Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8467 Multi-Conductor - Audio, Control and Instrumentation Cable
For more Information
please call
1-800-Belden1
General Description:
18 AWG stranded (19x30) tinned copper conductors, conductors cabled, PVC insulation, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
7
18
19x30
TC - Tinned Copper
7
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material
Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.018
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride .037
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1
2
3
4
5
6
7
Black
White
Red
Green
Brown
Blue
Orange
0.309 in.
Overall Nominal Diameter:
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +60°C
60°C (UL AWM Style 2598)
69 lbs/1000 ft.
146 lbs.
3.250 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
NEC Articles:
CEC/C(UL) Specification:
AWM Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
CMG
800
CMG
UL Style 2598 (300 V 60°C)
Yes
Yes
Yes
Yes
Page 1 of 2
08-12-2014
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
8467 Multi-Conductor - Audio, Control and Instrumentation Cable
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
04/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
CSA Flame Test:
UL1685 FT4 Loading
FT4
Suitability
Suitability - Indoor:
Yes
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
26
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
6.3
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Description
Current
10C Temperature Rise 3.5 Amps per conductor @ 25°C ambient
Put Ups and Colors:
Item #
8467 060100
8467 0601000
8467 06010000
8467 060250
8467 060500
8467 0605000
Notes:
C = CRATE REEL PUT-UP.
Putup
100 FT
1,000 FT
10,000 FT
250 FT
500 FT
5,000 FT
Ship Weight
7.700 LB
74.000 LB
750.000 LB
18.750 LB
40.500 LB
365.000 LB
Color
CHROME
CHROME
CHROME
CHROME
CHROME
CHROME
C
C
C
Notes
Item Desc
7 #18 PVC PVC
7 #18 PVC PVC
7 #18 PVC PVC
7 #18 PVC PVC
7 #18 PVC PVC
7 #18 PVC PVC
Revision Number: 5
© 2014 Belden, Inc
All Rights Reserved.
Revision Date: 08-05-2013
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 2 of 2
08-12-2014