https://www.phoenixcontact.com/us/produkte/2986012
Safety module - PSR-SCP- 24DC/TS/M - 2986012
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
A freely configurable master module for the monitoring of emergency stop, safety doors, light grids,
etc., with 20 safe inputs and four safe outputs, four message outputs, two clock outputs and two
ground switching outputs, can be expanded with additional input/output modules. Width: 67.5 mm
Why buy this product
Including PSR-TBUS plug-in connector (DIN rail connector) for adapting safe extension modules
Including IFS-CONFSTICK memory stick for easily storing and saving the configuration
Option for connecting fieldbus gateways for diagnostics and signaling functions
Easy graphical configuration with the SAFECONF software
Flexible extension with safe inputs and outputs
Multifunctional use for a wide range of safety functions
Quick startup thanks to user-friendly simulation and test options
Easy graphical configuration instead of complex programming
Up to Cat. 4/PL e according to ISO 13849-1, SILCL 3 according to IEC 62061, SIL 3 according to IEC 61508
Safe and standard extension via INTERFACE DIN rail TBUS
With 20 safe inputs, 4 safe outputs, 4 alarm outputs, and 2 clock outputs on a design width of just 67.5 mm
Key commercial data
Packing unit
Minimum order quantity
Catalog page
GTIN
Custom tariff number
Country of origin
85364900
GERMANY
0
1
Page 30 (IF-2011)
Technical data
Input data
Nominal input voltage UN
Input voltage range in reference to UN
Typical input current at UN
Maximum response time
Bypassing voltage dips
Recovery time
24 V DC
0.85 ... 1.1
110 mA
< 30 ms
20 ms
< 10 s
05.06.2012 Page 1 / 5
https://www.phoenixcontact.com/us/produkte/2986012
Safety module - PSR-SCP- 24DC/TS/M - 2986012
Technical data
Input data
Protective circuit
Status display
Number of safe inputs
Nominal voltage UN
Typical current consumption
Signal level "0" signal
Signal level "1" signal
Permissible cable length
Error detection time at 1-channel structure
Surge protection Suppressor diode
4 LEDs (green, red)
20
24 V DC
4 mA
<5V
> 11 V
2000 m
<1s
Output data
Output data
Number of safe semiconductor outputs
Number of ground switching outputs
Nominal voltage UN
Limiting continuous current
Max. capacitive load
Max. inductive load
Test pulses
Short-circuit protection
Clock outputs
Number of outputs
Nominal voltage UN
Limiting continuous current
Test pulses
Short-circuit protection
Alarm outputs
Number of outputs
Nominal voltage UN
Limiting continuous current
Short-circuit protection
20 safe digital inputs 4 safe digital outputs 4 digital alarm outputs
Clock outputs Yes
4 (Cat.4 / ISO 13849)
2
24 V DC
2 A (see derating curve)
1 µF (When using electromechanical components (e.g.,
contactors), the capacitive load can be disregarded.)
(A suitable and effective protective circuit is to be provided for
inductive loads. A recommended measure is the use of free-
wheeling diodes.)
< 1 ms (To ground)
Yes
Yes
2
24 V DC (A1 / A2)
100 mA
~ 100 ms
Yes
Yes
4
24 V DC (A1 / A2)
100 mA
Yes
General data
Width
Height
Depth
Ambient temperature (operation)
Ambient temperature (storage/transport)
Mounting position
Category according to EN 13849-1
Name
67.5 mm
99 mm
114.5 mm
-20 °C ... 55 °C
-20 °C ... 70 °C
Horizontal
4
Air and creepage distances between the power circuits
05.06.2012 Page 2 / 5
https://www.phoenixcontact.com/us/produkte/2986012
Safety module - PSR-SCP- 24DC/TS/M - 2986012
Technical data
General data
Standards/regulations
Rated surge voltage / insulation
Rated insulation voltage
Pollution degree
Surge voltage category
Housing material
Number of possible safe extension modules
Interfaces
DIN EN 50178
0.8 kV / Basic isolation
50 V
2
III
Polyamide PA non-reinforced
10
USB
Connection data
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
Screw thread
Connection method
0.2 mm²
2.5 mm²
0.2 mm²
2.5 mm²
24
12
7 mm
M3
Screw connection
Classifications
eclass
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
27371102
27371102
27371901
27371901
27371819
etim
ETIM 2.0
ETIM 3.0
ETIM 4.0
EC001449
EC001449
EC001449
unspsc
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211901
39121501
39121501
39121501
39121501
Approvals
Certificates
05.06.2012 Page 3 / 5
https://www.phoenixcontact.com/us/produkte/2986012
Safety module - PSR-SCP- 24DC/TS/M - 2986012
Approvals
Certification
UL Listed / GOST / cUL Listed / cUL Listed
Certification EX
Certification submitted
Approval details
UL Listed
GOST
cUL Listed
cUL Listed
Drawings
Connection diagram
Application drawing
INTERFACE-PSR
use only
PSR-TBUS
INTERFACE-PSR
use only
PSR-TBUS
INTERFACE-PSR
use only
PSR-TBUS
PSR-TBUS-
Steckverbinder
PSR-TBUS-
PSR-TBUS-
Steckverbinder Steckverbinder
S1
K2
K1
K1
K2
S2
The TBUS connectors carry out the cross-wiring between the modules.
L+
L-
I0
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
I17
I18
I19
O0
O1
O2
O3
A1
A1
A2
A2
24V
0V
O0-
O1-
T0
T0
T1
T1
M0
M1
M2
M3
PSR - TRISAFE
05.06.2012 Page 4 / 5
https://www.phoenixcontact.com/us/produkte/2986012
Safety module - PSR-SCP- 24DC/TS/M - 2986012
Diagram
Total current
Output Ox [A]
Circuit diagram
A1 A2
T0 T0 T1 T1
I0 I1
I19 M0 M1 M2 M3
2
1,5
TBUS
NON-SAFE
POWER
24V DC
TEST PULSE
OUTPUT
SAFE INPUT
MONITORING
OUTPUT
1
0,5
0
0
25 30 35 40 45 50 55 60
Ambient temperature [°C]
LOGIC
POWER
24V DC
SAFE OUTPUT
USB
CONF
STICK
24V 0V O0 O1 O2 O3 O0- O1-
© Phoenix Contact 2012 - all rights reserved
http://www.phoenixcontact.com
05.06.2012 Page 5 / 5
TBUS
SAFE