https://www.phoenixcontact.com/us/products/2903335
Relay Module - RIF-1-RPT-LV-230AC/1X21AU - 2903335
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Pre-assembled relay module with push-in connection, consisting of: relay base, multi-layer contact relay, plug-in
display/suppressor module, and retaining bracket. Contact type: 1 PDT. Input voltage: 230 V AC
The figure shows the 24 V DC
version
Key commercial data
Packing unit
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 pc
68.0 GRM
85364900
Germany
Technical data
Dimensions
Width
Height
Depth
16 mm
93 mm
75 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-40 °C ... 50 °C
-40 °C ... 85 °C
Coil side
Nominal input voltage U
N
Input voltage range in reference to U
N
Nominal input current at U
IN
Typical response time
Typical release time range
Operating voltage display
230 V AC
(see diagram)
6 mA
3 ms ... 12 ms
3 ms ... 20 ms
Yellow LED
3/7/14 Page 1 / 6
https://www.phoenixcontact.com/us/products/2903335
Relay Module - RIF-1-RPT-LV-230AC/1X21AU - 2903335
Technical data
Coil side
Protective circuit
Varistor
Contact side
Contact type
Contact material
Maximum switching voltage
Minimum switching voltage
Maximum inrush current
Min. switching current
Limiting continuous current
Interrupting rating (ohmic load) max.
Switching capacity in acc. with DIN VDE 0660/IEC 60947
Note
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Min. switching current
Interrupting rating (ohmic load) max.
1 PDT
AgNi, hard gold-plated
30 V AC
36 V DC
100 mV (at 10 mA)
50 mA
1 mA (at 24 V)
50 mA
1.2 W (at 24 V DC)
2 A (24 V (DC13))
6 A (230 V (AC 15))
the following values are applicable if a gold layer is destroyed
250 V AC/DC
12 V (at 10 mA)
25 A (20 ms, N/O contact)
10 mA (at 12 V)
240 W (at 24 V DC)
58 W (at 48 V DC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
2500 VA (for 250 V AC)
Connection data
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section stranded, with ferrule with plastic sleeve min.
Conductor cross section stranded, with ferrule with plastic sleeve max.
Conductor cross section stranded, with ferrule without plastic sleeve min.
Conductor cross section stranded, with ferrule without plastic sleeve max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Push-in connection
0.14 mm²
1.5 mm²
0.14 mm²
1.5 mm²
0.14 mm²
1.5 mm²
0.14 mm²
1.5 mm²
26
16
3/7/14 Page 2 / 6
https://www.phoenixcontact.com/us/products/2903335
Relay Module - RIF-1-RPT-LV-230AC/1X21AU - 2903335
Technical data
Connection data
Stripping length
8 mm
General
Type of note
Note
Test voltage relay winding/relay contact
Operating mode
Degree of protection
Mechanical service life
Standards/regulations
Rated insulation voltage
Pollution degree
Surge voltage category
Mounting position
Assembly instructions
Notes on operation
FBS 2-6... plug-in bridge for the input side (A2) and FBS-2-8... plug-in
bridge for the output side (11/21)
4 kV
rms
(50 Hz, 1 min.)
100% operating factor
IP20 (Relay socket)
RT II (Relay)
Approx. 10 cycles
DIN EN 50178
IEC 62103
250 V AC
2
III
any
In rows with zero spacing
7
Articles in set
Relay socket - RIF-1-BPT/2X21 - 2900931
RIF-1... relay base, for miniature power relay with 1 or 2 PDTs or solid-state relays of the same design, push-in
connection, plug-in option for input/suppressor modules, for mounting on NS 35/7,5
Single relay - REL-MR-230AC/21HC AU - 2961529
Pluggable miniature relays, with power contact for high continuous current and additional hard gold plating, 1 PDT, input
voltage 230 V AC
3/7/14 Page 3 / 6
https://www.phoenixcontact.com/us/products/2903335
Relay Module - RIF-1-RPT-LV-230AC/1X21AU - 2903335
Articles in set
Plug-in module - RIF-LV-120-230 AC/110 DC - 2900944
Plug-in module, for mounting on RIF-1, RIF-2, RIF-3, and RIF-4, with varistor and yellow LED, input voltage: 120 - 230 V
AC/110 V DC ±20%
Retaining bracket - RIF-RH-1 - 2900953
Relay retaining bracket, with ejector function and holder for marking material, suitable for RIF-1 relay base, for 16 mm tall
miniature power relay and solid-state relay
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27371102
27371102
27371603
27371603
27371603
27371603
27371603
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001456
EC001456
EC001437
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211917
39121516
39121516
39121516
39121516
Drawings
3/7/14 Page 4 / 6
https://www.phoenixcontact.com/us/products/2903335
Relay Module - RIF-1-RPT-LV-230AC/1X21AU - 2903335
Circuit diagram
22 12
24 14
Coil voltage U/U
N
Diagram
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1,0
0,9
0,8
0,7
0,6
20
21 11
A2
A1
AC coils
30
DC coils
AC coils
40
50
60
70
Ambient temperature [°C]
80
Operating voltage range
Diagram
20
10
7
Diagram
Switching current [A]
Cycles
10
6
4
2
1
0,5
0,3
0,2
0,1
10
20
30
50 70 100
200
Switching voltage [V]
300
10
6
1
10
5
2
10
4
0
1
2
3
4
5
6
7 8
9 10 11 12 13 14 15 16
Switching current [A]
1
250 V AC, ohmic load (DC coils)
2
250 V AC, ohmic load (AC coils)
AC, ohmic load
DC, ohmic load
DC, L/R = 40 ms
Interrupting rating
Electrical service life
Diagram
1
0,9
Reduction factor
0,8
0,7
0,6
0,5
0,4
0,3
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
COS
j
Service life reduction factor
3/7/14 Page 5 / 6