Current Transducer
Hall Effect
Features:
•
•
•
•
•
•
•
•
•
•
Highly reliable hall effect device.
Compact and light weight.
Fast response time.
Excellent linearity of the output voltage over a wide input range.
Excellent frequency response (> 50 KHz).
Low power consumption (12 mA nominal).
Capable of measuring both DC and AC, both pulsed and mixed.
High isolation voltage between the measuring circuit and the current-carrying conductor
(2.5 KV ac).
Extended operating temperature range.
Flame-Retardant plastic case and silicone encapsulate, using UL classified materials, ensures
protection against environmental contaminants and vibration over a wide temperature and
humidity range.
Applications
•
•
•
•
•
•
•
•
•
•
•
•
•
UPS systems.
Industrial robots.
NC tooling machines.
Elevator controllers.
Process control devices.
AC and DC servo systems.
Motor speed controller.
Electrical vehicle controllers.
Inverter-controlled welding machines.
General and special purpose inverters.
Power supply for laser processing machines.
Controller for traction equipment eg. electric trains.
Other automatic control systems.
Specification Table
Parameter
Nominal Input Current
Linear Range
Nominal Output Voltage
Offset Voltage
Output Resistance
Hysteresis Error
Supply Voltage
Linearity
Consumption Current
Response Time (90% V
hn
)
Frequency Bandwidth (-3dB)
Thermal Drift of Output
Thermal Drift of Zero Current Offset
Dielectric Strength
Isolation Resistance 1,000 V dc
Symbol
I
fn
I
fs
V
hn
V
os
R
OUT
V
oh
V
CC
/ V
EE
ρ
I
CC
T
r
f
BW
-
-
-
R
IS
Unit
A dc
V
mV
Ω
mV
V
%
mA
µs
Hz
% / °C
mV / °C
V
MΩ
TMA50A
±50
±150
TMA100A
±100
±300
TMA200A
±200
±600
TMA400A
±400
±900
4 V ±1% at If = I
fn
(R
L
= 10 KΩ)
Within ±40 mV at I
f
= 0, T
a
= 25°C
< 100
Ω
Within ±20 mV at I
f
= I
fn
→
0
±15 V ±5%
Within ±1% of I
fn
±15 mA Max.
10 µs at d I
f
/ dt = I
fn
/ µs
DC to 50 KHz
Within ±0.1% / °C at I
fn
Within ±1.5 mV / °C at I
fn
2.5 KV ac × 60 s
> 1,000 MΩ
www.element14.com
www.farnell.com
www.newark.com
Page <1>
06/06/11 V1.1
Current Transducer
Hall Effect
Specification Table
Parameter
Operating Temperature
Storage Temperature
Mass
Symbol
T
a
T
s
W
Unit
°C
g
TMA50A
TMA100A
TMA200A
TMA400A
-15°C to 80°C
-20°C to 85°C
65 g
Appearance, Dimensions and Pin Identification
All dimensions in mm ±0.1, holes –0, +0.2 except otherwise noted
Pin Assignment
1
2
3
4
+15 V
-15 V
V
OUT
0V
Positive current flow direction
Part Number Table
Description
Current Transducer
Current Transducer
Current Transducer
Current Transducer
Part Number
TMA400A
TMA200A
TMA50A
TMA100A
Dimensions : Millimetres
Important Notice :
This data sheet and its contents (the "Information") belong to the members of the Premier Farnell group of companies (the "Group") or are licensed to it. No licence is granted for the use of
it other than for information purposes in connection with the products to which it relates. No licence of any intellectual property rights is granted. The Information is subject to change without notice and replaces
all data sheets previously supplied. The Information supplied is believed to be accurate but the Group assumes no responsibility for its accuracy or completeness, any error in or omission from it or for any use
made of it. Users of this data sheet should check for themselves the Information and the suitability of the products for their purpose and not make any assumptions based on information included or omitted.
Liability for loss or damage resulting from any reliance on the Information or use of it (including liability resulting from negligence or where the Group was aware of the possibility of such loss or damage arising)
is excluded. This will not operate to limit or restrict the Group's liability for death or personal injury resulting from its negligence. Multicomp is the registered trademark of the Group. © Premier Farnell plc 2011.
www.element14.com
www.farnell.com
www.newark.com
Page <2>
06/06/11 V1.1