PRODUCT INFORMATION
ÖLFLEX® CONTROL TM CY
ÖLFLEX® Control Cable PVC Screened 0.6/1kV UL TC-ER WTTC AWM600V OIL RES CSA AWM
ÖLFLEX® CONTROL TM CY: UL MTW TC-ER WTTC AWM 600V OIL RES II WET CSA AWM I/II A/B FT4, Screened PVC
Power Control Cable 0.6/1 kV, Tray Exposed Run, Wind Turbine
Info
Torsion resistant for drip loops
Wide application range (NFPA 70/NEC)/ compliance with NFPA 79 for industrial machinery
EMC/Screened
Torsion-resistant
Interference signals
Oil-resistant
Mechanical resistance
Flame-retardant
Cold-resistant
Benefits
Wide application range due to multiple certifications
Cost-saving, easy installation due to omission of closed raceways (suitable for open wiring)
Last Update (19.11.2016)
©2016 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.
PN 0456 / 02_03.16
PRODUCT INFORMATION
ÖLFLEX® CONTROL TM CY
Application range
Industrial machinery; plant engineering
Machine tools compliant with UL MTW (Machine Tool Wiring)
TC-ER (Tray Cable Exposed Run) approval for open wiring between cable tray and industrial machines/plants acc. to NEC
336.10(7)
Wind turbines: USA Wind Turbine Tray Cable (WTTC)
According to NEC/ NFPA 70 (2014), ARTICLE 501, for hazardous Class I, Division 2 locations determined in NEC ARTICLE
500
Product features
Flame-retardant according to CSA FT4
UL Vertical-Tray Flame Test
Oil-resistant according to UL OIL RES I & II
Water-resistant, UL 75°C wet rating
High degree of screening
low transfer impedance
(max. 250 Ω/km at 30 MHz)
Suitable for torsional applications which are typical for the loop in wind turbine generators (WTG)
Norm references / Approvals
Multi-standard cables have conductor strands with nominal sizes in mm²
or
AWG/kcmil. The master size is mentioned in the
table below, while the equivalent size of the other system can be found in the Appendix T16 of this catalogue. For this related
secondary size the cross-section of the conductor mostly works out to be greater than the
specified nominal value.
UL cable type certifications for US use:
- (UL) TC-ER per UL 1277 [UL file no.: E171371];
- (UL) MTW per UL 1063 [UL file no.: E155920];
- (UL) WTTC per UL 2277 [UL file no.: E323700];
- UL AWM styles 2587 & 21098 (Oil) per UL 758 [UL file no.: E100338].
Attributes:
- UL OIL RES I/ II;
- 75°C Wet, 90°C Dry;
- Technically sunlight resistant (not SUN. RES. certified);
- Direct burial;
- Bus Drop Cable (2.5 mm²/ 14 AWG and larger, 3-core and 4-core versions only);
- NFPA 79 2015 Edition;
- FT4 flame retardance.
NEC (NFPA 70):
- Class 1, Division 2 per NEC Article 501.
UL and CSA cable type certifications for use in Canada:
- c(UL) CIC/ TC FT4 [UL file no.: E171371];
- CSA AWM I/II A/B FT1;
- CSA C22.2 210.2.
Additionally:
- Impact and Crush test per UL 1277 (excluding 0.75 mm²)
Product Make-up
Fine-wire strand made of bare copper wires
Insulation: PVC with nylon sheath (PA skin)
Aluminum-coated foil
Tinned-copper braiding
Outer jacket: Specially Formulated Thermoplastic Polymer
Color of the outer jacket: Gray
Last Update (19.11.2016)
©2016 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.
PN 0456 / 02_03.16
PRODUCT INFORMATION
ÖLFLEX® CONTROL TM CY
Technical Data
Classification:
ETIM 5.0 Class-ID: EC000104
ETIM 5.0 Class-Description: Control cable
Black with white numbers
Fine-wire, bare copper strand
TW-0 & TW-2, refer to Appendix T0
Static/Occ. moved: 5/20 x OD*
UL/CSA: 600 V (TC, MTW, CIC), WTTC 1000 V
UL AWM: 600 V
CSA AWM: 1000 V
IEC U
0
/U: 600/1000 V
2000 V
G = with GN-YE protective conductor
X = without protective conductor
-40°C (static)/ -25°C (occ. moved) to +90°C (AWM: +105°C)
Core identification code:
Conductor stranding:
Torsion movement in WTG:
Minimum bending radius:
Nominal voltage:
Test voltage:
Protective conductor:
Temperature range:
Note
Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon
request.
Copper price basis: EUR 150/100 kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related
surcharges.
Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum
Please specify the preferred type of packaging (e.g. 1 x 610 m drum or 8 x 76 m coils).
Photographs are not to scale and do not represent detailed images of the respective products.
* Prices are net prices without VAT and surcharges. Sale to business customers.
*OD = Outer diameter
Last Update (19.11.2016)
©2016 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.
PN 0456 / 02_03.16
Powered by TCPDF (www.tcpdf.org)
Powered by TCPDF (www.tcpdf.org)
ÖLFLEX® CONTROL TM CY
Article number
ÖLFLEX® CONTROL TM CY
281803CY
281804CY
281805CY
281807CY
281812CY
281818CY
281825CY
281603CY
281604CY
281605CY
281607CY
281612CY
281618CY
281403CY
281404CY
281405CY
281407CY
281204CY
281205CY
281004CY
280804CY
Number of cores and mm² per
conductor
3G1
4G1
5G1
7G1
12 G 1
18 G 1
25 G 1
3 G 1.5
4 G 1.5
5 G 1.5
7 G 1.5
12 G 1.5
18 G 1.5
3 G 2.5
4 G 2.5
5 G 2.5
7 G 2.5
4G4
5G4
4G6
4 G 10
Outer diameter (mm)
Copper index (kg/km)
Weight (kg/km)
Last Update (19.11.2016)
©2016 Lapp Group - Technical changes reserved
Product Management www.lappkabel.de
You can find the current technical data in the corresponding data sheet.
PN 0456 / 02_03.16
8.1
8.6
9.3
10
12.8
15.5
17.5
8.8
9.4
10.2
11.1
15
17.2
9.7
10.4
11.5
12.4
12.3
14.2
15.3
18.5
49.5
60.2
81.4
101.1
161.4
228.2
326.4
65
81.9
99.1
140.4
225.2
321.7
105.7
135.6
160.3
213
198.5
242.7
284236
458.4
119
137
149
193
330
438
574
144
173
189
246
426
552
180
223
268
327
315
388
552
857
PRODUCT INFORMATION