]TYP
THREAD SIZE
#6-32[M3] HARDWARE
#6-32 THD TERMINAL
SCREW
7-9 IN-LBS
[0.8-1.0 NM]
15-20 IN-LBS
[1.7-2.3 NM]
TABLE A
2.920
[74.17]TYP
TORQUE
F
OF
LOAD
1.240
[31.49]TYP
TERMINAL ARE SUPPLIED WITH
#10-32 SCREW AND PRESSURE
PLATE PER TERMINAL
Notes:
1
Tolerance ±.020 [.51] unless otherwise specified.
5.