UNO-PS/1AC/12DC/55W
Primary-switched power supply unit
Data sheet
105550_en_00
1
Description
© PHOENIX CONTACT 2013-04-04
The UNO POWER power supply unit impresses in world-
wide use thanks to maximum energy efficiency. Low no-
load losses and the high degree of efficiency save energy.
Thanks to its high power density, the UNO POWER power
supply unit is the ideal solution, particularly in compact con-
trol boxes.
Features
–
–
–
Worldwide use thanks to input voltage range of
85 V AC ... 264 V AC
Maximum system availability through reliable power
supply with 12 V DC
Maximum energy efficiency thanks to optimized
efficiency over the entire operating range of the
power supply unit and low no-load losses
Particularly compact: 55 W of power from this narrow
power supply, which is just 35 mm wide
–
Make sure you always use the latest documentation.
It can be downloaded from the product at
phoenixcontact.net/products.
UNO-PS/1AC/12DC/55W
2
1
2
3
4
5
6
Table of contents
Description .............................................................................................................................. 1
Table of contents ..................................................................................................................... 2
Ordering data .......................................................................................................................... 3
Technical data ......................................................................................................................... 4
Intended use............................................................................................................................ 7
Structure.................................................................................................................................. 7
6.1
Device elements
.................................................................................................................. 7
6.2
Block diagram
..................................................................................................................... 7
Assembly................................................................................................................................. 8
7.1
Unpacking
......................................................................................................................... 8
7.2
Mounting the power supply unit
............................................................................................... 8
7.3
Mounting on a DIN rail
......................................................................................................... 10
7.4
Normal mounting position
.................................................................................................... 10
Installing the power supply unit.............................................................................................. 11
8.1
Safety regulations and installation notes
.................................................................................. 11
8.2
Mains connection
.............................................................................................................. 11
8.3
Device connections
............................................................................................................ 12
8.4
Connecting cables
............................................................................................................. 12
Operating behavior of the power supply unit.......................................................................... 13
9.1
Normal operation
............................................................................................................... 13
9.2
Overload response
............................................................................................................. 13
9.3
Behavior at ambient temperatures > 55°C
................................................................................ 13
9.4
Behavior in the case of alternative mounting positions
................................................................. 14
Operating the power supply unit ............................................................................................ 17
10.1 Function monitoring
............................................................................................................ 17
10.2 Operating power supply units in parallel
.................................................................................. 18
10.3 Operating the power supply unit in series
................................................................................. 19
Removal ................................................................................................................................ 19
11.1 Removing the power supply unit
............................................................................................ 19
11.2 Notes on disposal
.............................................................................................................. 19
7
8
9
10
11
105550_en_00
PHOENIX CONTACT
2
UNO-PS/1AC/12DC/55W
3
Ordering data
Type
UNO-PS/1AC/12DC/55W
Description
DIN rail power supply unit 12 V DC/55 W, primary-switched, single-phase
Order No.
2902999
Pcs. / Pkt.
1
Accessories
Redundancy module, 5-24 V DC, 2x 5 A, 1x 10 A
Type
STEP-DIODE/5-24DC/2X5/1X10
Order No.
2868606
Pcs. / Pkt.
1
Our range of accessories is being continually extended, our current range can be found in the download area.
105550_en_00
PHOENIX CONTACT
3
UNO-PS/1AC/12DC/55W
4
Technical data
Input data
Nominal input voltage range
AC input voltage range
AC frequency range
Current consumption
Inrush current limitation
I
2
t
Typical response time
Power failure bypass
Protective circuit
Input fuse, integrated
Choice of suitable fuses
100 V AC ... 240 V AC
85 V AC ... 264 V AC
45 Hz ... 65 Hz
1 A (120 V AC)
0.6 A (230 V AC)
< 30 A (typical)
< 0.5 A
2
s
<1s
> 20 ms (120 V AC)
> 90 ms (230 V AC)
Transient surge protection Varistor
2 A (slow-blow, internal)
6 A ... 16 A (Characteristics B, C, D, K)
Input connection data
Connection method
Conductor cross section, solid
Conductor cross section, stranded
Conductor cross section AWG/kcmil
Stripping length
Screw thread
Tightening torque
Screw connection
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
24 ... 14
8 mm
M3
0.5 Nm ... 0.6 Nm
Output data
Nominal output voltage
Output current
Derating
Control deviation
12 V DC ±1%
4.6 A (-25°C ... 55°C)
55 °C ... 70 °C (2.5%/K)
< 1 % (change in load, static 10% ... 90%)
< 3 % (Dynamic load change 10% ... 90%, 10 Hz)
< 0.1 % (change in input voltage ±10%)
< 0.5 s (U
OUT
(10% ... 90%))
< 30 mV
PP
(with nominal values)
yes, with redundancy module
Yes
≤
25 V DC
< 35 V DC
Ascent time
Residual ripple
Connection in parallel
Connection in series
Protection against surge voltage on the output
Resistance to reverse feed
Output connection data
Connection method
Conductor cross section, solid
Conductor cross section, stranded
Conductor cross section AWG/kcmil
Stripping length
Screw thread
Tightening torque
Screw connection
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
24 ... 14
8 mm
M3
0.5 Nm ... 0.6 Nm
105550_en_00
PHOENIX CONTACT
4
UNO-PS/1AC/12DC/55W
Power consumption
Efficiency
Maximum power dissipation NO-Load
Power loss nominal load max.
> 89 % (for 230 V AC and nominal values)
< 0.3 W
<8W
General data
Insulation voltage input/output
MTBF
Housing material
Foot latch material
Dimensions W / H / D
Weight
4 kV AC (type test)
3 kV AC (routine test)
> 500000 h (According to EN 29500)
polycarbonate
Plastic POM
35 mm / 90 mm / 84 mm
0.2 kg
Security
Degree of protection
Protection class
SELV
IP20
II (in an enclosed control cabinet)
IEC 60950-1 (SELV) and EN 60204 (PELV)
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Vibration (operation)
Shock
Pollution degree
Climatic class
Inflammability class in acc. with UL 94 (housing)
-25 °C ... 70 °C (> 55° C derating)
-40 °C ... 85 °C
≤
95 % (at 25 °C, no condensation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
30 g in each direction, according to IEC 60068-2-27
2
3K3 (in acc. with EN 60721)
V0
Standards
Electrical Equipment for Machinery
Electrical safety (of information technology equipment - Safety - Part 1)
Electronic equipment for use in electrical power installations
SELV
Safe isolation
Protection against electric shock
Limitation of mains harmonic currents
Network version/undervoltage
Information technology equipment - Safety (CB Scheme)
EN 60204-1
IEC 60950-1/VDE 0805 (SELV)
EN 50178/VDE 0160 (PELV)
IEC 60950-1 (SELV) and EN 60204 (PELV)
DIN VDE 0100-410
DIN 57100-410
EN 61000-3-2
EN 61000-4-11
CB Scheme
Approvals
UL approvals
CSA
UL Listed UL 508
UL/C-UL Recognized UL 60950
CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
105550_en_00
PHOENIX CONTACT
5