Date:- 18 Mar, 2005
Data Sheet Issue:- 1
Ultra Rapid
Semiconductor Protection Fuse
American Square Body Type Fuses
American Long Blades
Voltage Ratings 900V to 1300V
Current Ratings 63A to 1800A
Sizes 0, 1, 2, 3
Key Features:
Exceptionally low I
2
t, power losses
Highly reliable low voltage indicator system
Non Magnetic construction
Conform to UL, CSA investigated, IEC, DIN and VDE standards
Increased technical performance gives higher ratings and a reduction in volume and weight
Microswitch system reference MS 7V 1-5
Data Sheet. 130USxDxxxxB
Issue 1
Page 1 of 8
March, 2005
WESTCODE
An
IXYS Company
American Square Body Fuse - Long Blades
Main Characteristics:
Size
Voltage
U
N
(V)
Ref:
130US0D0063B
130US0D0080B
130US0D0100B
130US0D0125B
Current
rating
I
N
(A)
63
80
100
125
160
200
250
280
315
350
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(kA
2
s)
0.21
0.47
0.83
1.3
2.55
4.7
9.6
14
20
28
Total Clearing
I
2
t @ U
N
(kA
2
s)
1.2
2.7
4.8
7.5
15
27
55
82
115
158
Watt Losses
0.8I
N
I
N
13
13.5
15
19
22.5
28
30.5
32
36
37.5
26
27
30
38
45
56
61
64
72
75
Tested
Interrupting
rating
0
1300V
130US0D0160B
130US0D0200B
130US0D0250B
130US0D0280B
130US0D0315B
100kA @1300V
1200V
120US0D0350B
150kA @ 1200V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch reference : MS 7V 1-5
Size
Voltage
U
N
(V)
Ref:
130US1D0160B
130US1D0200B
130US1D0250B
130US1D0280B
Current
rating
I
N
(A)
160
200
250
280
315
350
400
450
500
550
630
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(kA
2
s)
2.6
4.7
8.9
12
16
22
38
47
68
84
125
Total Clearing
I
2
t @ U
N
(kA
2
s)
15
27
51
68
92
127
220
270
390
485
725
Watt Losses
0.8I
N
I
N
23
27
30.5
35
38
40
40
47.5
50
56
60
46
54
61
70
76
80
80
95
100
112
120
Tested
Interrupting
rating
1300V
1
130US1D0315B
130US1D0350B
130US1D0400B
130US1D0450B
130US1D0500B
100kA @ 1300V
1200V
120US1D0550B
120US1D0630B
150kA @ 1200V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch reference : MS 7V 1-5
Data Sheet. 130USxDxxxxB
Issue 1
Page 2 of 8
March, 2005
WESTCODE
An
IXYS Company
American Square Body Fuse - Long Blades
Size
Voltage
U
N
(V)
Ref:
130US2D0280B
130US2D0315B
130US2D0350B
Current
rating
I
N
(A)
280
315
350
400
450
500
550
630
700
800
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(kA
2
s)
10
15
21
32.5
44
57
68
105
145
215
Total Clearing
I
2
t @ U
N
(kA
2
s)
60
87
120
190
255
330
390
610
815
1240
Watt Losses
0.8I
N
I
N
36
38
38
40
44.5
49
60
62.5
70
73
72
76
77
80
89
98
120
125
140
146
Tested
Interrupting
rating
1300V
2
130US2D0400B
130US2D0450B
130US2D0500B
130US2D0550B
100kA @1300V
1200V
1100V
120US2D0630B
110US2D0700B
110US2D0800B
150kA @ 1200V
150Ka @ 1100V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Micro switch reference : MS 7V 1-5
Size
Voltage
U
N
(V)
Ref:
130US3D0315B
130US3D0350B
130US3D0400B
Current
rating
I
N
(A)
315
350
400
450
500
550
630
700
800
900
1000
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(kA
2
s)
12
17
25
35.5
44
57
84
110
190
250
370
Total Clearing
I
2
t @ U
N
(kA
2
s)
68
100
145
205
255
330
485
640
1090
1440
2130
Watt Losses
0.8I
N
I
N
42
43
46.5
50
56
60
66
73
74
85
87
84
86
93
100
112
120
132
146
148
170
168
Tested
Interrupting
rating
1300V
3
130US3D0450B
130US3D0500B
130US3D0550B
130US3D0630B
130US3D0700B
100kA @ 1300V
1200V
1100V
900V
120US3D0800B
110US3D0900B
100US3D1000B
150kA @ 1200V
150kA @ 1100V
150kA @ 900V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Micro switch reference : MS 7V 1-5
Electrical Characteristics:
Times vs current characteristics
The curves shown on page 4 indicate the pre-arcing time for each rated current as a function of RMS
value of pre-arcing current I:
-
Tolerances on this current ± 8%
-
Beyond 30 sec, small overloads must be eliminated by another device.
-
Curve CC’ represents the maximum times taken by the associated device to clear small overloads; only its
horizontal line is represented.
Its oblique line must be plotted according to sketch in top right corner:
-
The intersection of the fuse and CC’ curves indicates the minimum breaking current I
pm
of the fuse.
Data Sheet. 130USxDxxxxB
Issue 1
Page 3 of 8
March, 2005
WESTCODE
Size 0
An
IXYS Company
American Square Body Fuse - Long Blades
Size 1
Size 2
Size 3
Data Sheet. 130USxDxxxxB
Issue 1
Page 4 of 8
March, 2005
WESTCODE
An
IXYS Company
American Square Body Fuse - Long Blades
Total clearing I²T:
The horizontal curves given below indicate the maximum values of total operating I
2
t (I
2
t
t
) as a function
of prospective current Ip @ 1000V or 850V, cosϕ = 0.15.
Oblique lines indicate the corresponding total operating time T
t
, with pre-arcing time in brackets.
Size 0
Size 1
Size 0
Size 1
Size 2 – Incorrect curve refer to factory
Size 3
Size 2
Size 3
Cut off Characteristics:
Data Sheet. 130USxDxxxxB
Issue 1
Page 5 of 8
March, 2005