POLYSNAP
®
POWER INLET MODULES
C14 IEC Fused Inlet - Vertical
VERTICAL MODULE ARRANGEMENT
Fused Inlet with 2.8mm or
6.3mm tags
Single Pole Switch Variations
Filtered Inlet Option
Options of I/O marked
switches
BZV01/Z0000/01
IEC CONNECTORS
How to Order
BZV xx / xxxxx / xx
Type of Inlet / Outlet
Single Fused C14 Power Inlet (cold condition),
6.3 or 2.8mm tabs:
01
= PF0011/63
02
= PF0011/28
Twin Fused C14 Power Inlet (cold condition),
6.3 or 2.8mm tabs:
15
= PF0033/63
16
= PF0033/28
Filtered or Non Filtered Inlet
Z0000 = Non Filtered
Axxxx = Standard
Bxxxx = Medical
Combination of Other Components
Single Pole Switch:
01
= S.P Switch
.
Single Pole Neon Switch:
Cxxxx = High Performance Standard
(Single Fuse Version only)
02
= S.P Red Neon Switch
.
08
= S.P Green Neon Switch
.
Neon Indicator:
03
= Red Neon Indicator
Single Pole High Inrush Switch:
46
= S.P High Inrush Switch
.
For Filtered inlet use 6th to 9th characters from filter
ordering code see pages 97-100.
Single Pole Switch Marked I/O:
69
= S.P Switch (I/O)
.
E.g. BZV01/A0620/01
Single Pole Neon Switch Marked (I/O):
71
= S.P Red Neon Switch (I/O)
.
74
= S.P Green Neon Switch (I/O)
.
Single Pole High Inrush Switch Marked (I/O):
98
= S.P High Inrush Switch (I/O)
.
Note: For technical details of individual components please see page 74
76
www.bulgin.co.uk
POLYSNAP
®
POWER INLET MODULES
C14 IEC Fused Inlet - Vertical
VERTICAL MODULE ARRANGEMENT
Fused Inlet with 2.8mm or
6.3mm tags
Double Pole Switch or
Indicator Variations
Filtered Inlet Option
Options of I/O marked
switches
BZV01/Z0000/10
Type of Inlet / Outlet
Single Fused C14 Power Inlet (cold condition),
6.3 or 2.8mm tabs:
01
= PF0011/63
02
= PF0011/28
Twin Fused C14 Power Inlet (cold condition),
6.3 or 2.8mm tabs:
15
= PF0033/63
16
= PF0033/28
Filtered or Non Filtered Inlet
Z0000 = Non Filtered
Axxxx = Standard
Bxxxx = Medical
Combination of Other Components
Neon Indicator:
D3
= Red Neon Indicator
Double Pole Switch:
Cxxxx = High Performance Standard
(Single Fuse Version only)
10
= D.P Switch
.
Double Pole Neon Switch:
11
= D.P Red Neon Switch
.
12
= D.P Green Neon Switch
.
Double Pole High Inrush Switch:
13
= D.P High Inrush Switch
.
For Filtered inlet use 6th to 9th characters from filter
ordering code see pages 97-100.
E.g. BZV01/A0620/10
Double Pole Switch Marked I/O:
70
= D.P Switch (I/O)
.
Double Pole Neon Switch Marked (I/O):
76
= D.P Red Neon Switch (I/O)
.
77
= D.P Green Neon Switch (I/O)
.
Double Pole High Inrush Switch Marked
(I/O):
78
= D.P High Inrush Switch (I/O)
.
B1
= D.P High Inrush Green Neon Switch
.
(I/O)
Note: For technical details of individual components please see page 74
www.bulgin.co.uk
77
IEC CONNECTORS
How to Order
BZV xx / xxxxx / xx
POLYSNAP
®
POWER INLET MODULES
C14 and C16 IEC Inlet - Vertical
VERTICAL MODULE ARRANGEMENT
Inlet with 2.8mm or 6.3mm
tags
Single Pole Switch or Neon
Indicator Variations
Filtered Inlet Option
Options of I/O marked
switches
Non Fused
BZV03/Z0000/02
IEC CONNECTORS
How to Order
BZV xx / xxxxx / xx
Type of Inlet / Outlet
Filtered or Non Filtered Inlet
Combination of Other Components
C14 Power Inlet (cold condition), 6.3 or 2.8mm
tabs:
03
= PX0575/63
04
= PX0575/28
C16 Power Inlet (hot condition), 6.3 or 2.8mm
tabs:
05
= PX0595/63
06
= PX0595/28
Z0000 = Non Filtered
Axxxx = Standard
Bxxxx = Medical
Single Pole Switch:
01
= S.P Switch
.
Single Pole Neon Switch:
02
= S.P Red Neon Switch
.
08
= S.P Green Neon Switch
.
Neon Indicator:
03
= Red Neon Indicator
Please note type 05 and 06 are not available in
filtered version
For Filtered inlet use 6th to 9th characters from
filter ordering code see pages 95-96.
E.g. BZV03/A0120/02
Single Pole High Inrush Switch:
46
= S.P High Inrush Switch
.
Single Pole Switch Marked I/O:
69
= S.P Switch (I/O)
.
Single Pole Neon Switch Marked (I/O):
71
= S.P Red Neon Switch (I/O)
.
74
= S.P Green Neon Switch (I/O)
.
Single Pole High Inrush Switch Marked
(I/O):
98
= S.P High Inrush Switch (I/O)
.
Note: For technical details of individual components please see page 74
78
www.bulgin.co.uk
POLYSNAP
®
POWER INLET MODULES
C14 and C16 IEC Inlet with Circuit Breaker
VERTICAL MODULE ARRANGEMENT
Inlet with 2.8mm or 6.3mm
tags
Single pole circuit breaker
Illuminated (red or green)
and non-illuminated rocker
switch
125Vac and 250Vac Neons
BZV03/Z0000/C1/T
6.3mm tabs on Circuit
Breaker
Panel Thickness: 1.0, 1.5, 2.0, 3.0mm.
Type of Inlet
Filtered or Non Filtered
Switch Button
Trip Current
C14 power inlet (cold condition), 6.3 or
2.8mm tabs:
03
= PX0575/63
04
= PX0575/28
C16 power inlet (hot condition), 6.3 or 2.8mm
tabs:
05
= PX0595/63
06
= PX0595/28
Z0000 = Non Filtered
Axxxx = Standard
C1 = non-illuminated
C2 = red neon (125Vac)
C3 = green neon (125Vac)
C4 = red neon (250Vac)
C5 = green neon (250Vac)
Q = 5.0A
T = 8.0A
U = 10.0A
X = 15.0A
Please note type 05 and 06 are not available in
filtered version
Note: For technical details of individual components also see page 74
% 1000
Trip Curves
Load Current as a Percent
of Circuit Breaker Rating
900
800
700
600
500
400
300
200
135
100
0
0.1
Capacity Correction Factors for Ambient Temperatures
Current Rating 5 to 15A
Temperature ˚C
Correction Factor
-10
.90
-20
.95
-25
1.00
-30
1.10
-40
1.32
-50
1.61
-60
2.15
1
10
100
1000
10000
Circuit Breaker Approvals:
Time in Seconds
Trip Curves are Specified at 25˚C/77˚F
www.bulgin.co.uk
79
IEC CONNECTORS
How to Order
BZV xx / Zxxxx / xx x
POLYSNAP
®
POWER INLET MODULES
C14 and C16 IEC Inlet - Vertical
VERTICAL MODULE ARRANGEMENT
Inlet with 2.8mm or 6.3mm
tags
Double Pole Switch/
Fuseholder/Indicator/
Voltage Selectors/
Blanking Plate
Filtered Inlet Option
BZV03/Z0000/07
Options of I/O marked
switches
How to Order
IEC CONNECTORS
BZV xx / xxxxx / xx
Type of Inlet / Outlet
C14 Power Inlet (cold
condition), 6.3 or 2.8mm
tabs:
03
= PX0575/63
04
= PX0575/28
C16 Power Inlet (hot
condition), 6.3 or 2.8mm
tabs:
05
= PX0595/63
06
= PX0595/28
Filtered or Non Filtered Inlet
Z0000 = Non Filtered
Axxxx = Standard
Bxxxx = Medical
Combination of Other Components
Twin Fuseholder and Double Pole
Switch:
05
= 2 x FX0359 + D.P Switch
.
Twin Fuseholder and Double Pole Neon
Switch:
06
= 2 x FX0359 + D.P Red Neon
.
Switch
09
= 2 x FX0359 + D.P Green Neon
.
Switch
19
= 2 x FX0359 + D.P Red Neon
.
Switch 125V
Twin Fuseholder and Neon Indicator:
07
= 2 x FX0359 + Red Neon
Indicator
Voltage Selector, Fuseholder and Double
Pole Switch:
15
= 1 x VS0001 + 1 x FX0359 +
Double Pole switch
Voltage Selector, Fuseholder and Double
Pole Neon Switch:
16
= 1 x VS0001 + 1 x FX0359 + D.P
.
Red Neon Switch
18
= 1 x VS0001 + 1 x FX0359 + D.P
.
Green Neon Switch
Voltage Selector, Fuseholder and Neon
Indicator:
17
= 1 x VS0001 + 1 x FX0359 + Red
Neon Indicator
Twin Fuseholder and Double Pole High
Inrush Switch:
20
= 2 x FX0359 + D.P High Inrush
.
Switch
Twin Fuseholder and Double Pole High
Inrush Neon Switch:
21
= 2 x FX0359 + 1 x D.P High
.
Inrush Green Neon Switch
22
= 2 x FX0359 + 1 x D.P High
.
Inrush Red Neon Switch
Voltage Selector, Neon Indicator and
Double Pole Switch
25
= 1 x VS0001 + 1 x
DX0928/110V/Red + D.P Switch
.
26
= 1 x VS0001 + 1 x
DX0928/110V/Green + D.P Switch
.
27
= 1 x VS0001 + 1 x
DX0928/250V/Red + D.P Switch
.
28
= 1 x VS0001 + 1 x
DX0928/250V/Green + D.P Switch
.
Voltage Selector, Neon Indicator and
Double Pole High Inrush Switch:
29
= 1 x VS0001 + 1 x
DX0928/250V/Red + D.P High Inrush
.
Switch
30
= 1 x VS0001 + 1 x
DX0928/250V/Green + D.P High
.
Inrush Switch
Fuseholder, Neon Indicator and Double
Pole Switch
31
= 1 x FX0359 + 1 x
DX0928/110V/Red + D.P Switch
.
32
= 1 x FX0359 + 1 x
DX0928/110V/Green + D.P Switch
.
33
= 1 x FX0359 + 1 x
DX0928/250V/Red + D.P Switch
.
34
= 1 x Fx0359 + 1 x
DX0928/250V/Green + D.P Switch
.
Fuseholder, Neon Indicator and Double
Pole High Inrush Switch:
35
= 1 x FX0359 + 1 x
DX0928/250V/Red + D.P High Inrush
.
Switch
36
= 1 x FX0359 + 1 x
DX0928/250V/Green + D.P High
.
Inrush Switch
Fuseholder, Blanking Plate and Double
Pole High Inrush Neon Switch:
47
= 1 x FX0359 + 1 x Blanking Plate
(Right) + D.P High Inrush Green Neon
.
Switch
Fuseholder, Blanking Plate and Double
Pole Switch:
48
= 1 x FX0359 + 1 x Blanking Plate
(Right) + D.P Switch
.
Please note type 05 and
06 are not available in
filtered version
For Filtered inlet use 6th to 9th
characters from filter ordering code
see pages 95-96.
E.g. BZV03/A0120/07