Power Supply, Primary Switch Mode, Narrow Design
MINI-PS-100-240AC/5DC/3
MINI POWER provides:
•
Extra narrow
widths of 22.5 and 45 mm (0.886 and
1.772 in.)
•
Global use
due to a wide range input
•
A high level of operational safety
in complex global
networks
•
Reliable start up
of heavy loads due to POWER
BOOST
The reliability of a power supply determines the
availability of individual components in a system and
whether complex systems can function safely.
The globalization of markets increases the demands
placed on the power supply. A wide range input and a
high level of availability are required. These
requirements are met by MINI POWER.
1. Brief Description
MINI POWER is the extra narrow power supply,
which is available in widths of 22.5 and 45 mm (0.886
and 1.772 in.).
In addition to a 24 V version with output currents of
0.65 A and 2 A, special voltages are also available with
5 V/3 A and +/- 15 V/1 A.
The POWER BOOST - a power reserve of up to
100% - ensures a reliable start of difficult loads.
The high level of operational safety is also ensured in
complex global networks. MINI POWER also operates
in applications where static voltage dips, transient
power supply failures or phase failure are common.
Large capacitors ensure mains buffering of more
than 20 ms at full load.
2. Area of Application
MINI POWER can be used globally due to the
consistent conversion of a wide range input.
In this way, your entire system can be tested at any
production location in the world and can be delivered to
any location in the world without faulty switching of the
input voltage. This reduces storage costs and logistical
effort.
An international approval package including
UL 60950 for IT equipment and UL 508 for industrial
control equipment enables the device to be used
globally.
Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local contact: www.phoenixcontact.com/salesnetwork
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/5DC/3
3. Technical Data
114.5
L (+)
NC
NC
N (–)
99
22.5
MINI-PS-100-240AC/5DC/3
1 AC
8 mm (0.31 in.)
Uu
solid
[mm
2
]
flexible
AWG
torque
[Nm]
0.5 - 0.6
0.5 - 0.6
Input
Output
0.2 - 2.5
0.2 - 2.5
0.2 - 2.5 24 - 14
0.2 - 2.5 24 - 14
Description
Power Supply
,
primary switch mode, narrow design
Technical Data
Input Data
1
Nominal input voltage
Input voltage range
Frequency
Current consumption (for nominal values)
Inrush current limiting/I
2
t (+25°C [+77˚F])
Mains buffering for a nominal load (typical)
Switch-on time after applying the AC supply voltage
Transient surge protection
Input fuse, internal
Recommended fuse
Type
MINI-PS-100-240AC/5DC/3
Order No.
29 38 71 4
Pcs.
Pkt.
1
100 - 240 V AC (wide range input)
85 - 264 V AC (0.4-0.2 A) 90 - 350 V DC (0.4-0.2 A)
45 - 65 Hz
0 Hz
0.2 A (120 V AC) - 0.4 A (230 V AC), approximately
< 25 A/< 1.5 A
2
s, typical
> 20 ms (120 V AC)/> 100 ms (230 V AC)
<1s
Varistor
2 AT (device protection)
Circuit breaker 10 A or 16 A
Characteristic B (EN 60 898)
Output Data
2
Nominal output voltage U
N
/tolerance
Setting range for the output voltage
Output current during convection cooling and nominal values
POWER BOOST I
BOOST
(t = 2, minutes [typical])
Nominal output current I
N
-25°C to +60°C (-13˚F to +140˚F)
Derating
Short-circuit current limit
Startup of capacitive loads
System deviation on:
Load change static 10 - 90%
Load change dynamic 10 - 90%
Input voltage change ±10%
Maximum power loss
No load/nominal load
Level of efficiency (typical)
Response time U
OUT
(10% - 90%)
Residual ripple/switching peaks (20 MHz)
Can be connected in parallel
Internal surge protection
Resistance to return supply
Signal Output Data
LED (U
out
> 4 V DC
=
LED permanently on)
5 V DC/±1%
4.5 - 5.5 V DC
Up to 6 A (U
out
= 5 V DC)
3 A (U
out
= 5 V DC)
From +60°C (+140˚F), 5% per Kelvin
I
BOOST
≈
6 A,
approximately
Unlimited
< 1%, typical
< 3%, typical
< 0.1%, typical
1.7 W/5 W
> 73% (for 230 V AC and nominal values)
< 100 ms, typical
< 100 mV
pp
(for nominal values)
To increase redundancy and power
Yes, limited to 20 V DC, approximately
6 V DC
Green LED
PHOENIX CONTACT page 2 of 8
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/5DC/3
General Data
Isolation voltage:
Input/output
Approval package
Safety transformers for switched-mode power supplies
Electrical safety
(of IT equipment)
Industrial control equipment
Equipping high voltage installations
with electronic equipment
Safety extra-low voltage
Safe isolation
Protection against electric shock
Protection against dangerous shock currents,
basic requirements for safe isolation
in electrical equipment
Limitation of harmonic line currents
Mounting position
Can be mounted with spacing
Degree of protection
Class of protection
MTBF
Housing version
Dimensions (W x H x D)
Weight
Climatic Data
Ambient temperature
Humidity
Vibration
Shock
Degree of pollution
Climatic category
- Vertical
- Horizontal
4 kV AC (type test)/3 kV AC (routine test)
EN 61 558-2-17
EN 60950/VDE 0805
UL/C-UL Recognized UL 60 950
u
1)
UL/C-UL Listed UL 508
U
1)
LISTED
EN 50 178/VDE 0160 (Surge Voltage Category III)
PELV (EN 50 178)
SELV (EN 60 950)
VDE 0100-410
DIN 57 100-410
DIN VDE 0106-101
According to EN 61000-3-2
On horizontal NS 35 DIN rail according to EN 50022
≥
8 cm (0.31 in.)
0 cm
IP 20
ΙΙ
, (in closed control cabinets)
> 500 000 h according to IEC 1709 (SN 29 500)
Polyamide PA, color green
(22.5 x 99 x 114.5 mm [0.886 x 3.898 x 4.508 in.])
0.17 kg, approximately
Operation
Storage
according to IEC 68-2-6
according to IEC 68-2-27
-25°C to +70°C (-13˚F to +158˚F) (> +60°C [+140˚F] derating)
-40°C to +85°C (-40˚F to +185˚F)
up to 95% at +25°C (+77˚F), no condensation
< 15 Hz, amplitude ±2.5 mm/15 Hz - 150 Hz, 2.3 g
30 g all space directions
2
(according to EN 50 178)
3K3 (according to EN 60 721)
UL approval for AC input voltage and ambient temperature up to
+60°C (+140°F)
1)
c
Conforms to the EMC Directive 89/336/EEC and the
Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility)
Noise Immunity According to EN 61000-6-2:
Electrostatic discharge
(ESD)
Electromagnetic
HF
field
Fast transients
(burst)
Surge current loads
EN 61000-4-2
3)
Housing
Contact discharge:
Air discharge:
Housing
Frequency:
Field strength:
Input:
Output:
Input:
Output:
Conducted
interference
Voltage dips
EN 61000-4-6
2)
I/O:
Frequency:
U
0
:
Input:
Requirements
EN 61 000-6-2
4 kV
8 kV
80 - 1000 MHz
10 V/m
2 kV
2 kV
2 kV
1 kV
0.5 kV
0.5 kV
0.15 - 80 MHz
10 V
30% reduction of the input
voltage for 0.5 periods
Not required
asymmetrical
5)
asymmetrical
5)
asymmetrical
5)
symmetrical
4)
asymmetrical
5)
symmetrical
4)
asymmetrical
5)
MINI-PS-100-240AC/5DC/3
Level 3
8 kV
8 kV
Level 3
80 - 1000 MHz/1.4 - 2.0 GHz
10 V/m
4 kV (Level 4)
2 kV (Level 3)
2 kV (Level 3)
1 kV (Level 3)
0.5 kV (Level 1)
0.5 kV (Level 1)
Level 3
0.15 - 80 MHz
10 V
See input data:
Mains buffering
> 20 ms
900 MHz/1800 MHz
20 V/m
EN 55011 (EN 55022) Class B
7)
EN 55011 (EN 55022) Class B
7)
EN 61000-4-3
2)
EN 61000-4-4
3)
EN 61000-4-5
3)
EN 61000-4-11
3)
Simulation of
radiophone
Radio interference
Radio interference
EN 50204
Frequency:
Field strength:
Noise Emission According to EN 50081-2:
EN 55011
EN 55011
Class A
6)
Class A
6)
EN 55011 corresponds to CISPR11/EN 55022 corresponds to
CISPR22
EN 61000 corresponds to IEC 1000
2)
Criterion A: Normal operating characteristics within the specified
limits.
3)
Criterion B: Temporary adverse effects on the operating
characteristics that the device corrects
4)
symmetrical:
5)
6)
Class
7)
Cable to cable
asymmetrical: Cable to ground
A:
Class B:
Industrial application
Industrial and domestic applications
PHOENIX CONTACT page 3 of 8
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/5DC/3
4. Device View, Connections, and Control Elements
3
4
–
2
P
NI
MI
5
5.
5- C
4. D
V
C
D K
O
C
A (-)
V N
0
24 NC
0-
10 NC
IN )
(+
L
E
OW
R
–
T
U
O
+
C
+
D
V
5
1
L
NC
NC
INPUT
AC:
N
100-240V
5V DC
50-60Hz
±1%
Range:
3A
85-264V
0.4-0.2A
DC:
90-350V
0.4-0.2A
MINI-PS-100-240AC/5DC/3
5
6
7
8
Order No.: 29 38 71 4
Power Supply
OUTPUT
APPROVALS
TEMPERATURE
U
LISTED
–25
INDUSTRIAL
CONTROL
EQUIPMENT
43KA
www.interface.phoenixcontact.com
Read installation instructions
before connecting to mains
- 25 … +
60
°C
- 13 … + 140
°F
u
INFORMATION
TECHNOLOGY
EQUIPMENT
5
Figure 04
1
AC input:
Input voltage 85 - 264 V AC
Frequency 45 - 65 Hz
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible)
(24 - 14 AWG)
Internal fuse 2 AT
Recommended fuse
10 A or 16 A c.b./Characteristic B
2
DC output:
Output voltage 5 V DC (default),
can be set from 4.5 - 5.5 V DC using
a potentiometer
3
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible)
(AWG 24 - 14)
The device is idling-proof and short-circuit-proof.
3
Potentiometer 4.5 - 5.5 V DC
4
DC OK LED
5
Universal latching foot for EN DIN rails
Installation and startup
must only be carried out by
qualified personnel. The relevant country-specific
regulations (e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure
that:
• The line has been connected correctly and protection
is provided against electric shock.
• The device can be switched off outside the power
supply according to EN 60950 regulations (e.g., by
the line protection on the primary side).
• All supply lines have sufficient fuse protection and
are the correct size.
• All output cables are the correct size for the maximum
device output current or have separate fuse
protection.
• Sufficient convection is ensured.
MINI POWER is a built-in device. After installation
the terminal area must be covered to provide sufficient
protection against unauthorized access to live parts.
This is ensured by installing the device in the control
cabinet or distributor box.
The device contains dangerous live components
and high levels of stored energy.
5. Safety and Warning Instructions
To ensure safe operation of the device and that
all functions can be used, please read these
instructions carefully.
Caution: Never carry out work when the
power is turned on, this is highly
dangerous.
PHOENIX CONTACT page 4 of 8
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/5DC/3
6. Installation
6.1. Mounting
The power supply can be snapped onto all DIN rails
according to EN 50022-35. The device must be
mounted horizontally (input terminals facing
downwards).
Installation Dimensions
8
–
MINI POWER
–
OU +
T
5V +
DC
8.0 cm (3.150 in.) for vertical installation
4.5
-5
V D .5
C
DC
OK
IN
L(+ 100
) N -24
C 0V
NC AC
N(-
)
22.5
Installation depth 106 mm (4.173 in.) (+ DIN
114.5 mm (4.508 in.)
80
106 mm (4.173 in.)
–
259 mm (10.197 in.)
+
–
+
OUT 5 V DC
99 mm (3.898 in.)
MINI POWER
4.5-5.5
V DC
DC
OK
IN 100-240 V AC
L(+) NC NC N(-)
80
Mounting:
Place the module with the DIN rail guideway on the
top edge
of the DIN rail and then snap it
downwards
.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the
bottom edge
of the
DIN rail.
Mounting
PHOENIX CONTACT page 5 of 8
7
6
To ensure sufficient convection, we
recommend the following minimum
spacing be used between modules:
5
/3
DC
C/5
40A
4
00-2
71
S-1
38
I-P
o.: 29
RE
MIN
r N
ly
ATU
e
upp
MPER
Ord
rS
TE
we
Po
–25
UT
TP
OU
UT
INP
:
0V
AC 0-24 z
10 0H
50-6ge:
n
Ra 64V
5-2 .2A
8 -0
0.4
:
V
DC -350A
90 -0.2
0.4
DC
5V
±
1%
3A
PR
AP
S
IAL
AL
OV
USTRL
–
–
+
+
°C
60
+
… 40
°F
- 25 … + 1
- 13
ION
AT Y
RM LOG
INFO NO T
CH EN
TE UIPM
EQ
U
LIS
TE
D
ns
INDNTRO T
EN
c ti o s
COUIPM
tr u a in
EQ A
in s m
43K
m
o n to
a ti n g
t.co
ta ll c ti
tac
in s n n e
con
ad c o
nix
R efo re
oe
be
.ph
u
ww
nte
w.i
rfa
ce
Figure 05
Figure 06
Removal
Figure 07