Product datasheet
Characteristics
CAD32GD
TeSys D control relay - 3 NO + 2 NC - <= 690 V -
125 V DC standard coil
Price* : 67.52 GBP
Main
Range
Product name
Product or component type
Device short name
Contactor application
TeSys
TeSys CAD
Control relay
CAD
Control circuit
Complementary
Utilisation category
AC-14
AC-15
DC-13
3 NO + 2 NC
<= 690 V AC 25...400 Hz
DC standard
125 V DC
6 kV conforming to IEC 60947
10 A at <= 60 °C
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
100 A 1 s
120 A 500 ms
140 A 100 ms
10 A gG conforming to IEC 60947-5-1
690 V conforming to IEC 60947-5-1
600 V certifications UL
600 V certifications CSA
Plate
Rail
Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end
1
Pole contact composition
[Ue] rated operational voltage
Control circuit type
[Uc] control circuit voltage
[Uimp] rated impulse withstand voltage
[Ith] conventional free air thermal
current
Irms rated making capacity
[Icw] rated short-time withstand current
Associated fuse rating
[Ui] rated insulation voltage
Mounting support
Connections - terminals
May 24, 2019
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end
Screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end
Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: solid - without cable end
Tightening torque
Control circuit voltage limits
Operating time
1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
0.1...0.25 Uc drop-out
0.7...1.25 Uc operational
15...25 ms coil de-energisation and NC closing
53...72 ms coil energisation and NO closing
16...24 ms coil de-energisation and NO opening
47...63 ms coil energisation and NC opening
30 Mcycles
180 cyc/mn
28 ms
5.4 W at 20 °C
5.4 W at 20 °C
17 V
5 mA
1.5 ms on de-energisation (between NC and NO contact)
1.5 ms on energisation (between NC and NO contact)
> 10 MOhm
Shocks control relay open 10 Gn for 11 ms IEC 60068-2-27
Shocks control relay closed 15 Gn for 11 ms IEC 60068-2-27
Vibrations control relay open 2 Gn, 5...300 Hz IEC 60068-2-6
Vibrations control relay closed 4 Gn, 5...300 Hz IEC 60068-2-6
77 mm
45 mm
93 mm
0.58 kg
Mechanical durability
Operating rate
Time constant
Inrush power in W
Hold-in power consumption in W
Minimum switching voltage
Minimum switching current
Non-overlap time
Insulation resistance
Mechanical robustness
Height
Width
Depth
Product weight
Environment
Standards
VDE 0660
IEC 60947-5-1
NF C 63-140
BS 4794
EN 60947-5
CSA
UL
IP2x front face conforming to VDE 0106
TH conforming to IEC 60068
-40...70 °C
-60...80 °C
3000 m without derating
Product certifications
IP degree of protection
Protective treatment
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
Offer Sustainability
Sustainable offer status
RoHS (date code: YYWW)
REACh
Product environmental profile
Product end of life instructions
Green Premium product
Compliant - since 0627 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Available
Product Environmental Profile
Available
End of Life Information
2