Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5320UL Multi-Conductor - Commercial Applications - 2 Conductors Cabled
For more Information
please call
1-800-Belden1
Description:
18 AWG bare copper conductors, PP insulation, conductors cabled together, PVC jacket with ripcord,
sequential footage marking every two feet.
Usage (Overall)
Suitable Applications:
Fire Protections, Alarm, Signal, Monitor/Detection, Audio Circuits, Control
Circuits, Initiating Circuits, Notification Circuits
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
2
18
Solid
BC - Bare Copper
Insulation
Insulation Material:
Insulation Material Wall Thickness (in.)
PP - Polypropylene 0.007
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride 0.017
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Length (in.) Twists (ft.)
3
4
Overall Cabling Color Code Chart:
Number Color
1
2
Black
Red
Overall Nominal Diameter:
0.143 in.
Mechanical Characteristics (Overall)
Operating Temperature Range:
UL Temperature Rating:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius (Install)/Minor Axis:
-20°C To +75°C
75°C
15.900 lbs/1000 ft.
39.200 lbs.
1.500 in.
Page 1 of 3
02-24-2012
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5320UL Multi-Conductor - Commercial Applications - 2 Conductors Cabled
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
NEC Articles:
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Other Specification:
FPLR
760
Yes
Yes
Yes
04/01/2005
Yes
Yes
Yes
Yes
California State Fire Marshall
Flame Test
UL Flame Test:
CSA Flame Test:
UL1666 Vertical Shaft
FT4
Plenum/Non-Plenum
Plenum (Y/N):
Plenum Number:
No
6320UL
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/ft)
.16
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
29
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
6.4
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
5 Amps per conductor @ 25°C
Related Documents:
No related documents are available for this product
Put Ups and Colors:
Item #
5320UL D15C500
5320UL D151000
5320UL 001U1000
5320UL 002U1000
5320UL 002U500
5320UL 0021000
5320UL 010U1000
Putup
500 FT
1,000 FT
1,000 FT
1,000 FT
500 FT
1,000 FT
1,000 FT
Ship Weight
7.000 LB
16.000 LB
16.000 LB
16.000 LB
8.500 LB
16.000 LB
16.000 LB
Color
BLUE
BLUE
BROWN
RED
RED
RED
BLACK
C
C
Notes
Item Desc
2 #18 PP FRPVC
2 #18 PP FRPVC
2 #18 PP FRPVC
2 #18 PP FRPVC
2 #18 PP FRPVC
2 #18 PP FRPVC
2 #18 PP FRPVC
Page 2 of 3
02-24-2012
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5320UL Multi-Conductor - Commercial Applications - 2 Conductors Cabled
5320UL 0101000
Notes:
C = CRATE REEL PUT-UP.
1,000 FT
16.000 LB
BLACK
2 #18 PP FRPVC
Revision Number: 3
© 2012 Belden, Inc
All Rights Reserved.
Revision Date: 07-24-2009
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3
02-24-2012