The configurable frequency transducer is suitable for the connection of NAMUR proximity sensors as well as for
sensors with NPN and PNP outputs. Configurable via DIP switch and teach-in wheel. Spring-cage connection,
standard configuration.
The figure shows a version with a
screw connection
Product description
The configurable 3-way isolated frequency transducer is suitable for the connection of NAMUR proximity sensors (IEC 60947-5-6 and EN 50227) as well
as for sensors with NPN and PNP outputs that generate a frequency signal.
The measured values are converted into a linear current or voltage signal.
The device is configured via DIP switches. Alternatively, the frequency range can be configured with extended options via the teach-in wheel. The
measuring transducer supports fault monitoring.
Key commercial data
Packing unit
GTIN
Custom tariff number
Country of origin
85437090
GERMANY
1 PCE
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
Height
Depth
6.2 mm
93.1 mm
102.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
29.08.2013 Page 1 / 7
https://www.phoenixcontact.com/us/products/2902833
Frequency transducer - MINI MCR-SL-F-UI-SP-NC - 2902833
Technical data
Ambient conditions
Ambient temperature (storage/transport)
Degree of protection
-40 °C ... 85 °C
IP20
Input data
Frequency input
Configurable/programmable
Frequency measuring range
Available input sources
Frequency input
Yes
0.002 Hz ... 20 kHz (DIP switch)
NPN/PNP transistor outputs
NAMUR initiators
Floating relay contact (dry contact)
Max. input amplitude
A/D conversion time
30 V (incl. DC voltage)
10 ms (At f > 500 Hz)
Output data
Output name
Configurable/programmable
Voltage output signal
Voltage output
Yes
0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. output voltage
Max. output current
Load/output load voltage output
Load/output load current output
approx. 12.3 V
24.6 mA
≥ 10 kΩ
500 Ω (at 20 mA)
Power supply
Supply voltage range
Typical current consumption
Power consumption
9.6 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN,
Order No. 2869728) can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715))
< 28 mA (at I
OUT
= 20 mA, 24 V DC, load 500 Ω)
< 800 mW (at I
OUT
= 20 mA, 9.6 V DC, load 500 Ω)
Connection data
Connection method
Conductor cross section solid min.
Conductor cross section solid max.
Spring-cage conn.
0.2 mm²
2.5 mm²
29.08.2013 Page 2 / 7
https://www.phoenixcontact.com/us/products/2902833
Frequency transducer - MINI MCR-SL-F-UI-SP-NC - 2902833
Technical data
Connection data
Conductor cross section stranded min.
Conductor cross section stranded max.
Conductor cross section AWG/kcmil min.
Conductor cross section AWG/kcmil max
Stripping length
0.2 mm²
2.5 mm²
24
12
8 mm
General
Maximum temperature coefficient
Status display
Operating elements
Protective circuit
Electrical isolation
Surge voltage category
Pollution degree
Rated insulation voltage
Test voltage, input/output/supply
Electromagnetic compatibility
Noise emission
Noise immunity
Color
Housing material
Mounting position
Assembly instructions
Conformance
ATEX
UL, USA / Canada
GL
0.01 %/K
LED red
Press/slide button
Transient protection
Basic insulation according to EN 61010
II
2
50 V AC/DC
1.5 kV (50 Hz, 1 min.)
Conformance with EMC Directive 2004/108/EC
EN 61000-6-4
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
green
PBT
Any
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
CE-compliant
II 3 G Ex nA IIC T4 Gc X
508 listed
Class I, Div. 2, Groups A, B, C, D T5 applied for
GL applied for
EMC data
Name
Standards/regulations
Typical deviation from the measuring range final value
Name
Standards/regulations
Typical deviation from the measuring range final value
Name
Electromagnetic RF field
EN 61000-4-3
0.1 %
Fast transients (burst)
EN 61000-4-4
2%
Conducted interferences
29.08.2013 Page 3 / 7
https://www.phoenixcontact.com/us/products/2902833
Frequency transducer - MINI MCR-SL-F-UI-SP-NC - 2902833
Technical data
EMC data
Standards/regulations
Typical deviation from the measuring range final value
EN 61000-4-6
0.3 %
Classifications
ETIM
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC001446
EC001485
EC001485
UNSPSC
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
UNSPSC 6.01
UNSPSC 7.0901
39121008
39121008
39121008
30211506
39121008
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
27200206
27200206
27200206
27200206
27200206
27200206
27200206
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
Approvals submitted
29.08.2013 Page 4 / 7
https://www.phoenixcontact.com/us/products/2902833
Frequency transducer - MINI MCR-SL-F-UI-SP-NC - 2902833
Approvals
Approval details
UL Listed
cUL Listed
cULus Listed
Accessories
Accessories
Power terminal block - MINI MCR-SL-PTB-FM - 2902958
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the T-connector. The FM
power terminal block offers the additional function of monitoring in combination with the fault monitoring module. Screw
connection.
Power terminal block - MINI MCR-SL-PTB-FM-SP - 2902959
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the T-connector. The FM
power terminal block offers the additional function of monitoring in combination with the fault monitoring module. Spring-
cage connection.
Monitoring module - MINI MCR-SL-FM-RC-NC - 2902961
The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to monitor
the supply voltages. The error is reported via an N/O contact. Screw connection, standard configuration.
29.08.2013 Page 5 / 7