Relay Output Modules
Relay Output Module Compatible with
MULTIPLE I/O TERMINAL
8- and 16-point relay output models are available.
Dimensions of 8-point model:
160 x 60 x 65 (W x H x D)
Dimensions of 16-point model:
160 x 60 x 65 (W x H x D)
DIN track mounting.
GT1-ROS16/ROP08
Ordering Information
I/O
classification
Relay output
Relay model
G6D-1A (24 VDC)
G2R-1-SN (24 VDC)
Note:
16
8
I/O points
Terminal
M3 terminal
block
Power supply
voltage
24 VDC
I/O specification
2 A/SPST-NO
5 A/SPST-NO
Model
GT1-ROS16
GT1-ROP08
A communications cable, GCN1--004, is included with each module.
Specifications
Characteristics
I/O power supply
voltage
Current consumption
(See note.)
Connecting Units
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Mounting method
Mounting strength
Terminal strength
Screw tightening
torque
Ambient temperature
Ambient humidity
Note:
24 VDC +10%/--15%
I/O Module interface
GT1-ROP08
GT1-ROS16
8
500 VAC (between isolated circuits)
±1,500
V (p-p) for 10 minutes with a pulse width of 0.1 to 1
ms
10 to 55 Hz, 1.0-mm double amplitude or 70 m/s
2
200 m/s
2
35-mm DIN track mounting
No damage when 100 N pull load was applied in all directions
No damage when 100 N pull load was applied
0.3 to 0.5 N
S
m
Operating:
Storage:
Operating:
--10°C to 55°C (with no icing or condensation)
--25°C to 65°C (with no icing or condensation)
25% to 85%
40 mA max.
50 mA max.
GT1-ROP08
GT1-ROS16
I/O power supply
350 mA max.
250 mA max.
The above current consumption is a value with all the points turned ON including the current consumption of the relay coils.
67
GT1-ROS16/ROP08
Relay Output Specifications
Item
Maximum contact current
Minimum applicable load (reference values)
Electrical life expectancy
Mechanical life expectancy
2A
5 VDC, 10 mA
G6D-1A
5A
GT1-ROS16/ROP08
G2R-1-SN
5 VDC, 100 mA
100,000 operations min. with switching frequency of 1,800 operations per hour (at
ambient temperature of 23_C with rated load)
20,000,000 operations min. with switching frequency of 18,000 operations per hour
(at ambient temperature of 23_C with rated load)
Nomenclature
·
GT1-ROS16
Output Indicators
Relay removal lever
Output relay
Connector 1 for I/O
Module interface
Connector 2 for I/O Module interface
I/O power supply
terminals
(beneath cover)
External connections
Indicator (see below)
DIN track mounting hook
Output Terminals (beneath cover)
Power
supply
Power
supply
Indicators
Indicator
TS
Lit
Lit
Not lit
Display
Green
Red
---
Color
The Module is normal.
The I/O Module interface has an error.
No power is supplied to the Module or the Module is being
initialized.
Relay removal lever
Output relay
Meaning
·
GT1-ROP08
Connector 1 for I/O
Module interface
Connector 2 for I/O Module interface
External connections
I/O power
supply
terminals
Power
supply
Power
supply
Indicator (see note)
Output terminals
Note:
The indicators for the GT1-ROP08 are the same as for the GT1-ROS16.
68
GT1-ROS16/ROP08
GT1-ROS16/ROP08
Operation
Internal Circuit Configuration
GT1-ROS16
GT1-ROP08
Voltage
step-down
Photocoupler
G6D-1A
Internal circuit
0, 1, etc.
C0, C1, etc.
Photocoupler
Internal circuit
Photocoupler
G6D-1A
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
·
GT1-ROS16
·
GT1-ROP08
65 max.
160 max.
68 max.
(81.2)
Installation
Wiring
GT1-ROS16
GT1-ROP08
24 VDC
I/O power
supply
AC (DC is also possible.)
Separate common is also I/O power
possible.
supply
Load
Load
AC (DC is also possible.)
Separate common is also
possible.
Load
Load
69
GT1-ROS16/ROP08
GT1-ROS16/ROP08
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
R
One East Commerce Drive
Schaumburg, IL 60173
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
1-800-55-OMRON
Cat. No.
P10FAX1A
6/00
Specifications subject to change without notice.
416-286-6465
885 Milner Avenue
Scarborough, Ontario M1B 5V8
Printed in U.S.A.