https://www.phoenixcontact.com/us/produkte/2817990
Type 2 surge protection connector - F-MS 12/ST - 2817990
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Surge protection plug type 2, with N-PE total current spark gap for base element.
Key commercial data
Packing unit
Minimum order quantity
Catalog page
GTIN
Custom tariff number
Country of origin
85363010
GERMANY
1
10
Page 36 (TT-2011)
Technical data
Standards
Housing material
Inflammability class according to UL 94
Color
Standards for air and creepage distances
Standards for air and creepage distances
Surge voltage category
Pollution degree
Degree of protection
Mounting type
Design
Number of positions
Ambient temperature (operation)
Arrester can be tested with CHECKMASTER from software
version:
Message: Surge protection fault
Direction of action
Width
PA
V0
black
EN 60664-1
EN 61643-11
III
2
IP20
On base element
DIN rail module, two-section, divisible
1
-40 °C ... 80 °C
From SW rev. 1.10
Optical
N-PE
17.7 mm
05.10.2012 Page 1 / 6
https://www.phoenixcontact.com/us/produkte/2817990
Type 2 surge protection connector - F-MS 12/ST - 2817990
Technical data
Standards
Height
Depth
Pitch unit
52.5 mm
55.5 mm
1 Div.
Protective circuit
IEC category
IEC category
EN type
Nominal voltage UN
Nominal DC sparkover voltage Uagn
Arrester rated voltage UC
Arrester rated voltage UC (N-PE)
UT (TOV-proof)
Nominal frequency fN
Nominal frequency fN
Ground conductor current IPE
Standby power consumption PC
Max. discharge surge current Imax (8/20) µs
Max. discharge surge current Imax (8/20) µs maximum (N-PE)
Nominal discharge surge current In (8/20) µs
Nominal discharge surge current In (8/20) µs (N-PE)
Lightning test current (10/350) µs, charge
Lightning test current (10/350) µs, peak value limp
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE)
Insulation resistance Riso:
Protection level Up
Protection level UP (N-PE)
Residual voltage
Residual voltage (N-PE)
Residual voltage (N-PE)
Residual voltage (N-PE)
Residual voltage (N-PE)
Response time
Response time (N-PE)
Follow current quenching capacity If (N-PE)
II
T2
T2
230 V AC
500 V ±20 %
260 V AC
260 V AC
1200 V AC (200 ms / N-PE)
50 Hz
60 Hz
≤ 1 µA
0.3 mVA
40 kA
40 kA
20 kA
20 kA
6 As
12 kA
≤ 1.5 kV
> 1 GΩ
≤ 1.5 kV
≤ 1.5 kV
≤ 150 V (at 5 kA)
≤ 150 V (at 5 kA)
≤ 400 V
≤ 250 V (at 10 kA)
≤ 100 V (at 3 kA)
≤ 100 ns
≤ 100 ns
100 A (260 V)
Connection, protective circuit
Connection type IN
Connection type OUT
FLASHTRAB/VALVETRAB plug-in system
FLASHTRAB/VALVETRAB plug-in system
Standards
Standards/regulations
Standards/regulations
IEC 61643-1 2005
EN 61643-11/A11 2007
05.10.2012 Page 2 / 6
https://www.phoenixcontact.com/us/produkte/2817990
Type 2 surge protection connector - F-MS 12/ST - 2817990
Classifications
eclass
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
27140201
27130801
27130801
27130801
27130805
27130805
etim
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000941
EC000941
EC000941
EC000941
unspsc
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30212010
39121610
39121610
39121610
39121620
Approvals
Approvals
Approvals
ÖVE / IECEE CB Scheme / UL Recognized / KEMA-KEUR / cUL Recognized / GOST / GL / CCA / ÖVE / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
ÖVE
IECEE CB Scheme
05.10.2012 Page 3 / 6
https://www.phoenixcontact.com/us/produkte/2817990
Type 2 surge protection connector - F-MS 12/ST - 2817990
Approvals
UL Recognized
KEMA-KEUR
cUL Recognized
GOST
GL
CCA
ÖVE
cULus Recognized
Accessories
Accessories
Marking
Zack marker strip - ZBN 18,LGS:ERDE - 2749589
Zack marker strip, Strip, white, Labeled, Horizontal: Grounding symbol, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
05.10.2012 Page 4 / 6
https://www.phoenixcontact.com/us/produkte/2817990
Type 2 surge protection connector - F-MS 12/ST - 2817990
Accessories
Zack marker strip - ZBN 18,LGS:L1-N,ERDE - 2749576
Zack marker strip, Strip, white, Labeled, Horizontal: L1, L2, L3, N, GND, Mounting type: Snap into tall
marker groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Marker pen - B-STIFT - 1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Additional products
Type 2 surge protection device - F-MS 12/FM - 2817974
Surge arrester type 2, consisting of base element with remote indicator contact and protective plug with N-
PE total current spark gap for mounting on NS 35/7.5, housing width: 17.5 mm (1 Div.)
Type 2 surge protection device - F-MS 12 - 2817987
Surge arrester type 2, consisting of base element and protective plug with N-PE total current spark gap for
mounting on NS 35/7.5, housing width: 17.5 mm (1 Div.)
05.10.2012 Page 5 / 6