Product availability : Non-Stock - Not normally stocked in distribution facility
Price* : 1,403.00 USD
Main
Range
Product name
Device short name
Product or component type
Device application
PowerPact
PowerPact B
BJ 050
Circuit breaker
Distribution
Complementary
Line Rated Current
Number of Poles
Protected poles description
Control type
Breaking capacity code
Breaking capacity
50 A
2P
2t
Toggle
J
100 kA at 240 V AC 50/60 Hz according to UL 489
100 kA at 480 V AC 50/60 Hz according to UL 489
Icu : 65 kA at 480/277 V AC 50/60 Hz according to IEC 60947-2
10 kA at 250 V DC 50/60 Hz according to UL 489
100 kA at 600Y/347 V AC 50/60 Hz according to UL 489
65 kA at 600 V AC 50/60 Hz according to UL 489
25 kA at 125 V DC 50/60 Hz according to UL 489
690 V AC 50/60 Hz according to IEC 60947-2
600Y/347 V AC 50/60 Hz according to UL 489
125 V DC 50/60 Hz according to UL 489
250 V DC 50/60 Hz according to UL 489
100 kA: at 220...240 V AC 50/60 Hz according to IEC 60947-2
65 kA: at 380...415 V AC 50/60 Hz according to IEC 60947-2
65 kA: at 440 V AC 50/60 Hz according to IEC 60947-2
25 kA: at 500...525 V AC 50/60 Hz according to IEC 60947-2
10 kA: at 690 V AC 50/60 Hz according to IEC 60947-2
8 kV according to IEC 60947-2
800 V according to IEC 60947-2
1
System Voltage
[Ics] rated service breaking capacity
[Uimp] rated impulse withstand voltage
[Ui] rated insulation voltage
May 3, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Trip unit technology
Trip unit name
Suitability for isolation
Utilisation category
Mechanical durability
Electrical durability
Connection pitch
Local signalling
Mounting mode
Electrical connection
AWG gauge
Tightening torque
Number of slots
Power wire stripping length
Color
9 mm pitches
Height
Width
Depth
Product weight
Quantity per set
Continuous current rating
Thermal-magnetic
TM-D
Yes according to IEC 60947-2
Category A
20000 cycles according to IEC 947-1 Annex K ed 5.2
10000 cycles according to IEC 947-1 Annex K ed 5.2 In at 440 V
1.06 in (27 mm)
Green flag presence of auxiliary contacts
By screws plate
Clip-on 35 x 15 mm symmetrical DIN rail
Everlink lug at line
Everlink lug at load
AWG 6...AWG 2/0 fine stranded (aluminium/copper)
AWG 14...AWG 3/0 rigid or stranded (aluminium/copper)