Product datasheet
Characteristics
M9U21140
Multi 9 - C60H-DC - MCB - 1P - 40 A - C Curve -
250 V DC - 10 kA
Range
Product name
Product or component type
Device short name
Device application
Poles description
Number of protected poles
[In] rated current
Network type
Trip unit technology
Curve code
Breaking capacity
Multi 9
Multi 9 C60H-DC
Miniature circuit-breaker
C60H-DC
Distribution
1P
1
40 A at 25 °C conforming to EN/IEC 60947-2
DC
Thermal-magnetic
C
10 kA Icu at 220 V DC conforming to EN/IEC 60947-2
6 kA Icu at 250 V DC conforming to EN/IEC 60947-2
20 kA Icu at 110 V DC conforming to EN/IEC 60947-2
5 kA AIR at 12...250 V DC conforming to UL 1077
10 kA Icu at 220 V DC conforming to GB 14048.2
6 kA Icu at 250 V DC conforming to GB 14048.2
20 kA Icu at 110 V DC conforming to GB 14048.2
Category A conforming to EN/IEC 60947-2
Yes conforming to EN/IEC 60947-2
EN/IEC 60947-2
GB 14048.2
UL 1077
IEC
CCC
UR
Utilisation category
Suitability for isolation
Standards
Product certifications
Complementary
[Ue] rated operational voltage
250 V DC
110 V DC
220 V DC
7...10 x In DC
7.5 kA 75 % conforming to EN/IEC 60947-2 - 220 V DC
4.5 kA 75 % conforming to EN/IEC 60947-2 - 250 V DC
15 kA 75 % conforming to EN/IEC 60947-2 - 110 V DC
7.5 kA 75 % conforming to GB 14048.2 - 220 V DC
1
Magnetic tripping limit
[Ics] rated service breaking capacity
Aug 17, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
4.5 kA 75 % conforming to GB 14048.2 - 250 V DC
15 kA 75 % conforming to GB 14048.2 - 110 V DC
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contact position indicator
Control type
Local signalling
Mounting mode
Mounting support
9 mm pitches
Height
Width
Depth
Net weight
Colour
Mechanical durability
Electrical durability
Provision for padlocking
Connections - terminals
DC conforming to EN/IEC 60947-2
6 kV conforming to EN/IEC 60947-2
Yes
Toggle
ON/OFF indication
Clip-on
DIN rail
2
81 mm
18 mm
73 mm
0.128 kg
Grey
20000 cycles
3000 cycles 250 V DC L/R = 2 ms
6000 cycles 250 V DC
Padlockable
Tunnel type terminal (top or bottom)1…35 mm² (AWG 18...AWG 2) - rigid stranded
Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 4) - flexible
Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 4) - flexible with ferrule
Tunnel type terminal (top or bottom) - 2 cable(s) 1…16 mm² (AWG 18...AWG 6) - rigid stranded
Tunnel type terminal (top or bottom) - 2 cable(s) 1…16 mm² (AWG 18...AWG 6) - flexible
Tunnel type terminal (top or bottom) - 2 cable(s) 1…16 mm² (AWG 18...AWG 6) - flexible with ferrule
Tunnel type terminal (top or bottom) - 3 cable(s) 4 mm² (AWG 6) - flexible stranded
14 mm for top or bottom connection
3.5 N.m top or bottom
Without
Wire stripping length
Tightening torque
Earth-leakage protection
Environment
Heat dissipation
IP degree of protection
Pollution degree
Tropicalisation
Relative humidity
Ambient air temperature for operation
Ambient air temperature for storage
4.3 W at 220 V - 40 A
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
3 conforming to EN/IEC 60947-2
2 conforming to IEC 60068-2
2 conforming to GB 14048.2
95 % at 55 °C
-25…70 °C
-40…85 °C
Offer Sustainability
REACh Regulation
REACh free of SVHC
EU RoHS Directive
Mercury free
RoHS exemption information
China RoHS Regulation
WEEE
REACh Declaration
Yes
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Yes
Yes
Download RoHS China Declaration
Product out of China RoHS scope. Substance declaration for your information
The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Contractual warranty
Warranty
18 months
2