SmartOnline 8kVA On-Line Double-Conversion
UPS, 8U Rack/Tower, 208/120V NEMA outlets
MODEL NUMBER:
SU8000RT3U1TF
Highlights
8kVA / 8000VA / 7200W on-line
double-conversion UPS, 0.9
output power factor
208/120V +/-2% output at 60Hz,
High efficiency economy mode
option
8U Rack/Tower compatible,
Hot-swap power and battery
modules
USB, RS232, EPO ports, Support
for SNMP/WEB and other card
options
Front panel LEDs with detailed
LCD monitoring and control
screen
Expandable runtime with optional
external battery packs
Description
Tripp Lite SU8000RT3U1TF 8000VA / 8kVA / 7200 watt online, double-conversion UPS system offers complete
power protection for critical network applications. This system delivers online, double-conversion UPS protection
with zero transfer time, suitable for advanced networking applications. Fault-tolerant auto-bypass prevents
unexpected service interruptions during UPS overload or internal fault conditions. Included detachable PDU with
manual bypass switch enables hot-swappable replacement of entire UPS power module with no interruption to
connected equipment. Enhanced availability, fault tolerance and simple hot-swap replacement options make this
UPS ideal for advanced networking applications in data centers, computer rooms, network closets and rugged
industrial locations.
Hardwire input (3 wire), L6-30R,
L6-20R & 5-15/20R outlets
Package Includes
SU8000RT3UPM 3U UPS power
module
BP240V10RT3U external battery
pack
SU5000XFMRT2U step down
transformer
Features
Tripp Lite SU8000RT3U1TF 8kVA / 8000VA / 7200 watt on-line, double-conversion UPS system in 8U total
rack/tower configuration (3U UPS power module, 3U external battery pack and 2U step-down transformer)
Detachable PDU with manual bypass switch enables hot-swappable UPS power module replacement with no
interruption in output power to connected networking equipment
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Hardwire input; 2 L6-30R, 4 L6-20R and 12 5-15/20R outlets
Maximum installed rack depth of only 32.5 in. / 82.6cm inches
Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage
fluctuations, power interruptions and line noise
SUPDMB710 Detachable PDU
with manual bypass switch
Four post compatible rack rail kit
(3 sets)
Tower stands for upright tower
configuration
PowerAlert software, complete
data cabling and user manual
Double-conversion operation converts raw input from AC to DC, then re-synthesizes output power back to perfect sine wave AC with enhanced protection
from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types
Maintains full-time sine wave output within 2% of 208/120V nominal at 60Hz during brownouts as low as 100V and overvoltages as high as 300V
Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH
external battery packs
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs
1/7
Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and
require replacement
PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as UPS batteries
become depleted
Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (Network
Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250 SNMP-enabled UPS, PDU and other
networking devices
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification
Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB
interface module)
Supports Emergency Power Off (EPO) via built-in interface
Included rail kit supports 8U 19 inch rackmount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks
Optional 2-9USTAND supports upright tower placement
Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and advanced UPS
settings for charge level, nominal voltage selection, frequency conversion and other operational parameters
LED / LCD display panel rotates for viewing in rackmount or tower configurations
Network-grade AC surge and noise suppression
Industrial mode option (factory preset) enables supports high current startup loads by momentarily switching to bypass mode in response to short duration
overload conditions
External battery packs are field replaceable and hot swappable
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA capacity (kVA)
Output Watt Capacity (watts)
Output kW capacity
Output power factor
Output Capacity Details
Nominal Output Voltage(s)
Supported
Nominal Voltage details
Frequency compatibility
8000
8
7200
7.2
0.9
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less
120V; 208V
7200 watts total output supported; 5000 watts maximum 120V output; add 1 additional SU5000XFMRT2U
transformer for full load 120V operation.
60 Hz
2/7
Frequency compatibility details
Output voltage regulation (line mode)
Output voltage regulation (Economy
line mode)
Output voltage regulation (Battery
mode)
Built-in UPS output receptacles
Output circuit breaker
Output AC waveform (AC mode)
Output AC waveform (battery mode)
Output frequency regulation +/- 0.05Hz (free running)
+/- 2%
+/- 10%
+/- 2%
12 5-15/20R outlet(s); 4 L6-20R outlet(s); 2 L6-30R outlet(s)
20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlets each, 20A
single-pole (x4) protect 3 5-15/20R outlets each
Pure Sine wave
Pure Sine wave
INPUT
Rated input current (at maximum
load)
Nominal Input Voltage(s) Supported
UPS input connection type
UPS input connection description
Recommended Electrical Service
Phase
44.2A (208V)
208V AC
Hardwire
3 wire single phase input (L1, L2, G)
208V 50A
Single-Phase
BATTERY
Full load runtime (minutes)
Half load runtime (minutes)
Expandable battery runtime
External battery pack compatibility
DC system voltage (VDC)
Battery recharge rate (included
batteries)
Battery replacement description
5.5 min. (7200w)
13.5 min. (3600w)
Supports extended runtime with optional external battery packs
BP240V10RT3U; BP240V557C-1PH
;
BP240V787C-1PH
;
BP240V1037C-1PH; BP240V1407C-1PH
240
Less than 6 hours from 10% to 90%
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Undervoltage correction
2% output voltage regulation in standard online, double-conversion mode
Corrects overvoltages up to 300V
Corrects undervoltages as low as 100V
LEDS ALARMS & SWITCHES
LED Indicators
6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
3/7
Front panel LCD display
Alarms
Alarm cancel operation
Switches
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN,
ITALIAN, SPANISH and PORTUGUESE (see manual)
Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel switch
2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module
replacement
SURGE / NOISE SUPPRESSION
UPS AC suppression response time
EMI / RFI AC noise suppression
Instantaneous
Yes
ISOLATION
Output isolation transformer
120V output is isolation transformer protected
PHYSICAL
Installation form factors supported
with included accessories
Included mounting accessory
description
Installation form factors supported
with optional accessories
Optional mounting accessory notes
Primary form factor
UPS / Power Module dimensions in
primary form factor (height x width x
depth / inches)
UPS / Power Module dimensions in
primary form factor (height x width x
depth / cm)
Installed whole system maximum
rack depth (inches)
Installed whole system maximum
rack depth (cm)
Rack Height
Secondary form factor
UPS / Power Module weight (lbs)
UPS / Power Module weight (kg)
Stepdown transformer dimensions
(height x width x depth / inches)
Stepdown transformer dimensions
(height x width x depth / cm)
Tower
3 sets of adjustable 4 post rack rails included; 2-9USTAND tower kit included (supports up to 9U in tower format)
2 post rackmount (2POSTRMKITHD)
3 sets of
2POSTRMKITHD
required for 2 post rackmount installation of separate power module, battery pack and
transformer
Rackmount
5.14 x 17.5 x 25.82
13.1 x 44.4 x 65.6
32.5
82.6
8U
Tower
43
19.5
3.5 x 17.5 x 20.8
8.9 x 44.4 x 63.5
4/7
Stepdown transformer weight (lbs)
Stepdown transformer weight (kg)
Included battery pack dimensions
(height x width x depth / inches)
Included battery pack dimensions
(height x width x depth / cm)
Included battery pack weight (lbs)
Included battery pack weight (kg)
UPS Shipping dimensions (height x
width x depth / inches)
UPS Shipping dimensions (height x
width x depth / cm)
Shipping weight (lbs)
Shipping weight (kg)
Cooling method
UPS housing material
57
25.9
5.25 x 17.5 x 25
13.3 x 44.4 x 63.5
158.7
72
49.25 x 23 x 31.5
125.1 x 58.4 x 80
402.2
182.6
Fan
Steel
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC mode BTU / hr. (full load)
AC economy mode BTU / hr. (full
load)
AC mode efficiency rating (100%
load)
AC economy mode efficiency rating
(100% load)
Operating Elevation (ft.)
Audible Noise
Operating Elevation (m)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
2732
1020
91%
96%
0-3000m (0 to 10,000 ft.)
60 dBA at front side 1 meter
0-3000 m
COMMUNICATIONS
Communications interface
Network monitoring port description
PowerAlert software
Communications cable
WatchDog compatibility
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports
Included
USB, DB9 serial and EPO cables included
Supports Watchdog application, OS and hard-reboot restart options for remote applications