High DC voltage ratings for critical industrial or commercial
applications that have specific current limitation requirements.
10X better current limitation helps prevent equipment damage
caused by short-circuit events
200kA AC Interrupting ratings comply with NEC
®
Section 110.9
for today’s large capacity systems
20kA DC interrupting ratings help meet the needs of protecting
higher ampacity DC circuits
Incorporates Class R rejection feature. Can be inserted in non-
rejection type fuse holders to physically and electrically replace
fast-acting Class H, K1, K5, RK5, and other fast-acting fuses.
2"
(± 0.31)
0.56" (± 0.008)
1/10 to 30A
Recommended fuse blocks:
Fuse amps
0-30
35-60
0-30
35-60
1-pole
RM25030-1_
RM25060-1_
RM60030-1_
RM60060-1_
2-pole
250V KWN-R
RM25030-2_
RM25060-2_
RM60030-2_
RM60060-2_
RM25030-3_
RM25060-3_
RM60030-3_
RM60060-3_
3-pole
3"
(± 0.31)
0.81" (± 0.008)
35 to 60A
600V KWS-R
600V KWS-R
See data sheet No. 10289 for details.
Fuse reducers for Class R fuses:
Equipment
fuse clips
60A
100A
200A
Desired fuse
(case) size
30A
30A
60A
60A
Catalog numbers (pairs)
250V
NO.263-R
NO.213-R
NO.216-R
NO.226-R
600V
NO.663-R
NO.216-R
NO.616-R
NO.626-R
5"
(± 0.31)
0.81" (± 0.008)
1/10 to 30A
For additional information on Class R fuse reducers, see data sheet
No. 1118.
5.5"
(± 0.31)
1.06" (± 0.008)
35 to 60A
2
Eaton.com/bussmannseries
250V KWN-R and 600V KWS-R Class RK1 fuses
Technical Data
10413
Effective July 2015
Time-current curves — average melt
KWN-R and KWS-R
30A
60A
AMP RATING
300
100
10
TIME IN SECONDS
1
0.1
0.01
40
10,000
3
100
CURRENT IN AMPS
Eaton.com/bussmannseries
1000
Technical Data
10413
Effective July 2015
250V KWN-R and 600V KWS-R Class RK1 fuses
Current limitation curves
KWN-R and KWS-R
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
100,000
10,000
60
30
A
100,000
RMS SYMMETRICAL CURRENTS IN AMPS
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYM RMS AMPS)
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help
the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or
limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin.
Once a product has been selected, it should be tested by the user in all possible applications.
控制器局部网CAN(Controller Area Network)属于现场总线的一种,是一种有效支持分布式控制或实时控制的串行通信网络,被公认为是最有前途的现场总线之一。 在工业控制系统中,电动执行器是电动单元组合仪表中一个很重要的执行单元。它由控制电路和执行机构两个在电路上完全独立的部分组成,可接收来自调节器的电控信号,将其线性地转换成机械转角或直线位移,用来操纵风门、挡板、阀门等...[详细]