<= 0.5 % within the supply voltage range (0.85...1.1 Un)
<= 0.06 % per degree centigrade depending permissible ambient air temperature
10 P
<= 0.5 % within the supply voltage range (0.85...1.1 Un)
<= 0.07 % per degree centigrade depending on temperature
5...30 % adjustable of current threshold setting
CE : EMC 89/336/EEC
CE : LVD 73/23/EEC
III conforming to IEC 60664-1
500 V conforming to IEC
> 0.1 Uc
Any position without derating
Screw terminals 2 x 2.5 mm², flexible cable without cable end
Screw terminals 2 x 1.5 mm², flexible cable with cable end
0.6...1.1 N.m
30000000 cycles
8A
Permissible continuous overload
Permissible non repetitive overload
Setting accuracy of the switching threshold
Switching threshold drift
Setting accuracy of time delay
Time delay drift
Hysteresis
Marking
Overvoltage category
[Ui] rated insulation voltage
Supply disconnection value
Operating position
Connections - terminals
Tightening torque
Mechanical durability
[Ith] conventional free air thermal current
Aug 16, 2014
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
[Ie] rated operational current
0.3 A at 115 V DC-13 70 °C conforming to VDE 0660
0.3 A at 115 V DC-13 70 °C conforming to IEC 60947-5-1/1991
0.1 A at 250 V DC-13 70 °C conforming to VDE 0660
0.1 A at 250 V DC-13 70 °C conforming to IEC 60947-5-1/1991
3 A at 250 V AC-15 70 °C conforming to VDE 0660
3 A at 250 V AC-15 70 °C conforming to IEC 60947-5-1/1991
3 A at 24 V AC-15 70 °C conforming to VDE 0660
3 A at 24 V AC-15 70 °C conforming to IEC 60947-5-1/1991
3 A at 115 V AC-15 70 °C conforming to VDE 0660
3 A at 115 V AC-15 70 °C conforming to IEC 60947-5-1/1991
2 A at 24 V DC-13 70 °C conforming to VDE 0660
2 A at 24 V DC-13 70 °C conforming to IEC 60947-5-1/1991