https://www.phoenixcontact.com/pi/products/2900538
Hybrid motor starter - ELR H5-SC- 24DC/500AC-9 - 2900538
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 9 A output current, with 24 V DC control
voltage, and screw connection.
Your advantages
22.5 mm wide
Reduction in wiring
Space saving
Long service life
3-phase loop bridges
Low-wear switching
Key Commercial Data
Packing unit
GTIN
GTIN
4046356526104
1 pc
Technical data
Device supply
Rated control circuit supply voltage U
S
Control supply voltage range
Rated control supply current I
S
Type of protection
24 V DC
19.2 V DC ... 30 V DC
40 mA
Surge protection
Reverse polarity protection
Input data
Input name
Rated actuating voltage U
C
Triggering voltage range
Rated actuating current I
C
Control input right/left
24 V DC
19.2 V DC ... 30 V DC
5 mA (Input type 1)
10/28/2018 Page 1 / 5
https://www.phoenixcontact.com/pi/products/2900538
Hybrid motor starter - ELR H5-SC- 24DC/500AC-9 - 2900538
Technical data
Input data
Switching threshold
Typical turn-off time
Type of protection
9.6 V (“0” signal)
19.2 V (“1” signal)
< 30 ms
Reverse polarity protection
Output data load output
Output name
Rated operating voltage U
e
Operating voltage range
Rated operating current I
e
Mains frequency
Load current range
Trigger characteristic in acc. with IEC 60947-4-2
Leakage current
Type of protection
AC output
500 V AC
42 V AC ... 550 V AC
9 A (AC-51)
6.5 A (AC-53a)
50/60 Hz
0 A ... 9 A (see to derating)
-
0 mA
Surge protection
General
Switching frequency
Mounting position
Mounting type
Assembly instructions
Operating mode
Maximum power dissipation
Minimum power dissipation
Operating voltage display
Status display
≤ 2 Hz (Load-dependent)
vertical (horizontal DIN rail, motor output below)
DIN rail mounting
alignable, for spacing see derating
100% operating factor
7W
0.88 W
Green LED
Yellow LED
Connection data, input side
Connection name
Connection method
Stripping length
Screw thread
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Torque
Control circuits
Screw connection
8 mm
M3
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
24 ... 14
0.5 Nm ... 0.6 Nm
Connection data, output side
Connection name
Connection method
Stripping length
Screw thread
Load circuit
Screw connection
8 mm
M3
10/28/2018 Page 2 / 5
https://www.phoenixcontact.com/pi/products/2900538
Hybrid motor starter - ELR H5-SC- 24DC/500AC-9 - 2900538
Technical data
Connection data, output side
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Torque
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
24 ... 14
0.5 Nm ... 0.6 Nm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Degree of protection
-25 °C ... 70 °C (observe derating)
-40 °C ... 80 °C
IP20
Dimensions
Width
Height
Depth
22.5 mm
106.6 mm
113.7 mm
UL data
SCCR
FLA
Group installation
100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (500 V AC (fuse: 20 A RK5 (standard fault)))
6.5 A (500 V AC)
20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and
stranded)
Category code
NLDX / NRNT
Insulation characteristics
Rated insulation voltage
Rated surge voltage
Overvoltage category
Degree of pollution
Designation
Insulation
500 V
6 kV
III
2
Insulation characteristics between the control input and control supply
voltage, and auxiliary circuit to the main circuit
Safe isolation (IEC 60947-1/EN 50178) at operating voltage ≤ 300 V AC
Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
Designation
Insulation
Isolation characteristics between the control input and control supply
voltage to auxiliary circuit
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Standards and Regulations
Designation
Standards/regulations
Standards/regulations
IEC 60947-1
IEC 60947-4-2
IEC 61508
10/28/2018 Page 3 / 5
https://www.phoenixcontact.com/pi/products/2900538
Hybrid motor starter - ELR H5-SC- 24DC/500AC-9 - 2900538
Technical data
Standards and Regulations
ISO 13849
Approvals/conformities
UL certificate
NLDX.E228652
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Diagram
Load current [A]
9
8
7
6
5
4
3
2
1
0,18
0
50
60
70
Ambient temperature [°C]
= aligned with > 20 mm spacing
= aligned without spacing
10
20
30
40
Block diagram
1/L1 3/L2 5/L3
U
s
T
R
L
2/T1 4/T2 6/T3
Logic
µP
Derating diagram
Approvals
Approvals
Approvals
UL Listed / cUL Listed / UL Listed / IECEE CB Scheme / cUL Listed / CCC / EAC
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 228652
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 228652
10/28/2018 Page 4 / 5
https://www.phoenixcontact.com/pi/products/2900538
Hybrid motor starter - ELR H5-SC- 24DC/500AC-9 - 2900538
Approvals
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 323771
IECEE CB Scheme
http://www.iecee.org/
DE1-55728
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 323771
CCC
2016010304871315
EAC
RU C-
DE.A*30.B.01082
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
10/28/2018 Page 5 / 5