Print
-
Create PDF
-
Create EXCEL file
20.04.2011
-
18:31:35h
Datasheet - SRB 402EM-24V
Output expanders / SRB 402EM
• Expander module for contact expansion
• 4 safety contacts, STOP 0
• 2 Signalling outputs
(Minor differences between the printed image and the original product
may exist!)
Ordering details
Product type description
Article number
EAN code
SRB 402EM-24V
1175611
4030661307909
Approval
Approval
USA/CAN
Classification
Standards
PL
Control category
DC
CCF
PFH value
- notice
SIL
Mission time
- notice
EN ISO 13849-1, IEC 61508, EN 60947-5-1
up e (STOP 0)
up 4 (STOP 0)
99% (STOP 0)
> 65 points
≤ 2,0.0 x 10
-8
/h (STOP 0)
up to max. 36500 switching cycles/year and at max. 60% contact load
up 3 (STOP 0)
20 Years
Global Properties
Product name
Standards
Compliance with the Directives (Y/N)
Climatic stress
Mounting
Terminal designations
Materials
- Material of the housings
- Material of the contacts
Weight
Start conditions
Start input (Y/N)
Feedback circuit (Y/N)
Start-up test (Y/N)
Reset after disconnection of supply voltage (Y/N)
Automatic reset function (Y/N)
Reset with edge detection (Y/N)
Pull-in delay
- ON delay with automatic start
Drop-out delay
- Drop-out delay in case of emergency stop
≤ 35 ms
30 ms
Plastic, glass-fibre reinforced thermoplastic, ventilated
, self-cleaning, positive action
250 g
Automatic
No
Yes
No
No
Yes
No
SRB 402EM
EN 60204-1, EN 60947-5-1, EN ISO 13849-1, IEC 61508
Yes
EN 60068-2-78
snaps onto standard DIN rail to EN 60715
IEC/EN 60947-1
Mechanical data
Connection type
Cable section
- Min. Cable section
- Max. Cable section
Pre-wired cable
Tightening torque for the terminals
Detachable terminals (Y/N)
Mechanical life
Electrical lifetime
restistance to shock
Resistance to vibration To EN 60068-2-6
0,25 mm²
2.5 mm²
rigid or flexible
0,6 Nm
Yes
10.000.000 operations
Derating curve available on request
30 g / 11 ms
10...55 Hz, Amplitude 0,35 mm, ± 15 %
Screw connection
Ambient conditions
Ambient temperature
- Min. environmental temperature
- Max. environmental temperature
Storage and transport temperature
- Min. Storage and transport temperature
- Max. Storage and transport temperature
Protection class
- Protection class-Enclosure
IP40
−40 °C
+85 °C
−25 °C
+45 °C
- Protection class-Terminals
- Protection class-Clearance
Air clearances and creepage distances To IEC/EN 60664-1
- Rated impulse withstand voltage U
imp
- Overvoltage category
- Degree of pollution
IP20
IP54
4 kV
III To VDE 0110
2 To VDE 0110
Electromagnetic compatibility (EMC)
EMC rating
conforming to EMC Directive
Electrical data
Rated DC voltage for controls
- Min. rated DC voltage for controls
- Max. rated DC voltage for controls
Rated AC voltage for controls, 50 Hz
- Min. rated AC voltage for controls, 50 Hz
- Max. rated AC voltage for controls, 50 Hz
Rated AC voltage for controls, 60 Hz
- Min. rated AC voltage for controls, 60 Hz
- Max. rated AC voltage for controls, 60 Hz
Contact resistance
Power consumption
Type of actuation
Rated operating voltage U
e
Operating current I
e
Frequency range
Electronic protection (Y/N)
Fuse rating for the operating voltage
20.4 V
26.4 V
max. 100 mΩ
1.0 W; 1.0 VA
AC/DC
24 VDC −15% / +20%, residual ripple max. 10%;
24 VAC −15% / +10%
0,05 A
50 / 60 Hz
No
1.0 A slow blow
20.4 V
26.4 V
20.4 V
28.8 V
Inputs
Monitored inputs
- Short-circuit recognition (Y/N)
- Wire breakage detection (Y/N)
- Earth connection detection (Y/N)
Number of shutters
Number of openers
Cable length
Conduction resistance
No
Yes
Yes
0 piece
1 piece
1500 m with 1.5 mm²;
2500 m with 2.5 mm² (for Rated voltage)
max. 40 Ω
Outputs
Stop category
Number of safety contacts
Number of auxiliary contacts
Number of signalling outputs
Switching capacity
- Switching capacity of the safety contacts
- Switching capacity of the auxiliary contacts
Fuse rating
max. 250 VAC, 6 A ohmic (inductive in case of appropriate protective wiring)
24 VDC, 2 A
0
4 piece
2 piece
0 piece
- Protection of the safety contacts
- Fuse rating for the auxiliary contacts
Utilisation category To EN 60947-5-1
Number of undelayed semi-conductor outputs with signaling
function
Number of undelayed outputs with signaling function (with
contact)
Number of delayed semi-conductor outputs with signaling
function.
Number of secure undelayed semi-conductor outputs with
signaling function
6 A gG D-fuse
2 A slow blow
depending on the connected safety relay module
0 piece
2 piece
0 piece
Number of delayed outputs with signalling function (with contact). 0 piece
0 piece
Number of secure, undelayed outputs with signaling function, with
contact.
4 piece
Number of secure, delayed semi-conductor outputs with signaling
function
0 piece
Number of secure, delayed outputs with signaling function (with
contact).
0 piece
LED switching conditions display
LED switching conditions display (Y/N)
Number of LED´s
LED switching conditions display
- The integrated LEDs indicate the following operating states.
- Position relay K1/K2
Yes
1 piece
Miscellaneous data
Applications
Output expanders
depending on the connected safety relay module
Dimensions
Dimensions
- Width
- Height
- Depth
22.5 mm
100 mm
121 mm
notice
Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit.
notice - Wiring example
Relay outputs:
1-channel control of the expander module is suitable for contact reinforcement or multiplication of the connected safety relay
module.
Terminals X1 and X2 of the expander module must be connected to the feedback circuit or reset circuit of the safety relay module.
The wiring diagram shows the control of the expander module by a SRB... safety relay module with the guard doors closed and in de-energised
condition.
Documents
Operating instructions and Declaration of conformity
(jp) 559 kB, 29.03.2011
http://127.0.0.1/Bilddata/Si_baust/Pdf/srb402em/bedien/jp/mrl_srb_402em_jp.pdf
Operating instructions and Declaration of conformity
(es) 535 kB, 08.02.2011
http://127.0.0.1/Bilddata/Si_baust/Pdf/srb402em/bedien/es/mrl_srb_402em_es.pdf
Operating instructions and Declaration of conformity
(it) 528 kB, 08.02.2011
http://127.0.0.1/Bilddata/Si_baust/Pdf/srb402em/bedien/it/mrl_srb_402em_it.pdf
Operating instructions and Declaration of conformity
(nl) 529 kB, 08.02.2011
http://127.0.0.1/Bilddata/Si_baust/Pdf/srb402em/bedien/nl/mrl_srb_402em_nl.pdf
Operating instructions and Declaration of conformity
(en) 706 kB, 21.01.2010
http://127.0.0.1/Bilddata/Si_baust/Pdf/srb402em/bedien/EN/mrl_srb_402em_en.pdf
Operating instructions and Declaration of conformity
(de) 919 kB, 05.07.2010
http://127.0.0.1/Bilddata/Si_baust/Pdf/srb402em/bedien/DE/mrl_srb_402em_de.pdf
Wiring example
(99) 15 kB, 04.08.2008
http://127.0.0.1/Bilddata/Si_baust/srb402em/schaltun/ksrb4l02.pdf
Images
Wiring example
K.A. Schmersal GmbH, Möddinghofe 30, D-42279 Wuppertal
The data and values have been checked throroughly. Technical modifications and errors excepted.
Generiert am 20.04.2011 - 18:31:35h Kasbase 1.4.7 DBI