22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity
Aug 17, 2019
1
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Suitability for isolation
Utilisation category
Trip unit name
Trip unit technology
Trip unit protection functions
Earth-leakage add-on module name
Pollution degree
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
Category A
TM-D
Thermal-magnetic
LI
MH
3 conforming to IEC 60664-1
Complementary
Control type
Mounting mode
Mounting support
Upside connection
Downside connection
Mechanical durability
Electrical durability
Toggle
Fixed
Backplate
Front
Front
40000 cycles
10000 cycles 440 V In/2 conforming to IEC 60947-2
15000 cycles 690 V In/2 conforming to IEC 60947-2
20000 cycles 440 V In conforming to IEC 60947-2
7500 cycles 690 V In conforming to IEC 60947-2
35 mm
Positive contact indication
1 x Ir (4t)
L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
125 A at 40 °C
Adjustable
0.7...1 x In
Fixed
120…400 s at 1.5 x In
15 s at 6 x Ir
Fixed
1250 A
Fixed
Class A
With
Adjustable 5 settings
0.03…10 A
Adjustable 4 settings
236 mm
140 mm
86 mm
2.6 kg
NSX160
Connection pitch
Local signalling
Neutral protection setting
Protection type
Trip unit rating
Long time pick-up adjustment type Ir
Long time pick-up adjustment range
Long time delay adjustment type
[Tr] long-time delay adjustment range
Short-time pick-up adjustment type Isd
[Isd] short-time pick-up adjustment
range
Short-time delay adjustment type
Earth-leakage protection class
Earth-leakage protection
Residual earth-leakage sensitity
adjustment type
[IΔn] residual earth-leakage sensitive
adjustment
Residual earth-leakage time delay
adjustment type
Height
Width
Depth
Net weight
Compatibility code
Environment
Overvoltage category
Electrical shock protection class
Standards
Product certifications
Class II
Class II
EN/IEC 60947
UL 508
EAC
CCC
2
Marine
IP degree of protection
IK degree of protection
Ambient air temperature for operation
Ambient air temperature for storage
IP40 conforming to IEC 60529
IK07 conforming to IEC 62262
-35…70 °C
-55…85 °C
Offer Sustainability
Sustainable offer status
REACh Regulation
EU RoHS Directive
Mercury free
RoHS exemption information
China RoHS Regulation
Environmental Disclosure
Circularity Profile
WEEE
Green Premium product
REACh Declaration
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Yes
Yes
Download RoHS China Declaration
Product out of China RoHS scope. Substance declaration for your information
Product Environmental Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and