SF 2010
SF 2012
2 & 6 AMP STANDARD & SURGE PROT’
db
db
GENERAL PURPOSE IEC INLET FILTER
WITH
INTEGRAL SINGLE OR DOUBLE FUSEHOLDER.
2 & 6 AMP MEDICAL VERSION
90
90
80
70
60
50
40
30
20
10
.1
.15
.4
1
4
10
Frequency MHz
40
100
500
SYMMETRIC
80
70
60
50
40
SYMMETRIC
ASYMMETRIC
30
20
10
.1
.15
.4
1
ASYMMETRIC
4
10
Frequency MHz
40
100
500
2 & 6 AMP EARTH LINE CHOKE &
EARTH`LINE CHOKE SURGE PROTECTED
db
90
80
70
60
50
40
30
20
10
.1
.15
.4
1
4
10
Frequency MHz
40
100
500
SYMMETRIC
ASYMMETRIC
SF 2010
SF 2012
Rated
Leakage Current
Current A @ 250V 50Hz
Inductance
L1 mH L2
µH
Connections
Input
Output
Resistor
Value MΩ
Number
of Fuses
Approvals
Standard Version
SF 2010-2/01
2
0.2mA
SF 2012-2/01
2
0.2mA
SF 2010-6/01
6
0.2mA
SF 2012-6/01
6
0.2mA
Medical Version
SF 2010M-2/01
2
5µA
SF 2012M-2/01
2
5µA
SF 2010M-6/01
6
5µA
SF 2012M-6/01
6
5µA
Surge Protected Version
(IEC 950 not applicable)
SF 2010Z-2/01
2
0.2mA
SF 2012Z-2/01
2
0.2mA
SF 2010Z-6/01
6
0.2mA
SF 2012Z-6/01
6
0.2mA
2.0
2.0
0.5
0.5
2.0
2.0
0.5
0.5
2.0
2.0
0.5
0.5
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
IEC 320
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
6.3 x 0.8 Faston
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
Earth Line Choke Version
SF 2010E-2/01
2
0.2mA
2.0
300
SF 2012E-2/01
2
0.2mA
2.0
300
SF 2010E-6/01
6
0.2mA
0.5
300
SF 2012E-6/01
6
0.2mA
0.5
300
Earth Line Choke, Surge Protected
(IEC 950 not applicable)
SF 2010EZ-2/01
2
0.2mA
2.0
300
SF 2012EZ-2/01
2
0.2mA
2.0
300
SF 2010EZ-6/01
6
0.2mA
0.5
300
SF 2012EZ-6/01
6
0.2mA
0.5
300
Temperature Range:
-25
0
C to +85
0
C
Operating Voltage:
250Vac
Operating Frequency:
0 to 400Hz
Test Voltage:
L+N to ground, 2700Vdc,
2 seconds
Varistor
Zinc oxide type; energy absorption 21
Joules (current impulse defined in
IEC 60-2 Section 6). Varistor voltage:
430Vdc(measured at 1mA); clamping
voltage 710V at 10A
s
Approved
❏
Submitted for Approval
IEC 950
(EN 60950) Applications
Twin fused version only
Continued on next page
18
FOR MORE INFORMATION PLEASE PHONE
01638 665161
SF 2010
SF 2012
Continued from previous page
DIMENSIONS
All dimensions are nominal and in mm
46
41
36
PANEL
CUT OUT
36
33.2
ø3.6
R3.0
29.0
36
57
33.5
FRONT AND REAR MOUNTING
28.7
CIRCUIT DIAGRAMS
SF 2010 = 1 Fuse 5 x 20mm
SF 2012 = 2 Fuses 5 x 20mm
Standard Version
L1
N
LINE
E
L
0.015µF (X2)
Medical Version (Suffix ‘M’)
N
R
LOAD
LINE
E
L
L1
2x2,200pF (Y)
L1
N
E
L
0.015µF (X2)
N
R
E
L
L1
0.015µF (X2)
LOAD
LOAD
Surge Protected Version (Suffix ‘Z’)
L1
N
LINE
E
L
0.015µF (X2)
Earth Line Version (Suffix ‘E’)
L1
N
N
LOAD
LINE
E
L
0.015µF (X2)
N
R
E
L
L1
2x2,200pF (Y)
R
E
L
L1
2x2,200pF (Y)
Earth Line Choke, Surge Protected Version (Suffix ‘EZ’)
L1
N
LINE
E
L
0.015µF (X2)
L2
R
N
E
L
L1
2x2,200pF (Y)
LOAD
L2
FOR MORE INFORMATION PLEASE PHONE
01638 665161
19