GE Energy
Data Sheet
CAR1212FP series rectifier
Input: 85Vac to 264Vac; Output: 12Vdc @ 1250W; 5 Vdc @ 0.5A
Features
Universal input with PFC
Constant power characteristic
3 front panel LEDs:
Remote ON/OFF control of the 12Vdc output
Remote sense on the 12Vdc output
No minimum load requirements
Active load sharing (single wire)
Hot Plug-ability
Efficiency: typically 89% at high line
85% at low line
Standby : 5Vdc
Auto recoverable OC & OT protection
Operating temperature: -10 - 70C (de-rated above
50C)
Digital status & control: I
2
C serial bus
EN/IEC/UL60950-1 2
nd
edition; UL, CSA and VDE
EMI: class A FCC docket 20780 part 15, EN55022
Meets EN6100 immunity and transient standards
Shock & vibration: NEBS GR-63-CORE, level 3
Applications
12Vdc distributed power architectures
Datacom and Telecom applications
Mid to high-end Servers
Enterprise Networking
Network Attached Storage
Telecom Access Nodes
Routers/Switches
Broadband Switches
ATE Equipment
Description
The CAR1212FP series of rectifiers provide highly efficient isolated power from world-wide commercial AC mains.
Offered in the industry standard compact 1U form factor, these rectifiers complement the CAR1212DC converter line,
providing comprehensive solutions for systems connected either to commercial ac mains or 48/60Vdc power plants.
This plug and play approach, between AC and DC input units, has significant advantages since systems can be readily
reconfigured by simply replacing the power supply.
The high-density, front-to-back airflow is designed for minimal space utilization and is highly expandable for future
growth.
July 20, 2012
©2012 General Electric Company. All rights reserved.
GE Energy
CAR1212FP series rectifier
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet.
Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1250W; 5 Vdc @ 0.5A
Parameter
Input Voltage: Continuous
Operating Ambient Temperature
Storage Temperature
I/O Isolation voltage to Frame (100% factory Hi-Pot tested)
Device
Symbol
VIN
TA
Tstg
Min
0
-10
-40
Max
264
70
1
85
1500
Unit
V
ac
°C
°C
V
ac
All
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter
Operational Range
Frequency Range
Main Output Turn_OFF
Maximum Input Current
(V
O
= V
O, set
, I
O
=I
O, max
)
Cold Start Inrush Current
(Excluding x-caps, 25C, <10ms, per ETSI 300-132)
Efficiency
(T
amb
=25C, V
in
= 230V, V
out
= 12V, I
O, max
)
Power Factor
Holdup time
2
(Vout= 12V
dc
, Tamb 25C)
Ride through
Leakage Current
Isolation
high line
low line
(Vin=230Vac, I
O
=I
O, max
)
V
in
= 220V
ac,
1250W
V
in
= 100V
ac,
1000W
(Vin= 250Vac, Fin = 60Hz)
Input/Output
Input/Frame
Output/Frame
All
V
IN
= 100V
ac
V
IN
= 180V
ac
(ETSI 300-132-1 recommendation)
Device
Symbol
V
IN
F
IN
V
IN
I
IN
I
IN
PF
T
T
I
IN
Min
85
47
Typ
110/230
50/60
Max
264
63
80
12
8.1
35
Unit
V
ac
Hz
V
ac
A
ac
A
peak
%
89
85
0.99
16.7
20
10
3
3000
1500
50
ms
ms
mArms
V
ac
V
ac
V
dc
12V
dc
MAIN OUTPUT
Parameter
Output Power
V
in
≥
180V
ac
V
in
≤
175V
ac
V
in
≤
90V
ac
All
V
out
Device
Symbol
W
Min
-
-
11.9
-3
Typ
-
-
12.00
Max
1250
1000
900
12.1
+3
120
+3
2
Unit
W
V
dc
%
mV
p-p
%
sec
Set point
Overall regulation (load, temperature, aging)
Ripple and noise
3
Turn-ON overshoot
Turn-ON delay
T
Derated above 50C at 2.5%/C
12V output can decay down to 10.8V
3
Measured across a 10µf electrolytic and a 0.1µf ceramic capacitors in parallel. 20MHz bandwidth
1
2
July 20, 2012
©2012 General Electric Company. All rights reserved.
Page 2
GE Energy
CAR1212FP series rectifier
12V
dc
MAIN OUTPUT (continued)
Parameter
Remote ON/OFF delay time
Turn-ON rise time (10 – 90% of V
out
)
Transient response 50% step [10%-60%, 50% - 100%]
(di/dt – 1A/µs, recovery 300µs)
Programmable range (hardware & software)
Overvoltage protection, latched
(recovery by cycling OFF/ON via hardware or software)
Output current
Current limit, Hiccup (programmable level)
Active current share
All
V
in
= HL
V
in
= LL
HL / LL
V
out
-5
11.4
14.5
0
I
out
110
-5
15
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1250W; 5 Vdc @ 0.5A
Device
Symbol
Min
Typ
Max
20
50
+5
12.6
15.5
104
83.5
135
+5
Unit
ms
ms
%V
out
V
dc
V
dc
A
dc
% of FL
% of FL
AUXILIARY OUTPUT
Parameter
Set point
Overall regulation (load, temperature, aging)
Ripple and noise
Output current
Isolation
Output/Frame
Device
All
All
All
All
All
Symbol
V
out
V
out
I
out
Min
-5
0
50
Typ
5.0
Max
+5
50
0.5
Unit
V
dc
%
mVp-p
A
dc
V
dc
Environmental, Reliability
Parameter
Ambient Temperature
Operating
Altitude Operating
Power Derating
Storage
Altitude non-operating
Acoustic noise
Over Temperature Protection
Humidity
Operating
Storage
30
10
110/95
95
95
6
4
320,000
100,000
-10
50
1524/5k
2.5
2.0
85
8200/30k
45
°C
m / ft
%/°C
C/1000
ft
°C
m / ft
dbA
°C
%
Grms
Zone
hrs
Full load, 25C
Shutdown / restart
Relative humidity, non-condensing
NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed
and tested to meet NEBS specifications.
Full load, 25C per Bellcore RPP
Full load, 50C per Bellcore RPP
Air inlet from sea level to 5,000 feet.
51°C to 70C
Above 5,000 ft
Min
Typ
Max
Units
Notes
-40
Shock and Vibration acceleration
Earthquake Rating
MTBF
July 20, 2012
©2012 General Electric Company. All rights reserved.
Page 3
GE Energy
CAR1212FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1250W; 5 Vdc @ 0.5A
EMC
Parameter
AC input
Criteria
Conducted emissions
Radiated emissions
Voltage dips
Standard
EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
EN55022
EN61000-4-11
Level
A*
A*
A
C
C
Test
0.15 – 30MHz
0 – 2 KHz
30 – 10000MHz
-30%, 10ms
-60%, 100ms
-100%, 5sec
4kV, 1.2/50µs, common mode
2kV, 1.2/50µs, differential mode
5/50ns, 2kV (common mode)
130dBµV, 0.15-80MHz, 80% AM
10V/m, 80-1000MHz, 80% AM
4kV contact, 8kV air
Voltage surge
immunity
Enclosure
immunity
Fast transients
Conducted RF fields
Radiated RF fields
ESD
EN61000-4-5
EN61000-4-4
EN61000-4-6
EN61000-4-3
ENV 50140
EN61000-4-2
A
A
B
A
A
A
B
* Note: Contact the factory for a recommended external EMI filter to meet Class B emissions
Status and Control
Details of analog controls are provided in this data sheet
under Signal Definitions. GE Energy will provide separate
application notes on the I2C protocol. Contact your local GE
Energy representative for details.
This signal is not overwritten by the firmware ON/OFF
instruction. The default firmware setting is ON. An OFF
command either through this signal or firmware would turn
OFF the power supply.
The default state re-initializes if bias power is interrupted to
the processor.
Enable:
This is a short signal pin that controls the presence
of the 12Vdc main output. This pin should be connected to
‘output return’ on the system side of the output connector.
The purpose of this pin is to ensure that the output turns ON
after engagement of the power blades and turns OFF prior
to disengagement of the power blades.
Write protect (WP):
This signal protects the contents of the
EEPROM from accidental over writing. When left open the
EEPROM is write protected. A LO (TTL compatible) permits
writing to the EEPROM. This signal is pulled HI internally by
the power supply. Used only for factory programming
Signal Definitions
All signals and outputs are referenced to Output return.
These include ‘Vstb return’ and ‘Signal return’.
Input Signals
Voltage programming (V
prog
):
An analog voltage on this
signal can vary the output voltage ± 5% from 11.4Vdc to
12.6Vdc. The equation of this signal is:
V
out
= 11.4 + (V
prog
* 0.3) 0 < V
prog
< 4
If Vprog is > 4V or left open the programming signal is
ignored and the unit output is set at the setpoint of 12Vdc.
Load share (Ishare):
This is a single wire analog signal that is
generated and acted upon automatically by power supplies
connected in parallel. The Ishare pins should be tied
together for power supplies if active current share among
the power supplies is desired. No resistors or capacitors
should get connected to this pin.
Remote ON/OFF:
Controls the presence of the main 12Vdc
output voltage. This is an open collector, TTL level control
signal. This signal needs to be pulled HI externally through a
resistor. Maximum collector voltage is 12Vdc and the
maximum sink current is 20mA. A Logic 1 (TTL HI level)
turns ON the 12Vdc output, while a Logic 0 (TTL LO level)
turns OFF the 12Vdc output.
Output signals
Output current monitor (Imon):
A voltage level of 0.05V / A
proportional to the delivered output current is present on
this pin. Accuracy ±10% of FL at loads > 25% of FL.
AC OK:
A TTL compatible status signal representing whether
the input voltage is within the anticipated range. This signal
needs to be pulled HI externally through a resistor.
Maximum sink current
≤
20mA and the max voltage is
12Vdc. Open collector (HI) on this signal indicates that the
input voltage is applied within the specified input range.
DC OK:
A TTL compatible status signal representing
whether the output voltage is present. This signal needs to
be pulled HI externally through a resistor. Maximum sink
July 20, 2012
©2012 General Electric Company. All rights reserved.
Page 4
GE Energy
CAR1212FP series rectifier
Input: 85Vac to 264Vac; Output: 12 Vdc @ 1250W; 5 Vdc @ 0.5A
current
≤
20mA and the max voltage is 12Vdc. Open
collector (HI) on this signal indicates that the output voltage
is present.
Over temp warning:
A TTL compatible status signal
representing whether an over temperature exists. This signal
needs to be pulled HI externally through a resistor.
Maximum sink current
≤
20mA and the max voltage is
12Vdc. Open collector (HI) on this signal indicates that
temperatures are normal.
If an over temperature should occur, this signal would pull
LO for approximately 10 seconds prior to shutting down the
power supply. The unit would restart if internal temperatures
recover within normal operational levels. At that time the
signal reverts back to its open collector (HI) state.
Fault:
A TTL compatible status signal representing whether
a Fault occurred. This signal needs to be pulled HI externally
through a resistor. Maximum sink current
≤
4mA and the
max voltage is 12Vdc. Open collector (HI) on this signal
indicates that no Fault is present.
This signal activates for OTP, OVP, OCP, AC fault or No
output.
PS Present:
This pin is connected to ‘output return’ within the
power supply. Its intent is to indicate to the system that a
power supply is present. This signal may need to be pulled
HI externally through a resistor.
Interrupt (SMBAlert):
A TTL compatible status signal,
representing the SMBusAlert# feature of the PMBus
compatible i
2
C protocol in the power supply. This signal
needs to be pulled HI externally through a resistor.
Maximum sink current
≤
4mA and the pull up resistor should
be tied to 3.3Vdc. Open collector (HI) on this signal indicates
that no Interrupt has been triggered.
pulled HI internal to the power supply. For a logic LO these
pins should be connected to ‘Output Return’
Serial Clock (SCL):
The clock pulses on this line are generated
by the host that initiates communications across the I²C
Serial bus. This signal is not pulled up internally. The end
user should add pull up resistance to 5Vdc as necessary to
ensure that rise and fall time timing and the maximum sink
current is in compliance to the I²C specifications.
Serial Data (SDA):
This line is a bi-directional data line. . This
signal is not pulled up internally . The end user should add
pull up resistance to 5Vdc as necessary to ensure that rise
and fall time timing and the maximum sink current is in
compliance to the I²C specifications.
Communications Protocol
The I²C protocol is described in detail by the
I
2
C and PMBus
Serial Communications Protocol for the CAR Family of Power
Supplies
application note.
The Y01A suffix module supports only the
I
2
C
command set.
I/O Expander option (PCF8574ATD-T)
The CAR1212FPx without extended i2c communications
(blank under the software option) has a single status/control
byte I/O expander that is accessible via default address
0 x 7Eh (A2, A1, A0 are pilled HI). This byte takes the form;
7
n/s
6
n/s
5
Fault
4
ON/OFF
3
Temp_OK
2
n/s
1
DCOK
0
ACOK
n/s – not supported
Bits 0, 1, 3, and 5 are ‘read_only’ and are HI [1] during normal
operation. The rectifier needs to be biased externally in order to
‘read’ its operational state without the presence of input power.
Bit 4 is a ‘read/write’ bit that can be used to verify the ON/OFF
commanded state or change the commanded output of the
rectifier. In order to turn the output OFF this bit needs to be pulled
LO [0].
No PEC support is provided. Standard i
2
c commands apply.
Serial Bus Communications
The I²C interface facilitates the monitoring and control of
various operating parameters within the unit and transmits
these on demand over an industry standard I²C Serial bus.
All signals are referenced to ‘Signal Return’.
Device addressing:
The microcontroller (MCU) and the
EEPROM have the following addresses:
Device
MCU
EEPROM
Address
0xBx
0xAx
1
1
Address Bit Assignments
(Most to Least Significant)
0
1
1 A2 A1 A0
0
1
0 A2 A1 A0
LEDs
Three LEDs are located on the front faceplate. The AC_OK
LED provides visual indication of the INPUT signal function.
When the LED is ON GREEN the power supply input is within
normal design limits.
R/W
R/W
When the DC_OK LED is GREEN the DC output is present.
When the FAULT_LED is RED then a fault condition exists
and the power supply may not provide output power. The
table below further defines these states:
Address lines (A2, A1, A0):
These signal pins allow up to eight
(8) modules to be addressed on a single I²C bus. The pins are
July 20, 2012
©2012 General Electric Company. All rights reserved.
Page 5